ICP iKAN-124, iKAN-116 User manual

  • Hello! I am an AI chatbot trained to assist you with the ICP iKAN-124 User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
WrittenbyTonyLee
EditedbySunnyChiu
iKANSeries
UserManual
Version1.0.1Jan.2016
iKANSeriesModbusLEDDisplayUserManualVersion1.0.1Page:2
Copyright©2016ICPDASCo.,Ltd.AllRightsReserved.Email:ser[email protected]om
Warranty
AllproductsmanufacturedbyICPDASareunderwarrantyregardingdefective
materialsforaperiodofoneyear,beginningfromthedateofdeliverytotheoriginal
purchaser.
Warning
ICPDASassumesnoliabilityforanydamageresultingfromtheuseofthisproduct.
ICPDASreservestherighttochangethismanualatanytimewithoutnotice.The
informationfurnishedbyICPDASisbelievedtobeaccurateandreliable.However,no
responsibilityisassumedbyICPDASforitsuse,norforanyinfringementsofpatents
orotherrightsofthirdpartiesresultingfromitsuse.
Copyright
Copyright©2016byICPDASCO.,LTD.Allrightsarereserved.
Trademarks
Namesareusedforidentificationpurposesonlyandmayberegisteredtrademarksof
theirrespectivecompanies.
ContactUS
Ifyouhaveanyproblems,pleasefeelfreetocontactusbyemailat:
Youcancountonusforaquickresponse.

iKANSeriesModbusLEDDisplayUserManualVersion1.0.1Page:3
Copyright©2016ICPDASCo.,Ltd.AllRightsReserved.Email:ser[email protected]om
Table of Contents
1.Introduction ...................................................................................................................................4
2.HardwareInformation ...................................................................................................................8
3.Configuration ...............................................................................................................................13
3.1.Ethernetconfiguration...................................................................................................... 13
3.2.ConnectingtoaremoteDL302device.............................................................................16
3.3.Importing/Exportingpreconfiguratedmessages.............................................................17
3.3.1.Exportingaconfigurationfile.................................................................................17
3.3.2.Importingaconfigurationfile ................................................................................19
3.4.COMportconfiguration ....................................................................................................20
3.5.LEDBrightnessandMessageMotionSpeedadjustment .................................................21
3.6.MISC. .................................................................................................................................23
4.Message s......................................................................................................................................25
4.1.EditingandManagingmessage s.......................................................................................25
4.2.Insertingsystemvariablesintoamessage........................................................................27
4.2.1.DisplayingtheIPAddress.......................................................................................29
4.2.2.DisplayingthecurrentDateandTime ...................................................................31
4.2.3.DisplayingtheCO2andtemperaturevaluesfromaremoteDL302module .......33
4.3.Insertingvariablesintoame ssage....................................................................................35
4.3.1.InsertingaCoilvariableintoamessage ................................................................35
4.3.2.Displayingthevalueofacoilwithreplacementtext.............................................37
4.3.3.Insertinganintegertypevariableintoame ssage.................................................39
4.3.4.DataMappingforIntegertypeVariables...............................................................41
4.3.5.Insertingafloattypevariableintoamessage.......................................................44
4.3.6.Settingthenumberofdecimalplacesforfloattypevariables..............................46
5.WritingVariable ...........................................................................................................................48
5.1.UsingtheiKANWebConfigurationPag e ..........................................................................48
5.2.UsingtheModbusTCP/RTUprotocol ...............................................................................52
6.FirmwareUpdate .........................................................................................................................53
6.1.DownloadingtheLatestFirmwar e....................................................................................53
6.2.InstallingeSearchutility ....................................................................................................54
6.3.Updatingfirmware............................................................................................................54
7.FAQ ...............................................................................................................................................59
7.1.HowtoobtaintheIPaddressfortheiKANdevice?..........................................................59
AppendixA:InstructionforInsertingVariable ................................................................................60
AppendixB:ModbusRegisterTables...............................................................................................61
RevisionRecord................................................................................................................................64
iKANSeriesModbusLEDDisplayUserManualversion1.0.0Page4
Copyright©2016ICPDASCo.,Ltd.AllRightsReserved.Email:ser[email protected]om
1. Introduction
TheiKANseriesisafamilyofindustrialModbusLEDdisplaydevicesthatdeliverindustrialgrade
antinoisecapabilitiesaswellasreliabilityandstability.Theseriesdisplaydeviceishighlysuitable
forpresentingformattedmessagesinindoorareasusingeitherUnicodecharacters,whichcanbe
usedtodisplaymultiplelanguages,orASCIIcharacters.SupportforthepopularModbus
industrialprotocolisprovidedmeaningthatiKANdisplaydevicescanbeeasilyintegratedinto
existingPLCandSCADAenvironments.
168variablesareprovidedtoallowdatawrittenfromaPCoraPLCtobedisplayedinaformatted
messageinrealtime.Sevencolorsareavailableforthetext,whichcanbeusedtoindicate
differentdegreesofimportanceofthemessage,aswellassignificantlyincreasethereadabilityof
themessageinanindustrialarena.
Messagescanbeeditedusingastandardwebbrowser,suchasGoogleChrome,Firefox,orIE,etc.,
onaPC,mobile device,orsmartphonewithoutanylimitationsrelatedtospecificcontroltoolsor
programs.Thedisplayofindividualmessagescanalsoberemotelyenabledordisabledas
necessaryusingthesamestandardwebbrowser.Eachmodelinthe iKANseriesprovidesstor age
spaceforupto64commonmessagesand10instantmessages,eachcontainingamaximumof40
Unicodecharactersor100ASCIIcharacters.Withanopenuserinterfaceandtheabilitytodisplay
realtimedata,theiKANseriesLEDdisplaycanbeinstalledinavarietyofindoorspaces,including
shoppingmalls,railwaystations,andindustrialareas.
iKANSeriesModbusLEDDisplayUserManualversion1.0.0Page5
Copyright©2016ICPDASCo.,Ltd.AllRightsReserved.Email:ser[email protected]om
Features:
SupportsmultiplelanguageswhenusingUnicodecharacters
Textheightof16cm
7colors,includingred,blue,yellow,green,lightblue,purpleandwhite
Adjustablebrightnessandmessagemotionspeed
Abletostoreupto64commonmessagesand10instantmessages
Abletointegratebothtextandvariablesinasinglemessage
SupportstheModbusTCP/RTUSlaveprotocols
BuiltinRTC(RealTimeClock)
WebbasedUserInterface
Canberemotelycontrolledusingasmartphoneorothermobiledevice
iKANSeriesModbusLEDDisplayUserManualversion1.0.0Page6
Copyright©2016ICPDASCo.,Ltd.AllRightsReserved.Email:ser[email protected]om
Functiondescription
PLCHMI
TheiKANseriescanbeemployedasalargeHMIwithamemorystorageofupto64common
messagesand10instantmessages,eachofwhichcanbeusedtodisplayinformation
generatedbyaPLC.Messagetextcanbedisplayedinarangeofsevencolors,includingred,
blue,yellow,green,lightblue,purple,andwhite,whichcanbeusedtoindicatewarningsor
alarms,aswellasincreasingthereadabilityofamessage.

SupportsMultipleLanguages
TheiKANseriesofdisplaydevicesupportsUnicodeinput,meaningthatmessagescanbe
configuredtobedisplayedinmultiplelanguages.
MessageEditing
Amaximumof64commonmessagesand10instantmessagescanbepreconfiguredfrom
thefirstmomentthattheiKANseriesdisplayisswitchedon.Whenthedisplayisin
operation,thefocusneedsonlybeonmessagemanagementratherthantheneedto
frequentlyupdatethemessages.
CO2:725 PPM
Voltage: 2.35 V
Machine A01: Active
iKANSeriesModbusLEDDisplayUserManualversion1.0.0Page7
Copyright©2016ICPDASCo.,Ltd.AllRightsReserved.Email:ser[email protected]om
MessagePriority
Instantmessageshaveahigherprioritythancommonme ssages.Onceaninstantmessageis
enabled,thecommonmessagecurrentlybeingdisplayedwillbesuspendeduntil theinstant
messageisdisabled.Thisfeatureallowsthemostimportantinformationtobedisplayedin
anemergencysituation.
Integertypevariablesenabledatamapping
TheiKANseriesofdisplaydevicesprovidetheabilitytoperformdatamappingtotranslatea
computerintegervaluetoareadablephysicalvalue,suchasthevoltage,temperature,or
relativehumidity,etc.Intheindustrialfield,thisisacommonlyperformedtaskbetweenthe
hostcomputerandthedataacquisitiondevicesviatheModbusprotocol,enablinga
reductionintheresourcesandprogrammingrequiredforthehostcomputer
Import/Exportthemessageconfiguration
TheiKANseriesallowsamessageandtheparametersofthevariablestobesavedasa
configurationfile,whichcanthenbeloadedontoanotheriKANseriesdevicetoavoidthe
needtorepeattheconfiguration.
SmartphoneApplication
Userscanmanagemessagesviaaregularsmartphonewithoutrequirementofaspecific
connectiondevice,meaningthatemergencyinformationcanbequicklysenttothedisplay
usingthesmartphone.
iKANSeriesModbusLEDDisplayUserManualversion1.0.0Page8
Copyright©2016ICPDASCo.,Ltd.AllRightsReserved.Email:ser[email protected]om
2. Hardware Information
Specifications
Model iKAN-116 iKAN-124
Display
Color Red,Blue,Yellow,Green,LightBlue,PurpleorWhite
CharacterSet 16bitUnicodeor7bitASCII
ASCII 16characters 24characters
Display
Size
Unicode 8characters 12characters
MessagePool
64commonmessagesand10instantmessages
Upto40Unicodecharactersor100ASCIIcharacterseach
DataPool 40Coilvalues,64Floatvalues,and64Integervalues
RTC
(RealtimeClock)
Dateandtime,24hourformat,includinghours,minutes,
seconds,dayoftheweek,date,month,year
Ethernet
Port 1xRJ45,10/100BaseTX
Protocol ModbusTCPSlave,Max.8connections
Configuration WebbasedUserInterface
COMPort
Interface RS232orRS485.
Notethattheinterfacescannotbeusedsimultaneously
Baudrate(bps) 1200,2400,4800,9600,19200,38400,57600,115200
DataFormat N81,E81,O81
Protocol ModbusRTUSlave
Power
InputRange 100~240V
AC
Consumption
0.25A@110V
AC
,
0.125A@220V
AC
0.3AA@110V
AC
,
0.15A@220V
AC
Mechanical
Dimensions(WxHxD) 1346mmx160mmx49mm 1986mmx160mmx49mm
Weight 4Kg 5Kg
Installation Wallmounting
HousingMaterial Aluminum
Environment
OperatingTemperature 0to60°C
StorageTemperature 10to75°C
Humidity 10to90%RH,Noncondensing
iKANSeriesModbusLEDDisplayUserManualversion1.0.0Page9
Copyright©2016ICPDASCo.,Ltd.AllRightsReserved.Email:ser[email protected]om
Appearance
Wiring
PowerandEthernetWiring
100~240VAC
PowerSupply
EthernetSwitch
DisplayArea
10/100BaseTXRJ45Connector
Ter minalBlock
‐COM1:RS232
‐COM2:RS485
‐FrameGround
PowerInput:100~240V
AC
Normal/InitSwitch
iKANSeriesModbusLEDDisplayUserManualversion1.0.0Page10
Copyright©2016ICPDASCo.,Ltd.AllRightsReserved.Email:ser[email protected]om
RS232Wiring
RS485Wiring
RS-232 Device
iKANSeriesModbusLEDDisplayUserManualversion1.0.0Page11
Copyright©2016ICPDASCo.,Ltd.AllRightsReserved.Email:ser[email protected]om
MountingPlatesInst allation
FastentheleftandrightmountingplatestoiKAN124displaywithfoursuppliedscrewseachside.
iKANSeriesModbusLEDDisplayUserManualversion1.0.0Page12
Copyright©2016ICPDASCo.,Ltd.AllRightsReserved.Email:ser[email protected]om
Dimensions(Units:mm)
iKAN116
iKAN124
iKANSeriesModbusLEDDisplayUserManualversion1.0.0Page13
Copyright©2016ICPDASCo.,Ltd.AllRightsReserved.Email:ser[email protected]om
3. Configuration
3.1. Ethernet configuration
ThefactorydefaultIPaddressforeachiKANdeviceis192.168.255.1.BeforeintegratinganiKAN
seriesdisplayintoyournetwork,youshouldconfiguretheIP,Mask,andGatewayaddressesfor
thedevicebysettingthevaluesthatarevalidforyournetworksystem.To dothis,followthe
instructionsgivenbelow.
NOTE:
z OneiKANdeviceuses2adjacentIPaddresses.OnceanIPaddressissetforaniKANdevice,
thenextIPaddresswillbeautomaticallysetforthecontrollerintheiKANdisplay.Ifthe
nextIPaddressisalreadyusedforanyotherdevice,youwillfailtocommunicatewiththe
iKANdisplay.
z DetailsonhowtochangetheIPaddressonyourcomputerdependuponthetype
architectureandoperatingsystemyouareusing.UsetheHelpandSupportfunctionality
onyourcomputerandsearchfor"IPAddressing".
z RemembertheIPaddressonyourcomputerforrestoringitlater.

1. ConnecttheiKANdisplaytotheHostPC,thenpoweronalldevices,asillustratedbelow.
2. SettheIPaddressofyourcomputer
100~240V
AC

Powersupply
EthernetSwitch
iKANSeriesModbusLEDDisplayUserManualversion1.0.0Page14
Copyright©2016ICPDASCo.,Ltd.AllRightsReserved.Email:ser[email protected]om
ThefactorydefaultIPaddressfortheiKANdeviceis192.168.255.1.Beforeattemptingto
connecttothebuiltinwebconfigurationpageontheiKANdevice,ensurethattheIPaddress
oftheHostPCissettoa validaddressintherange192.68.255.2to192.168.255.253.This
addressshouldbeuniqueandshouldnotbeusedbyotherEthernetdevices.
3. EntertheIPaddressoftheiKANdisplayintheaddressbarofabrowser,suchasGoogle
Chrome,Firefox,orIE,etc.,andthenpressEnter.ThewebconfigurationpagefortheiKAN
devicewillthenbedisplayed.
4. ConfiguretheIP,Mask,andGatewayaddressesfortheiKANdevicebyfollowingthe
instructionsgivenbelow.
n
o
q
p
iKANSeriesModbusLEDDisplayUserManualversion1.0.0Page15
Copyright©2016ICPDASCo.,Ltd.AllRightsReserved.Email:ser[email protected]om
ClicktheSystemtabatthetopofthepage.
ClicktheETHERNEToptionfromthemenuonthelefthandsideofthepage.
EnteravalidvaluefortheIP,Mask,andGat ewayaddressesinthefieldsinthe
LOCALETHERNETsection.NotethattheIPaddressmustbeuniqueandmustnot
beduplicatedwithotherEthernetdevicesinthenetwork.
ClicktheUpdateSettingsbuttontosavethenewvaluesandcompletethe
configurationprocess.
NotethattheiKANdevicewillbe automaticallyresetonceyouclicktheUpdate
Settingsbutton.
RestoretheIPaddressoftheHostPCtothepreviousvalue.
Repeatstep3above,butenterthenewIPaddressoftheiKANdevice,andthen
pressEntertodisplaythewebuserinterfacethatallowsmessagestobe
preconfigured.
r
q
p
o
n
iKANSeriesModbusLEDDisplayUserManualversion1.0.0Page16
Copyright©2016ICPDASCo.,Ltd.AllRightsReserved.Email:ser[email protected]om
3.2. Connecting to a remote DL-302 device
TheiKANseriesdevicescanbeusedtodisplaydatasuchasthetemperature,humidityandCO2
valuessourcedfromaspecificremoteDL302devicethatisconnectedtothesamenetworkas
theiKANdevice.OncetheIPaddressfortheDL302devicehasbeenconfigured,thedata
recordedbytheDL302canbeautomaticallyobtained.TospecifytheIPaddressoftherequired
DL302device,followtheinstructionsgivenbelow.
ClicktheSystemtabatthetopofthepage.
ClicktheETHERNEToptionfromthemenuonthelefthandsideofthepage.
EntertheIPaddressforthedesiredDL302.
ClicktheUpdateSettingsbuttontosavethenewvaluesandcompletethe
configurationprocess.
n
o
p
q
n
o
q
p
iKANSeriesModbusLEDDisplayUserManualversion1.0.0Page17
Copyright©2016ICPDASCo.,Ltd.AllRightsReserved.Email:ser[email protected]om
3.3. Importing/Exporting pre-configurated messages
IfyoursystemcontainsmorethanoneiKANseriesdevice,itcouldtakealotoftimetoconfigure
eachoneindividually.Tosimplifythisprocess,theImport/Exportfunctionthatisfoundonthe
webconfigurationpagecanbeusedtopreconfigurethe contentsofamessageorvariableon
theiKANseriesdevicebefor eusingModbusTCP /RTUcommandstomanagethemessagepool,
therebyreducingtheneedtorepeattheconfigurationtasksmultipletimes.
OnceamessagehasbeenconfiguredfortheiKANdevice,usetheExportfunctiontosavethe
contentsasaCSVfileontheHostPC.ThismeansthatadditionaliKANseriesdisplaydevicescan
beeasilyconfiguredbyimportingthecsvfiletothatdevice.
3.3.1. Exporting a configuration file
n
o
p
q
iKANSeriesModbusLEDDisplayUserManualversion1.0.0Page18
Copyright©2016ICPDASCo.,Ltd.AllRightsReserved.Email:ser[email protected]om
ClicktheSystemtabatthetopofthepage.
Click the IMPORT/EXPORT option from the menu on the lefthand side of
thepage.
ClicktheSavebuttontosavethecurrentconfigurationasaCSVfile.
Aconfirmationdialogwillbedisplayed,clicktheOKbuttontosavethefile.
ClicktheExportbuttontosavetheconfigurationfiletotheHostPC.
The exported will be saved to the download folder location where your
browsersavesdownloadedfiles. 
n
o
p
q
iKANSeriesModbusLEDDisplayUserManualversion1.0.0Page19
Copyright©2016ICPDASCo.,Ltd.AllRightsReserved.Email:ser[email protected]om
3.3.2. Importing a configuration file
Thefollowingisadescriptionofhowtoimportapreviouslystoredconfigur ationfile.Notethat
theImportfunctionwillonlyloadconfigurationinformationrelatedtomessagesandvariables.
ClicktheSystemtabatthetopofthepage.
ClicktheIMPORT/EXPORToptionfromthemenuonthelefthandsideofthe
page.
ClicktheChooseFilebutton,andthenselectthedesiredCSVfile,whichis
msg_con.csvinthiscase.
ClicktheImportbuttontoloadthecontentsoftheconfigurationfile,whichis
msg_con.csvintheillustrationabove.Oncethefilehasbeenloaded,themessage
“CSVfilesuccessfullyuploaded”willbedisplayed,asillustratedbelow.
n
o
p
q
n
o
q
p
iKANSeriesModbusLEDDisplayUserManualversion1.0.0Page20
Copyright©2016ICPDASCo.,Ltd.AllRightsReserved.Email:ser[email protected]om
3.4. COM port configuration
RS232andRS485arebothprovidedtocommunicatewithModbusRTUdevices.Bothinterfaces
usethesameconfigurationsettingsincludingBaudRate,DataBits,StopBit,andParity,butonly
oneinterfacecanbeusedatthesametime.TransmissiondataformatisN81,E81orO81
selectableontheiKANdevice.
ClicktheSystemtabatthetopofthepage.
ClicktheSERIALPORToptionfromthemenuonthelefthandside ofthepage.
EntertheBaudRate,DataBitts,StopBit(s)andParity;allthesettingsneedbe
identicalwiththeparametersusedontheModbusRTUdevice(s)for
transferringdatacorrectly.
ClicktheUpdateSettingsbuttontosavethenewvaluesandcompletethe
configurationprocess
n
o
q
p
n
o
p
q
/