Cabling the Dell™
PowerEdge™ R710
ADellTechnicalWhitePaper
By Chris M. Kitten and Jose L. Flores
Dell Datacenter Infrastructure Engineering
March 2009
CablingtheDell™PowerEdge™R710
Pageii
THISWHITEPAPERISFORINFORMATIONALPURPOSESONLY,ANDMAYCONTAINTYPOGRAPHICALERRORSAND
TECHNICALINACCURACIES.THECONTENTISPROVIDEDASIS,WITHOUTEXPRESSORIMPLIEDWARRANTIESOF
ANYKIND.
©2009DellInc.Allrightsreserved.Reproductionofthismaterialin
anymannerwhatsoeverwithouttheexpress
writtenpermissionofDellInc.isstrictlyforbidden.Formoreinformation,contactDell.
Dell,theDELLlogo,andtheDELLbadge,PowerEdge,isatrademarkofDellInc.
CablingtheDell™PowerEdge™R710
Page1
Table of Contents
Introduction...............................................................................................................................................................2
CablingaPowerEdgeR710withCMA.......................................................................................................................2
2.1InstallingtheCablestotheSystem.................................................................................................................2
Figure1:SystemwithCablesInstalled..........................................................................................................2
2.2RoutethePowerCablesThroughtheStrainReliefs.......................................................................................3
Figure2:RoutingPowerCablesThroughtheStrainReliefs.........................................................................3
2.3RoutingtheCablesThroughtheCMA.............................................................................................................3
Figure3:RoutingtheCablesThroughtheCMA...........................................................................................4
Figure4:CompletedLeftSideMountedCMAInstallation............................................................................5
Figure5:CompletedRightSideMountedCMAInstallation..........................................................................5
CablingaPowerEdgeR710WithoutaCMA..............................................................................................................5
3.1RoutingtheCables..........................................................................................................................................5
Figure6:CableRoutingWithoutaCMA........................................................................................................6
ReplacingaPowerSupplyonaPowerEdgeR710withCMA.....................................................................................6
Figure7:ReplacingOuterPowerSupply.......................................................................................................7
CablingaPowerEdgeR710InstalledinStaticRails...................................................................................................7
Figure8:CablingaSystemInstalledinStaticRails........................................................................................7

CablingtheDell™PowerEdge™R710
Page2
Introduction
Thiswhitepaperdescribesrecommendedcableroutingprocedures,bothwithandwithouttheoptionalCable
ManagementArm(CMA)fortheDell™PowerEdge™R710inthefollowingracks:
PowerEdge4210
PowerEdge2410
PowerEdge4220
PowerEdge2420
IfusingtheoptionalCMA,followingtheseprocedureswillallowyouto
extendthesystemfromtherackforservice
withoutpoweringdownordisconnectingthecables.IfnotusingtheCMA,followingtheseprocedureswillensure
secureattachmentandstrainreliefofthecablesbehindthesystem.Forguidelinesonhowtoroutecableswithin
therack,refertotheDell
WhitePaper“BestPracticesGuideforRackEnclosures.”
CablingaPowerEdgeR710withCMA
ThissectiondetailshowtocableaPowerEdgeR710usingaCMA.Ifyouarecablingthesystemwithoutthe
optionalCMA,pleasereferto“CablingaPowerEdgeR710WithoutaCMA”laterinthiswhitepaper.
FollowtheinstructionscontainedintheRackInstallationGuidefoundintherailkit
toinstalltheserverintothe
rackandtoinstallthecables.AllillustrationsinthefollowingsectionswerecreatedusingaPowerEdgeR710.
NOTE:ThePowerEdgeR710isnotcompatiblewithpreviousgenerationrailsandCMAs.
2.1InstallingtheCablestotheSystem
AttachtheCMAtraytothebackoftherailsasdescribedintheCMAInstallationInstructionsprovidedintheCMA
kit.Pluginallapplicablecablestotherearofthesystem.Verifythatallconnectionsaresecure.SeeFigure1.
Figure1:SystemwithCablesInstalled
CablingtheDell™PowerEdge™R710
Page3
2.2RoutethePowerCablesThroughtheStrainReliefs
Afterthetrayandcablesareinstalled,routethepowercablesthroughthestrainreliefslocatedonthepower
supplyhandlesasshowninFigure2.
Figure2:RoutingPowerCablesThroughtheStrainReliefs
2.3RoutingtheCablesThroughtheCMA
NOTE:TheCMAcanbeinstalledoneithertherightorleftrearsideoftherails.MountingtheCMAontheside
oppositethepowersupplies(leftsidemount)isrecommended;otherwise,theCMAmustbedisconnectedinorder
toremovetheouterpowersupply.Referto“ReplacingaPower
SupplyonaPowerEdgeR710withCMA”laterin
thiswhitepaperfordetailsonpowersupplyreplacement.
NOTE:Forguidelinesonhowtoroutecableswithintherack,refertotheDellWhitePaper“BestPracticesGuide
forRackEnclosure”.
LeftSideMountingInstructions
1. InstalltheCMAon
theleftrearsideoftherailsbyattachingbothCMAhousingstotheattachmentbracketson
therails.SeeFigure3.
2. RoutethecablesthroughtheCMAwhilekeepinganytwistingofthecablestoaminimum.Ifthecablebundle
includesaKVMdongle,placethedongleinside
theCMAbasket.UsethehookandloopstrapsontheCMAto
securethecables.
CablingtheDell™PowerEdge™R710
Page4
Figure3:RoutingtheCablesThroughtheCMA
3. OnceallthecablesareroutedthroughtheCMA,dressthecablesbetweenthebackofthesystemandthe
entranceoftheCMAwiththetiewrapsprovidedintheCMAkit.Thetiewrapsareshowninyellowinall
illustrations.
4. Clip
offtheexcesslengthofmaterialfromthetiewrapsandmakesurethatthetiewrapsarepositionedto
avoidinterferencewithadjacentsystems.
5. ReturntheCMAtotheclosed(retracted)position.
6. Extendthesystemfromtheracktoverifythereissufficientslackinthecablesat
boththeentranceandexitof
theCMA.
7. SeeFigure4foranexampleofacompletedleftsidemountedCMAinstallation.
Cables entering CMA should
have a small amount of slack
to avoid cable strain when
CMA is extended.
NOTE: Do not store excess
cable slack inside the CMA.
The cable may protrude
through the CMA causing
binding and potentially
damaging the cable.
CablingtheDell™PowerEdge™R710
Page5
Figure4:CompletedLeftSideMountedCMAInstallation
RightSideMountingInstructions
InstalltheCMAontherightrearsideoftherailsbyattachingbothCMAhousingstotheattachmentbracketson
therails.Followsteps26fromtheleftsidemountinginstructionsintheprevioussection.SeeFigure5foran
exampleofacompleted
rightsidemountedCMAinstallation.
Figure5:CompletedRightSideMountedCMAInstallation
CablingaPowerEdgeR710withoutaCMA
NOTE:TheCMAontheDellPowerEdgeR710isoptional.WithouttheCMAinstalled,thesystemmustbepowered
downandallcablesdisconnectedbeforeitcanberemovedfromtherack.
3.1RoutingtheCables
1. Pluginallapplicablecablestotherearofthesystem,verifyingthatallconnectionsaresecure.
CablingtheDell™PowerEdge™R710
Page6
2. Usingthehookandloopstrapssuppliedwiththerailkit,bundlethecablesandsecurethemtoeithertheleft
railorrightrailCMAattachmentbracketsasdescribedintheRackInstallationGuide.SeeFigure6foran
exampleofpowercablessecuredto
therightCMAbracketanddatacablessecuredtotheleftCMAbracket.
3. Itisrecommendedthatthecablesbesecuredtotheouterbrackets,butcablesmaybesecuredtotheinner
bracketsifdesired.
Figure6:CableRoutingWithoutaCMA
ReplacingaPowerSupplyonaPowerEdgeR710withCMA
1. RemovethetrayfromundertheCMAasdescribedintheCMAInstallationInstructionsprovidedwiththeCMA
kit.
2. SwingtheCMAintotheserviceposition.
3. Disconnectthepowercordfromthepowersupplyanddisengagethestrainrelief.
4. Removeandreplacethepowersupply
a. If
theCMAisattachedtotherightsideandtheouterpowersupplyneedstobereplaced,theinner
CMAattachmenthousingwillneedtobedisconnected.WhilesupportingtheCMAwithonehand,
removeandreplacethepowersupplywiththeotherhandasshowninFigure7.
b.
IftheCMAisattachedtotherightsideandtheinnerpowersupplyneedstobereplaced,theCMA
doesnotneedtobedisconnected.
c. IftheCMAisattachedtotheleftside,bothpowersuppliescanberemovedwithoutdisconnecting
theCMA.
5. Pluginthepower
cord.
6. Reengagethestrainrelief.
7. ReplacetheCMAsupporttray.
8. ReturntheCMAtotheclosed(retracted)position.
CablingtheDell™PowerEdge™R710
Page7
Figure7:ReplacingOuterPowerSupply
CablingaPowerEdgeR710InstalledinStaticRails
NOTE:TheCMAisonlycompatiblewithslidingrails,andnotwithstaticrails.
1. FollowtheinstructionsintheRackInstallationGuideincludedinthestaticrailkittoinstalltheserverintoa2
postor4postrack.
2. Verifythatthehookandloopsstrapsprovidedwith
thestaticrailkitareinstalledtotherearoftherails.
3. Pluginallapplicablecablestotherearofthesystemandverifythatallconnectionsaresecure.
4. Usingthehookandloopstrapssuppliedwiththerailkit,bundlethecablesandsecurethemto
eithertheleft
railorrightrailasdescribedintheRackInstallationGuide.SeeFigure8.
Figure8:CablingaSystemInstalledinStaticRails
Inner CMA attachment
housing has been
disconnected
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9

Dell R710 Owner's manual

Category
Car kits
Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI