INSTALLATION AND
OPERATION MANUAL
RETROFIT SYSTEMS
HVRS200-2TRE
HVRS200-2TREX
Engineered for quick and easy replacement of existing progressive cavity grinder systems.
Form #23833A714 (09/05/2019)
7265 0118
*
HVRS200-2TRE
TABLE OF CONTENTS:
SECTION .................................................................................................................................................................................................. PAGE
General Information .................................................................................................................................................................................. 3
Grinder Installation Instructions ............................................................................................................................................................... 4
Retrot System Replacement Parts ......................................................................................................................................................... 5
Warranty ................................................................................................................................................................................................... 6
3
23833A714 (09/05/19)
GENERAL INFORMATION
NOTICE TO THE INSTALLER: Please make sure you provide this
manual to the owner of the equipment or to the responsible
party who maintains the system.
This is the safety alert symbol. When you see this symbol on
your pump or in this manual, look for one of the following signal
words and be alert to the potential for personal injury.
warns about hazards that will cause serious personal
injury, death or major property damage if ignored.
warns about hazards that can cause serious
personal injury, death or major property damage if ignored.
warns about hazards that will or can cause minor
personal injury or property damage if ignored.
NOTICE indicates special instructions which are important but
not related to hazards.
Carefully read and follow all safety instructions in this manual
and on pump.
This manual contains important information for the safe use
of this product. Read this manual completely before using this
product and refer to it often for continued safe product use.
Reasonable care and safe methods should be practiced. Check
local codes and requirements before installation. DO NOT
DISCARD OR LOSE THIS MANUAL.
When unpacking unit, check for concealed damage. Claims for
damage must be made upon receipt through the delivery carrier.
Damage cannot be processed from the factory.
Before handling these pumps and controls, always
disconnect the power first. Do not smoke, use flames or devices
that can produce electrical discharge or sparks in a septic
(gaseous) or possible septic sump.
CALIFORNIA PROPOSITION 65 WARNING:
This product and related accessories contain
chemicals known to the State of California to cause cancer,
birth defects or other reproductive harm.
ELECTRICAL SAFETY
Risk of electrical shock or electrocution
May result in serious injury or death or fire hazard. Installer must
disconnect all electrical sources prior to installation, handling
or servicing. Only qualified personnel may install this system.
NFPA 70/National Electrical Code (NEC) or local codes must
be followed. System must be properly grounded according to
National Electrical Code (NEC). Do not lift pump by power cord.
GENERAL SAFETY
Biohazard Risk
Once wastewater source has been connected to system,
biohazard risk exists. Installer(s) and/or service personnel
must use proper personal protective equipment and follow
handling procedures per OSHA 29 CFR 1910.1030 when handling
equipment after wastewater source has been connected to
system.
Risk of Asphyxiation
Installer(s) and/or service personnel must use proper personal
protective equipment and follow OSHA 29 CFR 1910.146 or OSHA
29 CFR 1926. Pump may be installed in a location classified as a
confined space.
Risk of Fire or Explosion
Do not smoke or use open flames in or around this system.
Risk of Cutting
Risk of serious cutting or amputation exists. Disconnect all
power sources prior to servicing pump. Pump may start without
warning.
Do not modify the cord and plug. When using the cord
and plug, plug into a grounded outlet only. When wiring to
a system control, connect the pump ground lead to the
system ground.
Do not run the pump dry. Dry running can overheat the
pump, which may cause personal injury through burns, and
will void the warranty. See "Standard Limited Warranty" on
Page 6.
The pump normally runs hot. To avoid burns, allow it to cool
for 30 minutes after shutdown before handling it.
Submersible sump pumps are not approved for use in swimming
pools, recreational water installations, decorative fountains
or any installation where human contact with the pumped fluid
is common. Pump is designed to be installed in a sump or wet
location where drainage collects.
UNPACKING PUMP:
Remove pump from carton. When unpacking unit, check
for concealed damage. Claims for damage must be made
upon receipt through the delivery carrier. Damage cannot be
processed from the factory.
Before handling these pumps and controls, always
disconnect the power first. Do not smoke, use flames or devices
that can produce an electrical discharge or sparks in a septic
(gaseous) or possible septic sump.
PUMPS NOT OPERATING OR IN STORAGE:
Pumps with carbon ceramic seals must have impellers manually
rotated (6 revolutions) after sitting nonoperational for 3 months
or longer and prior to electrical start-up.
Pumps with tungsten carbide seals must have impellers
manually rotated (6 revolutions) after sitting nonoperational for
3 weeks or longer and prior to electrical start-up.
For pump installation and troubleshooting, refer to operation
and installation manual HYD1046.
NOTICE Pentair Hydromatic* HVRS200-2TRE and HVRS200-2TREX
are retrofit systems designed for replacement of pump and in-basin
controls only. System uses existing ball valve, latch and existing
underground wiring and alarm panel.
4
23833A714 (09/05/19)
GRINDER INSTALLATION INSTRUCTIONS
4
1. Remove existing pump and pipe system.
2. Make sure pump compartment is clean of any debris.
3. Make sure there is sufficient amount of
power/control/alarm cord to be able to splice into Pentair
Hydromatic* power/control/alarm cords at the new junction
box.
4. Lift pre-assembled unit into place using lift rope supplied.
5. Guide tabs will line up with existing alignment brackets.
Retrofit system discharge piping should seal with existing
pipe socket.
6. After gooseneck is lined up directly above ball valve socket,
drop into place. Make certain that adapter is forced all the
way into socket to ensure a pressure tight seal.
7. If gooseneck and T-handle do not seat evenly, adjust
discharge piping length by loosening lock nut and rotating
discharge piping until proper length is reached.
8. Rotate ball valve handle/latch to secure piping and open
valve. If gooseneck is not completely forced into the seal
with existing pipe socket as described above, ball valve
handle/latch will not close completely over gooseneck
piping.
9. Route power, control cords, and high water alarm through
junction box.
10. Properly calibrate operation of the unit by ensuring that
liquid level in the basin is at its lowest level when control
panel cycles unit off.
PENTAIR HYDROMATIC RETROFIT FLOAT CONTROL JUNCTION BOX
WIRING DIAGRAM
INCOMING 14/3 POWER CORD
5
23833A714 (09/05/19)
RETROFIT SYSTEM REPLACEMENT PARTS
7264 0118
Item Part No. Description Quanity
1 528350017 HVRS200M2-2 1
2 26517C015 ADAPTER - T-HANDLE 1
3 21929A012 BOLT - 3/8" SST 2
4 19109A018 NUT - 3/8" SST 2
5 05454A015 WASHER - LOCK 3/8" SST 2
6 001780081 SCREW - CAP 5/16-18 SST 2
7 05008A052 NIPPLE - 1-1/4" SST 1
8 28232B011 DISCHARGE PIPE - PUMP SIDE ADJUSTABLE 1
9 28232B003 PIPE LOCKNUT - 1-1/4" SST 1
10 28232B002 DISCHARGE PIPE - CV SIDE 1-1/4" SST 1
11 21903A012 CHECK VALVE - 1-1/4" BALL 1
12 05004A124 BUSHING - 1-1/2"MPT X 1 FPT 1
13 21903A100 ANTI SIPHON VALVE 1
14 22418A016 DISCHARGE PIPE - 1-1/4" SST 1
15 14740A019 HOSE CLAMP 1
16 27659A001 CONTROL FLOAT W/ CLAMP 2
17 23019252100 ROPE - 3/8" POLY 15FT
18
27480A104 PANEL / J-BOX, SQUARE PLUG
27480A105 PANEL / J-BOX ROUND PLUG
WARRANTY
Pentair Hydromatic* warrants its products against defects in material and workmanship for a period of 12 months from
installation date or 18 months from manufacturing date, whichever occurs rst – provided that such products are used in
compliance with the requirements of the Pentair Hydromatic catalog and technical manuals for use in pumping raw sewage,
municipal wastewater or similar, abrasive-free, noncorrosive liquids.
During the warranty period and subject to the conditions set forth, Pentair Hydromatic, at its discretion, will repair or
replace to the original user, the parts that prove defective in materials and workmanship. Pentair Hydromatic reserves the
right to change or improve its products or any portions thereof without being obligated to provide such a change or im-
provement for prior sold and/or shipped units.
Start-up reports and electrical schematics may be required to support warranty claims. Submit at the time of start up
through the Pentair Hydromatic website: http://forms.pentairliterature.com/startupform/startupform.asp? type=h. War-
ranty is effective only if Pentair Hydromatic authorized control panels are used. All seal fail and heat sensing devices must
be hooked up, functional and monitored or this warranty will be void. Pentair Hydromatic will cover only the lower seal and
labor thereof for all dual seal pumps. Under no circumstance will Pentair Hydromatic be responsible for the cost of eld
labor, travel expenses, rented equipment, removal/reinstallation costs or freight expenses to and from the factory or an
authorized Pentair Hydromatic service facility.
This limited warranty will not apply: (a) to defects or malfunctions resulting from failure to properly install, operate or main-
tain the unit in accordance with the printed instructions provided; (b) to failures resulting from abuse, accident or negli-
gence; (c) to normal maintenance services and parts used in connection with such service; (d) to units that are not installed
in accordance with applicable local codes, ordinances and good trade practices; (e) if the unit is moved from its original
installation location; (f) if unit is used for purposes other than for what it is designed and manufactured; (g) to any unit that
has been repaired or altered by anyone other than Pentair Hydromatic or an authorized Pentair Hydromatic service provid-
er; (h) to any unit that has been repaired using non factory specied/OEM parts.
Warranty Exclusions: PENTAIR HYDROMATIC MAKES NO EXPRESS OR IMPLIED WARRANTIES THAT EXTEND BEYOND THE
DESCRIPTION ON THE FACE HEREOF. PENTAIR HYDROMATIC SPECIFICALLY DISCLAIMS THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR ANY PARTICULAR PURPOSE.
Liability Limitation: IN NO EVENT SHALL PENTAIR HYDROMATIC BE LIABLE OR RESPONSIBLE FOR CONSEQUENTIAL, IN-
CIDENTAL OR SPECIAL DAMAGES RESULTING FROM OR RELATED IN ANY MANNER TO ANY PENTAIR HYDROMATIC PROD-
UCT OR PARTS THEREOF. PERSONAL INJURY AND/OR PROPERTY DAMAGE MAY RESULT FROM IMPROPER INSTALLATION.
PENTAIR HYDROMATIC DISCLAIMS ALL
LIABILITY, INCLUDING LIABILITY UNDER THIS WARRANTY, FOR IMPROPER INSTALLATION. PENTAIR HYDROMATIC RECOM-
MENDS INSTALLATION BY PROFESSIONALS.
Some states do not permit some or all of the above warranty limitations or the exclusion or limitation of incidental
or consequential damages and therefore such limitations may not apply to you. No warranties or representations
at any time made by any representatives of Pentair Hydromatic shall vary or expand the provision hereof.
1101 Myers Parkway | Ashland, OH 44805 | Ph: 855-274-8947 | Orders Fax: 419-281-4087 | pentair.com/hydromatic
*For a detailed list of where Pentair trademarks are registered, please visit www.pentair.com/en/registrations.html. Pentair trademarks and logos are owned by Pentair PLC. or its aliates. Third
party registered and unregistered trademarks and logos are the property of their respective owners. Because we are continuously improving our products and services, Pentair reserves the
right to change specications without prior notice. Pentair is an equal opportunity employer.
HYD12647ENG (09/05/19) ©2019 Pentair, Inc. All Rights Reserved.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6

Hydromatic HYDROMATIC HVRS200-2TRE Owner's manual

Type
Owner's manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI