Operating Instructions | SICK 73
Operating Instructions PAC50
8017612/14NK / 8/2/2019 | PAC50
Subject to change without notice
Product description
4.3.4 Changing the parameters in LT mode
The sensor is in measurement standby (see 4.3.2), the information shown on the display appears in green
and the measurement is either started manually using the
pushbutton or via the PLC using Q1 as a switch-
ing input. The current measured value is always shown in the top part of the display. The following scenarios
may occur during the measurement:
4.3.4.1 System supply pressure p
0
< (pressure) threshold p
1
or p
2
After the measurement starts, the sensor switches directly to an error mode if p
0
is not at least 0.02 bar
greater than the upper threshold p
1
. The display turns red. In the display, “WARN” appears underneath the
current measured value, and “p<p
1
” and the value for p
1
(e.g., “0.60”) or “p<p
2
” and the value for p
2
appear
in the bottom line.
The message must be acknowledged by pressing in order to set the sensor back to measurement standby.
4.3.4.2 Supply pressure p
0
> p
1
and t
out
reached before undershooting of p
1
Timer A starts once the measurement does. The upper threshold p
1
is not reached by the time tout is
reached. During the measurement, “TimA” appears in the top status line together with the corresponding time
value in seconds, and “P>P
1
” appears in the bottom status line together with the value for P1, e.g., “0.60”.
The measurement stops once the time value for t
out
has been reached. “DONE” appears in the top status line
to indicate that the measurement has been completed. In the bottom status line, the values for dP (pressure
difference between p
0
and the current pressure upon reaching t
out
), dT (corresponds to tout in this case)
and the value for QL (absolute value if a volume has been specied or “- - - -QL” if vol = 0 has been retained)
appear alternately.
The message must be acknowledged by pressing in order to set the sensor back to measurement standby.