Vaillant Buffer tank Installation guide

Category
Measuring, testing & control
Type
Installation guide
DE, BEde, AT, GB, IT, CHde, CHit, ES, CZ
VWZ MPS 40
Installation instructions
Installation instructions
VWZ MPS 40
Installation instructions
For the competent person
Instructions for use
For the operator
EN
1 Safety .....................................................................17
1.1 Symbols used ..........................................................17
1.2 Quali cations ...........................................................17
1.3 General safety advices ............................................17
1.4 Intended use ...........................................................17
1.5 Regulations (directives, laws, standards) ................18
2 Notes on the documentation ................................19
2.1 Observe other applicable documents ......................19
2.2 Storing documents ..................................................19
2.3 Validity of the instructions ........................................19
3 Description of the product ...................................19
3.1 Product structure .....................................................19
3.2 Type designation and serial number .......................19
3.3 Data plate description .............................................19
4 Mounting and installation .....................................20
4.1 Preparing the mounting and installation ..................20
4.2 Mounting the product ..............................................21
4.3 Hydraulic installation ...............................................21
4.4 Different con gurations ...........................................22
4.5 Passage and routing of the temperature sensor
cable ........................................................................23
5 Start-up ..................................................................23
5.1 Purging the appliance .............................................23
5.2 Installing the casing .................................................24
5.3 Handing over the product to the user ......................24
5.4 Spare parts ..............................................................24
6 Decommissioning .................................................24
7 Recycling and disposal ........................................24
8 Technical data .......................................................24
9 Customer service ..................................................24
0020153953_05 - 03/15 - Vaillant
17
SAFETY
1 Safety
1.1 Symbols used
The warning notes are classi ed in
accordance with the severity of the possible
danger using the following warning signs and
signal words.
Warning
symbol
Explanation
a
Danger!
Immediate danger to life or risk
of severe personal injury.
a
Warning!
Risk of minor personal injury.
b
Caution!
Risk of material or
environmental damage.
1.2 Quali cations
Any work carried out must be by suitably
quali ed personnel.
Incorrect installation can cause damage to
the unit, to the site or injury to others.
1.3 General safety advices
1.3.1 Danger to life due to missing
or not properly working safety
devices
Missing safety devices can cause life-
threatening scalding and other injuries, for
example by burst pipes.
The information contained in this document
do not show all schemes required for a
professional installation of safety devices.
Install the necessary safety devices in the
system.
Inform the user about the function and
location of safety devices.
Observe the relevant national and
international laws, standards and
guidelines.
1.3.2 Risk of material damage by
additives in the heating water
Frost and corrosion protection agents can
cause changes to seals, noise during heating
mode and may lead to other consequential
damage.
Do not use any unsuitable frost or
corrosion protection agents.
1.3.3 Risk of material damage caused
by unsuitable tools
The use of unsuitable tools or improper use
thereof may cause damage, such as gas or
water leaks.
When tightening or loosening threaded
connections, always use suitable opened
spanners, but do not use pipe wrenches,
extensions, etc.
1.3.4 Risk of structural damages by
escaping water
Incorrect installation can cause leakages.
Make sure there are no stresses in the
hydraulic lines.
Correctly position the seals.
1.4 Intended use
The product is a state-of-the-art product
which has been constructed in accordance
with recognised safety regulations.
Nevertheless, there is still a risk of injury or
death to the user or others or of damage to
the product and other property in the event
of improper use or use for which it is not
intended.
This product can be used by children
over eight years old and also by persons
with limited physical, sensory or mental
capabilities or insuf cient experience and/
or knowledge if they are supervised or have
been provided with instructions on how to
safely use the product, and they understand
the risks resulting from using the product.
Children must not play with the product.
Cleaning and user maintenance work must
not be carried out by children unless they are
supervised.
0020153953_05 - 03/15 - Vaillant
18
SAFETY
Intended use includes the following:
observing the included operating,
installation and maintenance instructions
for this product and any other parts and
components of the system
installing and tting the product in
accordance with the product and system
approval
complying with all of the inspection and
maintenance conditions listed in the
instructions.
The appliance should be installed in a place
where it will not be exposed to damp or
water splashes. Comply with the electrical
protection index (IP) shown in the technical
data.
Any other use than the use described in the
instructions at hand or any use extending the
described use is not intended.
Any direct commercial or industrial use is
also deemed to be improper.
1.5 Regulations (directives, laws,
standards)
Please observe the existing national rules
and regulations, standards, laws and
guidelines.
0020153953_05 - 03/15 - Vaillant
19
NOTES ON THE DOCUMENTATION
2 Notes on the documentation
2.1 Observe other applicable documents
Observe absolutely all operating and installation
instructions enclosed with the product, for the various
parts and components of the system.
2.2 Storing documents
Pass these instructions and all other applicable
documents to the system user.
The system user should retain these instructions so that
they are available when required.
2.3 Validity of the instructions
These instructions apply exclusively to:
Product Article number
VWZ MPS 40 0020145020
3 Description of the product
3.1 Product structure
1
A
B
C
D E
F
1 Sleeve for temperature
sensor
(temperature sensor VR
10 not supplied)
A Connector 1"
B Connector 1"
C Connector 1"
D Connector 1"
E Connector 1"1/4
F Connector 1"1/4
3.2 Type designation and serial number
Data plate location:
1
1 Data plate
The type designation and the serial number are shown on
the data plate.
3.3 Data plate description
The data plate certi es the country where the product is
intended to be installed.
The data plate contains the following data:
Abreviation/
symbol
Description
Country code: "UK"
Country where the product is
intended to be installed
Serial-no
Commercial name of the product
and its serial number
Code Product code of the appliance
PMS Central heating maximum pressure
0020153953_05 - 03/15 - Vaillant
20
MOUNTING AND INSTALLATION
4 Mounting and installation
i
Notes
All the drawings dimensions are shown in mm.
4.1 Preparing the mounting and
installation
4.1.1 Delivery and installation on site
4.1.1.1 [product] unpack
Remove the product from its box.
Remove the protective lm from all parts of the product.
4.1.1.2 Check scope of delivery
Please check the scope of delivery for completeness.
1 Hydraulic module + 3 plug 1" + 1 plug 1"1/4
1 accessories bag
1 bag of documents (1 operating and installation)
4.1.2 Observing distances and mounting
clearances
4.1.2.1 Product and connection dimensions
360
720
350
637
87 101
632
180 180
212 220
140
440
100 100
140 440
4.1.2.2 Distance to in ammable parts
Make sure that no item that can easily catch re is in
direct contact with the components, which may reach a
temperature greater than 80°C.
Make sure that there is a minimum distance of 200 mm
between items that can easily catch re and the hot
surfaces.
4.1.2.3 Mounting clearances
Ensure the distances indicated on the diagram.
This will ensure that the connections to the water can be
accessed and inspected.
Additional clearances around the appliance may be
advantageous for its installation and maintenance.
200
mini.
200
mini.
150
mini.
20
mini.
>600*
180
i
Notes
* Clearance necessary for the installation or
maintenance of the appliance.
0020153953_05 - 03/15 - Vaillant
21
MOUNTING AND INSTALLATION
4.1.3 Considering the product location
4.1.3.1 Surrounding conditions
Do not install the product above another product that
could damage it (for example, above a cooker that might
emit steam or grease) or in a room, which has a lot of
dust in the atmosphere which is corrosive.
Make sure that the room where you want to t the
product is suf ciently protected against frost.
4.1.3.2 Properties of the mounting surface
Before choosing a site for the product, carefully read
the safety warnings and instructions in the operating
instructions and installation instructions.
Ensure that the wall to which the product will be mounted
on is structurally safe in order to support the weight of the
product.
4.2 Mounting the product
4.2.1 Removing the casing
1
1 Front casing
Remove the front casing (1).
4.2.2 Wall-mounting of the product
a
Danger!
Danger to life if the load-bearing
capacity of the fixing elements
used is insufficient!
If the fixing elements do not have
sufficient load-bearing capacity, the
product can come loose and fall
down.
When fitting the product, ensure
that the fixing elements have a
sufficient load-bearing capacity.
Determine the assembly location.
Drill the holes to receive the fastenings (see chapter 4.1).
Fix the hanging bracket on the wall.
1
1 Hanging bracket
Lifting the product into position, lean the top of the product
slightly to the wall and position just above the hanging
bracket.
Lower the product slowly and engage onto the hanging
bracket.
This product is for internal installation only.
4.3 Hydraulic installation
b
Caution!
Risk of damage caused by con-
taminated lines!
Foreign bodies such as welding
remnants, sealing residue or dirt in
the supply lines can cause damage
to the product.
Flush the supply lines thoroughly
before installation.
0020153953_05 - 03/15 - Vaillant
22
MOUNTING AND INSTALLATION
b
Caution!
Risk of damage caused by heat
transfer when soldering.
Heat that is transferred during sol-
dering can cause damage
(expanded) polypropylene around
hydraulic module and to the seals in
the service valves.
Protect (expanded) polypropylene
of hydraulic module.
Do not solder the connection
pieces if the connection pieces
are screwed to the service valves.
b
Caution!
Risk of damage due to corrosion.
If plastic pipes that pass oxygen are
used in the heating installation, this
may corrode or sludge up the
appliance’s heating circuit or the
appliance itself.
If you use plastic pipes that pass
oxygen in the heating installation,
add a corrosion inhibitor to the
circuit water.
1
2
3
6
5
4
1 Connector G1"
2 Connector G1"
3 Connector G1"
4 Connector G1"
5 Connector G1"1/4
6 Connector G1"1/4
Only use the original seals supplied with the appliance.
Connect the heating circuit as speci ed.
4.4 Different con gurations
4.4.1 Case No 1
3
3
1
1
2
2
4.4.2 Case No 2
3
3
1
1
4
4.4.3 Case No 3
3
3
1
1
4
4
4
4
0020153953_05 - 03/15 - Vaillant
23
START-UP
4.4.4 Case No 4
3
1
1
4
4
3
2
2
1 Heat pump
2 Boiler
3 Heating
4 Plug
4.5 Passage and routing of the
temperature sensor cable
i
Notes
The temperature sensor (VR 10) is not supplied.
It must be ordered separately.
i
Notes
The temperature sensor cable must be passed
through the hole provided for this purpose.
1
2
3
3
1 Temperature sensor
housing
2 Temperature sensor
cable
3 Temperature sensor
cable passage
i
Notes
The temperature probe must be assembled
using thermal paste for good heat transfer.
5 Start-up
For lling, refer to the installation instructions of the heat
pump.
Check the electrical and water installation.
Check all connections for leaks.
Purge your heating system.
5.1 Purging the appliance
1
1 Air vent
Open the air vent (1), when lling the heating circuit with
water.
Close the vent as soon as water ows (repeat the
operation several times if necessary).
0020153953_05 - 03/15 - Vaillant
24
DECOMMISSIONING
5.2 Installing the casing
1
1 Front casing
Put the front casing back on
5.3 Handing over the product to the user
After completing the installation:
Answer any questions the user may have.
5.4 Spare parts
In case you need spare parts during maintenance or
repair, exclusively use genuine Vaillant spare parts.
The genuine component parts of the product have been
certi ed together with the product in the course of the CE
conformity check. If you do not use certi ed genuine Vaillant
spare parts during maintenance or repair, the CE conformity
of the product will expire. That is why we imperatively
recommend to install genuine Vaillant spare parts.
6 Decommissioning
Drain the appliance (It is recommended that a drain valve
at the lowest point of the installation).
De-install the product.
Recycle or dispose the product and its components (see
chapter 7).
7 Recycling and disposal
The competent person who installed your product is
responsible for the disposal of the packaging.
If the product is identi ed with this symbol:
In this case, do not dispose of the product with household
waste.
Instead, hand in the product to a collection centre for old
electrical or electronic appliances.
If the product contains batteries that are marked with
this symbol, these batteries may contain substances that
are hazardous to human health and the environment.
In this case, dispose of the batteries at a collection point
for batteries.
8 Technical data
Description Unit
Net Weight kg 18
Nominal capacity of hydraulic module l 40
Maximum admissible water pressure
bar 3.0
Mpa 0.3
Minimum admissible water pressure
bar 0.5
Mpa 0.05
9 Customer service
For contact details for our customer service department, you
can write to the address that is provided on the back page,
or you can visit www.vaillant.co.uk.
© These instructions, or parts thereof, are protected by copyright and may be reproduced
or distributed only with the manufacturer's written consent.
0020153953_05
12.03.2015
Lieferant/Fournisseur/Supplier/Fornitore/Proveedor/Dodavatel
Vaillant Deutschland GmbH & Co.KG
Berghauser Str. 40
D-42859 Remscheid
Telefon 021 91 18-0 Telefax 021 91 18 28-10
Vaillant Pro -Hotline 018 06 99 91 20 20 (20 Cent/Anruf aus dem deutschen Festnetz, aus dem
Mobilfunknetz max. 60 Cent)Anruf. Vaillant Werkskundendienst 018 06 99 91 50
(20 Cent/Anruf aus dem deutschen Festnetz, aus dem Mobilfunknetz max. 60 Cent/Anruf.)
[email protected] www.vaillant.de
Vaillant Group Austria GmbH
Forchheimergasse 7 A-1230 Wien
Telefon 05 70 50-0 Telefax 05 70 50-11 99
Telefon 05 7050 2100 (zum Regionaltarif österreichweit, bei Anrufen aus dem Mobilfunknetz ggf. abweichende
Tarife - nähere Information erhalten Sie bei Ihrem Mobilnetzbetreiber)
www.vaillant.at www.vaillant.at/werkskundendienst/
Vaillant Sàrl
Rte du Bugnon 43
CH-1752 Villars-sur-Glâne
Tél. 026 409 72-10
Fax 026 409 72-14
Service après-vente tél. 026 409 72-17 Service après-vente fax 026 409 72-19
[email protected] www.vaillant.ch
N.V. Vaillant S.A.
Golden Hopestraat 15 B-1620 Drogenbos
Tel. 2 334 93 00 Fax 2 334 93 19
Kundendienst 2 334 93 52 Service après-vente 2 334 93 52
Klantendienst 2 334 93 52
[email protected] www.vaillant.be
Vaillant Ltd
Nottingham Road DE56 1JT Derbyshire Belper
Telephone 44 84 56 02 29 22 Vaillant Service Solutions 44 807 06 06 07 77
Spares Technical Enquiries 44 17 73 59 66 15
www.vaillant.co.uk
Vaillant Group Italia S.p.A unipersonale
Società soggetta all'attività di direzione e coordinamento della Vaillant GmbH
Registro A.E.E. IT08020000003755 Registro Pile IT09060P00001133
Via Benigno Crespi 70 20159 Milano
Tel. 02 69 71 21 Fax 02 69 71 25 00
Centro di Assistenza Tecnica Vaillant Service 800 08 87 66
[email protected] www.vaillant.it
Vaillant S. L.
Atención al cliente
C/La Granja, 26 Pol. Industrial Apartado 1.143 28108 Alcobendas (Madrid)
Teléfono 902 11 68 19 Fax 916 61 51 97 www.vaillant.es
Vaillant Group Czech s. r. o.
Chrášt'any 188 CZ-25219 Praha-západ
Telefon 2 81 02 80 11 Telefax 2 57 95 09 17
[email protected] www.vaillant.cz
Hersteller/Fabricant/Manufacturer/Produttore/Fabricante/Výrobce
Herausgeber/Éditeur/Publisher/Editore/Editor/Vydavatel
Vaillant GmbH
Berghauser Str. 40 D-42859 Remscheid
Telefon 021 91 18-0 Telefax 021 91 18 28-10
[email protected] www.vaillant.de
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64

Vaillant Buffer tank Installation guide

Category
Measuring, testing & control
Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI