State GS6-30-MDV250, GS6-40-MDV- 250, GS6-50-MDV-250 User manual

Category
Water heaters & boilers
Type
User manual

This manual is also suitable for

100291750_2000547498_(Rev. B)
November 2017
Installa on Instruc ons and
Use & Care Guide
Keep this manual in the pocket on heater for future reference whenever maintenance, adjustment or service is required.
Retain your original receipt as proof of purchase.
Read this manual and the labels on the water heater before you install,
operate, or service it. If you have di culty following the direc ons, or
aren’t sure you can safely and properly do any of this work yourself:
Call our Technical Assistance Hotline at 1-800-365-0024. We can help you with
installa on, opera ons, troubleshoo ng, or maintenance. Before you call, write
down the model and serial number from the water heaters data plate.
Incorrect installa on, opera on, or service can damage the water heater, your house
and other property, and present risks including re, scalding, electric shock, and
explosion, causing serious injury or death.
Do not store or use gasoline or other
ammable vapors and liquids in the
vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
Do not touch any electrical switch;
do not use any phone in your
building.
Immediately call your gas supplier
from a neighbors phone. Follow the
gas supplier’s instruc ons.
If you cannot reach your gas
supplier, call the re department.
Installa on and service must be
performed by a quali ed installer,
service agency or the gas supplier.
WARNING: If the informa on in
these instruc ons is not followed
exactly, a re or explosion may
result causing property damage,
personal injury or death.
LOW LEAD
CONTENT
Table of Contents Page
IMPORTANT SAFETY INFORMATION .................................................................. 3
GETTING STARTED ............................................................................................. 7
INSTALLATION .................................................................................................. 11
OPERATION ...................................................................................................... 27
TROUBLESHOOTING ........................................................................................ 30
MAINTENANCE ................................................................................................ 32
REPAIR PARTS .................................................................................................. 35
GAS CONVERSION ......................................................................................... 23
Shall not be installed in the occupied space of the manufactured
(mobile) home.
Originally shipped set for Natural Gas and convertible to L.P. Propane
Gas (all parts included). See Gas Conversion on page 23.
For potable water heating only. Not suitable for space heating.
Residential Direct Vent Water Heater with the
Flammable Vapor Igni on Resistant
Safety System
For Installa on in a Manufactured Home (Mobile Home)
2 • Residen al Gas Water Heater Use and Care Guide for Manufactured Homes
COMPLETED INSTALLATION (TYPICAL)
Gas Supply
^ŚƵƚŽī
Gas Supply
Gas Control
Valve/Thermostat
Sediment Trap
Ground Joint
Union
Metal Drain Pan
Terminate the
discharge pipes
through the
ƐƚƌƵĐƚƵƌĂůŇŽŽƌŽƌ
a maximum of six
inches above a
ŇŽŽƌĚƌĂŝŶ͘
Protect discharge
pipes from
ĨƌĞĞnjŝŶŐ͘
Drain Valve
>ŝŐŚƟŶŐ/ŶƐƚƌƵĐƟŽŶƐ
T&P Discharge
Pipe
T&P Relief Valve
Expansion Tank
(connect to
cold water supply)
Cold Water
Line
Cold Water
^ŚƵƚŽī
Roof Jack / Vent
Hot Water
Line
Flue Reducer
ŽŶǀĞƌƐŝŽŶ/ŶƐƚƌƵĐƟŽŶƐ
ZĂƟŶŐWůĂƚĞ
Read and follow
Ăůů ĐĂƵƟŽŶƐ ĂŶĚ
warnings on the
water heaters
ůĂďĞůŝŶŐ͘
Residen al Gas Water Heater Use and Care Guide for Manufactured Homes • 3
SAFETY
IMPORTANT SAFETY INFORMATION
Important informa on to keep
Fill out this sec on and keep this
manual in the pocket of the water
heater for reference.
Date Installed:
Model number:
Serial number:
Maintenance performed:* Date:
This is the safety alert symbol. It is used to alert you to
poten al physical injury hazards. Obey all safety mes-
sages that follow this symbol to avoid possible property
damage, serious injury or death. Do not remove any per-
manent instruc ons, labels, or the ra ng plate from either the outside of
the water heater or on the inside of the access panels. Keep this manual
near the water heater.
DANGER
Read and follow all safety messages and instruc ons in
this manual.
DANGER indicates hazardous situa-
on that, if not avoided, will result
in death or serious injury.
WARNING
WARNING indicates a hazardous
situa on that, if not avoided, could
result in death or serious injury.
CAUTION
CAUTION indicates a hazardous
situa on that, if not avoided, could
result in minor or moderate injury.
NOTICE
NOTICE indicates prac ces not
related to physical injury.
WARNING! If the informa on in these instruc ons is not followed exactly,
a re or explosion may result causing property damage, personal injury or
death. Do not store or use gasoline or other ammable vapors and liquids in
the vicinity of this or any other appliance.
An odorant is added by the gas supplier to the gas used by this water heater.
This odorant may fade over an extended period of me. Do not depend upon
this odorant as an indica on of leaking gas. We recommend installing a fuel gas
and carbon monoxide detector.
*Drain and ush tank and remove
and inspect anode rod a er rst six
months of opera on and at least
annually therea er. Operate the
Temperature and Pressure Relief Valve
(T&P) annually and inspect T&P valve
every 2-4 years (see the label on the
T&P valve for maintenance schedule).
See the Maintenance sec on for more
informa on about maintaining this
water heater.
4 • Residen al Gas Water Heater Use and Care Guide for Manufactured Homes
SAFETY
IMPORTANT SAFETY INFORMATION
T
o reduce the risk of property
damage, serious injury or death,
read and follow the precau ons below,
all labels on the water heater, and
the safety messages and instruc ons
throughout this manual.
RISKS DURING
INSTALLATION AND
MAINTENANCE
Li ing Risk
WARNING! The
water heater is heavy.
Follow these
precau ons to reduce
the risk of property damage, injuries
from li ing or impact injuries from
dropping the water heater.
Use at least two people to li the
water heater.
Be sure you both have a good grip
before li ing.
Use an appliance dolly or hand
truck to move the water heater.
Explosion Risk
WARNING! Read the water heaters
ra ng plate to determine the type of
gas required. Failure to follow these
instruc ons can result in serious injury
or death from explosion, re or
carbon monoxide poisoning.
Do not connect a natural gas water
heater to an L.P. gas supply.
Do not connect an L.P. gas water
heater to a natural gas supply.
Use a new CSA approved gas
supply line.
Install a shut-o valve on the gas
supply line.
Do not use this water heater
with any gas other than the one
listed on the original ra ng plate
unless the water heater has been
properly converted. Refer to the
Gas Conversion sec on of this
manual to convert from one gas
type to another. See page 23.
Gas Pressure
WARNING! The gas supply pressure
must not exceed the maximum supply
pressure as stated on the water
heater’s ra ng plate. The minimum
supply pressure is for the purpose of
input adjustment. L.P. gas supply
pressure must not exceed 13” water
column. Have a quali ed person
(licensed plumber, gas company
personnel, or authorized service
technician) check for proper L.P. gas
pressure. L.P. gas pressures exceeding
13” water column can result in serious
injury or death from explosion or re.
RISKS DURING
OPERATION
Scalding Risk
This water heater
can make water hot
enough to cause severe burns instantly,
resul ng in severe injury or death.
Feel water before bathing or
showering.
To reduce the risk of scalding,
install Thermosta c Mixing Valves
(temperature limi ng valves) at
each point-of-use. These valves
automa cally mix hot and cold
water to limit the temperature at
the tap. Follow manufacturers
instruc ons for installa on and
adjustment of the valves.
The gas control valve on this water
heater has been factory set to its
lowest se ng to reduce the risk
of scalding. Higher temperatures
increase the risk of scalding, but
even at 120°F, hot water can
scald. If you choose a higher
temperature se ng, Thermosta c
Mixing Valves located at each
point-of-use are par cularly
important to help avoid scalding.
Table 1
Temperature
Time to Produce
a Serious Burn
120°F (49°C) More than 5 minutes
125°F (52°C) 1½ to 2 minutes
130°F (54°C) About 30 seconds
135°F (57°C) About 10 seconds
140°F (60°C) Less than 5 seconds
145°F (63°C) Less than 3 seconds
150°F (66°C) About 1½ seconds
155°F (68°C) About 1 second
For informa on about changing the
factory temperature se ng, refer
to the “Adjus ng the Temperature”
sec on in this manual (page 29).
Even if you set the water heaters gas
control valve to a low se ng, higher
water temperatures may occur in
certain circumstances:
In some cases, repeated small draws
of water can cause the hot and cold
water in the tank to “stack” in layers.
If this happens, the water can be as
much as thirty degrees ho er than
the gas control valve se ng. This
temperature varia on is the result
of your usage pa ern and is not a
malfunc on.
Water temperature will be ho er if
someone adjusted the gas control
valve to a higher se ng.
Problems with the gas control
valve or other malfunc ons may
Residen al Gas Water Heater Use and Care Guide for Manufactured Homes • 5
SAFETY
IMPORTANT SAFETY INFORMATION
result in higher than expected water
temperatures.
If the water heater is in a hot
environment, the water in the
tank can become as hot as the
surrounding air, regardless of the
temperature se ng.
If the water supplied to the water
heater is pre-heated (for example,
by a solar system) the temperature
in the tank may be higher than the
water heaters temperature se ng.
Should overhea ng occur or the
burner fail to shut o , turn o the
manual gas supply valve to the water
heater and call a quali ed person.
To reduce the risk of unusually hot
water reaching the xtures in the
house, install Thermosta c Mixing
Valves at each point-of-use.
If anyone in your home is at par cular
risk of scalding (for example, the elderly,
children, or people with disabili es)
or if there is a local code or state law
requiring a certain water temperature
at the hot water tap, these precau ons
are par cularly important.
According to a na onal standard (ASSE
1070) and many local plumbing codes,
the water heaters gas control valve
should not be used as the sole means
to regulate water temperature and
avoid scalds.
Properly adjusted Thermosta c Mixing
Valves installed at each point-of-use
allow you to set the tank temperature
to a higher se ng without increasing
risk of scalds. A higher temperature
se ng allows the tank to provide
much more hot water and can help
provide proper water temperatures
for appliances such as dishwashers
and washing machines. Higher tank
temperatures (140°F) also kill bacteria
that cause a condi on known as “smelly
water” and can reduce the levels
of bacteria that cause water-borne
diseases.
Water Contamina on Risk
Do not use chemicals that could
contaminate the potable water supply.
Do not use piping that has been treated
with chromates, boiler seal, or other
chemicals.
Fire Risk
This water heater is
equipped with a
Flammable Vapor Igni on
Resistance (FVIR) system.
FVIR is designed to reduce the risk of
ammable vapor-related res. FVIR
makes this product more sensi ve to
installa on errors or improper
installa on environments. The FVIR
system will not prevent a possible re/
explosion if the igniter is depressed and
ammable vapors have accumulated in
the combus on chamber with the pilot
light o .
Do not a empt to light this appliance,
or depress the igniter bu on, if you
suspect ammable vapors have
accumulated inside or outside the
appliance. Immediately call a quali ed
person to inspect the appliance. Water
heaters subjected to a ammable vapors
incident will show a discolora on on the
ame arrestor and require replacement
of the en re water heater. Improper
installa on or an inadequate air supply
can also cause the FVIR system to disable
the water heater.
To reduce the risk of a re that could
result in property damage, or serious
injury or death:
Do not store things that can burn
easily such as paper or clothes next
to the water heater.
Do not store or use gasoline or other
ammable substances in the vicinity
of this or any other appliance.
Keep the water heater from
becoming wet. Immediately shut
the water heater o and have it
inspected by a quali ed person if you
nd that the wiring, thermostat(s)
or surrounding insula on have been
exposed to water in any way (e.g.,
leaks from plumbing, leaks from
the water heater itself can damage
property and could cause a re risk).
If the water heater is subjected to
ood condi ons or the thermostat(s)
have been submerged in water,
the en re water heater must be
replaced.
Replace the water heaters viewport
if glass is missing or damaged. Repair
the combus on chamber door seals
if damaged.
Explosion Risk
High temperatures and
pressures in the water
heater tank can cause an explosion
resul ng in property damage, serious
injury or death. A new Temperature
and Pressure (T&P) Relief Valve is
included with your water heater to
reduce risk of explosion by discharging
hot water. Addi onal temperature and
pressure protec ve equipment may be
required by local codes.
A na onally recognized tes ng
laboratory maintains periodic
inspec on of the valve produc on
process and cer es that it meets the
requirements for Relief Valves for Hot
Water Supply Systems, ANSI Z21.22.
The T&P Relief Valve’s relief pressure
must not exceed the working pressure
ra ng of the water heater as stated on
the ra ng plate.
6 • Residen al Gas Water Heater Use and Care Guide for Manufactured Homes
SAFETY
IMPORTANT SAFETY INFORMATION
Maintain the T&P Relief Valve properly.
Follow the maintenance instruc ons
provided by the manufacturer of the
T&P Relief Valve (label a ached to T&P
Relief Valve). An explosion could occur
if the T&P Relief Valve or discharge
pipe is blocked. Do not cap or plug the
T&P Relief Valve or discharge pipe.
Fire and Explosion Risk if Hot Water is
Not Used for Two Weeks or More.
CAUTION! Hydrogen gas builds up
in a hot water system when it is not
used for a long period (two weeks or
more). Hydrogen gas is extremely
ammable. If the hot water system
has not been used for two weeks or
more, open a hot water faucet for
several minutes at the kitchen sink
before using any electrical appliances
connected to the hot water system. If
hydrogen is present there will
probably be an unusual sound such as
air” escaping through the pipe as hot
water begins to ow. Do not smoke or
have an open ame or other igni on
source near the faucet while it is
open.
Carbon Monoxide Risk
WARNING! This water heater
operates by burning gas.
Carbon monoxide is a
colorless, odorless
gas that is a by-
product of burning of
fuels such as coal,
wood, charcoal, oil,
kerosene, propane, and natural gas.
Breathing excessive and abnormal
amounts of carbon monoxide can
cause carbon monoxide poisoning,
resul ng in serious injury or death.
This water heater must be supplied
with adequate combus on air and
must be properly vented to the
outdoors. Have a quali ed person
(licensed plumber, authorized gas
company personnel, or authorized
service technician) install the ven ng
system using these installa on
instruc ons as well as those provided
by the roof jack manufacturer.
Install a fuel gas and carbon
monoxide detector in the living
areas of your home.
Do not install this water heater
in the occupied space of the
manufactured (mobile) home.
Failure to follow these instruc ons
can result in serious injury or
death from carbon monoxide
poisoning.
Burn Risk
This water heaters
ven ng system can
become hot enough to burn. Do not
touch the ven ng system while water
heater is on, or un l the water heater
is turned o and the ven ng allowed
to cool.
Installa on Accessories
Figure 1:Gas Water Heater Hook-Up Kit
Figure 2:Install a Pressure Reducing Valve set to
50 to 60 PSI.
Residen al Gas Water Heater Use and Care Guide for Manufactured Homes • 7
GETTING STARTED
GETTING STARTED
1
Review all of the instruc ons
before you begin work.
Improper installa on can
damage the water heater, your home
and other property, and can present
risks of serious injury or death.
2
This water heater is design-
cer ed by CSA Interna onal
as a Category I, non-direct
vented water heater which takes its
combus on air through openings in an
enclosure. (See Enclosure InstallaƟ on
Requirements.) This water heater must
be installed according to all local and
state codes or, in the absence of local
and state codes, the “Na onal Fuel Gas
Code”, ANSI Z223.1(NFPA 54)-current
edi on. This is available from the
following:
CSA America, Inc.
8501 East Pleasant Valley Road
Cleveland, OH 44131
Na onal Fire Protec on Associa on
1 Ba erymarch Park
Quincy, MA 02269
Manufactured home manufacturers:
The installa on must conform to The
Manufactured Home ConstrucƟ on
and Safety Standard, Title 24 CFR, Part
3280. This standard is available through
the U.S. Department of Housing and
Urban Development (HUD), 451 7th
Street S.W., Washington D.C. 20410.
Check with local code o cials about
codes governing this installa on. Have
your installa on inspected by a code
o cial to ensure the installa on meets
all local codes.
NOTICE: If you lack the necessary skills
required to properly install this water
heater, or you have di culty following
the instruc ons, you should not proceed
but have a quali ed person perform the
installa on of this water heater.
Massachuse s code requires this water
heater to be installed in accordance
with Massachuse s 248-CMR 2.00 and
248-CMR 5.00: State Plumbing Code.
Other local and state authori es may
have similar requirements or other
codes applicable to the installa on of
this water heater.
NOTICE: The state of California re-
quires bracing, anchoring, or strapping
the water heater to avoid its moving
during an earthquake. Contact local
u li es for code requirements in your
area, visit h p://www.dsa.dgs.ca.gov,
or call 1-916-445-8100 and request
instruc ons. Other loca ons may have
similar requirements. Check with your
local and state authori es.
3
Before you start, be sure you
have the following tools and
supplies:
Common plumbing tools
(depending on what type of water
pipes you have).
Te on® tape or pipe joint
compound approved for potable
water.
For homes with copper pipes, you
may purchase a Gas Water Heater
Hook-Up Kit (available at your local
hardware store ) with compression
ngs that don’t require soldering.
This kit includes two 12” ex water
lines, two compression ngs, an
18” exible gas line, two nipples,
and Te on® tape.
For homes with plas c pipe, use
threaded connectors suitable for
the speci c type of plas c pipe
used: CPVC or PEX (cross-linked
polyethylene). Do not use PVC
pipe.
Non-corrosive gas leak detec on
solu on made from hand
dishwashing soap mixed with water
(1 part soap to 15 parts water)
or children’s soap bubbles and a
small, so -bristled brush.
An appliance dolly or hand truck to
move the water heater.
Recommended Accessories:
A metal drain pan.
Automa c water leak detec on
and shut-o device.
Pressure Reducing Valve.
Thermal Expansion Tank.
Thermosta c Mixing Valves at each
point-of-use.
Fuel gas and carbon monoxide
detector.
4
Review the following
requirements and
recommenda ons before
installing the water heater.
Vent System
Requirements
WARNING! Carbon Monoxide
Hazard. This water heater must be
supplied with adequate air and vented
to outdoors. The vent system must be
installed by a quali ed person.
Examples of a quali ed person include
gas technicians, authorized gas
company personnel, and authorized
service technicians. Failure to properly
vent the water heater can result in
severe injury or death from carbon
monoxide poisoning.
To reduce the risk of carbon monoxide
poisoning, install a fuel gas and carbon
monoxide detector. Install and maintain
the detector in accordance with the
manufacturers instruc ons and local
codes.
This water heater uses a direct vented,
8 • Residen al Gas Water Heater Use and Care Guide for Manufactured Homes
GETTING STARTED
Figure 3: Enclosure Configurations
GETTING STARTED
single-pipe vent system to remove
exhaust gases created by the burning
of fossil fuels. Air for combus on
is ducted in from the outside (see
Enclosure InstallaƟ on Requirements).
This water heater must be properly
vented for the removal of exhaust
gases to the outside atmosphere.
Correct installa on of the vent pipe
system is mandatory for the proper
and e cient opera on of this water
heater and is an important factor in the
life of the unit.
The vent pipe must be installed
according to all local and state codes
or, in the absence of local and state
codes, the NaƟ onal Fuel Gas Code,
ANSI Z223.1 (NFPA 54)-current edi on.
Manufactured home manufacturers
must conform with The Manufactured
Home ConstrucƟ on and Safety
Standard, Title 24 CFR, Part 3280.
The vent pipe installa on must not
be obstructed so as to prevent the
removal of exhaust gases to the
outside atmosphere.
IMPORTANT:
Do not use a vent damper anywhere
in the vent system of this water
heater.
DO not common vent this water
heater with any other appliance.
• This water heater must have a
properly-installed dra hood and be
connected to a listed roof jack that
terminates to the outdoors. The
roof jack vent pipe must be secured
to the ue reducer with sheet metal
screws. (Roof jack not furnished.)
The following roof jack models are
cer ed for use with this water heater
and are available from your water
heater supplier:
Roof Jack for roof pitch of 7-12 or less:
TABLE 2
KIT NUMBER MAXIMUM LENGTH
BETWEEN ROOF
AND CEILING
100285331 12”
100285333 32”
100285412 60”
100285414 95”
Install the roof jack according to its
manufacturers instruc ons.
AIR INTAKE
OPENING
MANUFACTURED HOME
OUTER PIPE OF
ROOF JACK:
0 IN. (0 CM)
MIN. CLEARANCE
DIRECT VENT
WATER HEATER
3” (76 mm) PVC PIPING - 30 AND 40 GAL.
4” (102 mm) PVC PIPING - 50 GAL.
SUPPORT PIPE AT
3-1/2 FT. (1.07 m) INTERVALS
BASEMENT OR
CRAWL SPACE
* VENT CAP MUST BE LOCATED A MINIMUM OF 12” (30.48 cm)
ABOVE GROUND OR ANTICIPATED SNOW LEVEL.
12” MIN.
45° ELBOW
METHOD 1:
AIR INTAKE - MINIMUM OPENING SIZE
METHOD 2:
AIR INTAKE - BASEMENT OR CRAWLSPACE
Residen al Gas Water Heater Use and Care Guide for Manufactured Homes • 9
GETTING STARTED
GETTING STARTED
Enclosure Installa on
Requirements
WARNING! Do not store or use
ammable materials, vapors, or liquids
in the water heater enclosure. Do not
use the enclosure as a storage area.
Whether replacing an old water heater
or pu ng the water heater in a new
loca on, the following cri cal points
must be observed.
This manufactured home gas-
red water heater is for use in a
manufactured home. You should
carefully choose an indoor loca on
for the new water heater, because
the placement is a very important
considera on for the safety of your
occupants in the building and for the
most economical use of the appliance.
This water heater is for use only in a
manufactured home and not intended
for outdoor installa on.
NOTICE: This water heater has been
designed and cer ed as a direct vent
(sealed combus on) unit and no dra
diverter is to be used.
Minimum clearances between the
water heater and combus ble surfaces
are stated on the label adjacent to
the gas control valve/thermostat. The
water heater is cer ed for installa on
on a combus ble oor. Minimum vent
clearances: 6” (15.2 cm). Provide 24”
(61 cm) front clearance for servicing
and adequate clearance between the
jacket top and ceiling for servicing the
ue area. Roof jack: surface of outer
pipe has a minimum clearance of 0” (0
cm).
The combus on and ven la on air ow
must not be obstructed.
Combus on air shall not be supplied
from occupied spaces. Instead,
combus on air must be supplied from
outside the manufactured home by
way of the furnished air intake duct
assembly. The air intake duct assembly
is 3” (7.62 cm) in diameter for 30 and
40 Gallon models or 4” (10.2 cm) in
diameter for 50 Gallon models.
The following methods may be used
to provide su cient combus on and
ven la on air to the water heater when
it is installed in the enclosure. See
Figure 3: Enclosure Con gura ons.
IMPORTANT:
A 3-1/2” (8.89 cm) diameter oor
opening beneath the water heater is
required to accommodate the air intake
duct assembly for 30 and 40 Gallon
models. A 4-1/2” (11.43 cm) diameter
oor opening is required beneath the
water heater for 50 Gallon models. The
weight of the water heater itself seals
the water heater to the air intake duct
assembly.
Method 1
When a manufactured home is skirted,
an air intake opening with a minimum
free area of 32 square inches (206.45
cm²) must be provided in the skirt. If
the opening is covered by louvers or
screen, the total free area must be 32
square inches (206.45 cm²). Other gas
red appliance in the home will require
addi onal free air openings; consult
these manufacturers for correct sizing.
See Figure 3.
Method 2
If the manufactured home is installed
over a basement or crawlspace,
combus on air must be supplied from
outside the manufactured home. The
combus on air intake piping can be
3” (76 mm) PVC for 30 and 40 gallon
models and 4” (102 mm) PVC for 50
Gallon models. The air intake piping
cannot exceed the lengths shown in
Table 3 (page 19), including ver cal
and horizontal runs, or have more than
3 elbows. All horizontal runs require
adequate support at 3-1/2 foot (1.07 m)
intervals. See Figure 3
IMPORTANT: The drain pan must not
cover any por on of the air intake
opening in the oor.
Also, if the manufactured home is
skirted, an air intake opening with a
minimum free area of 32 square inches
must be provided in the skirt. Other
gas red appliances in the home may
require addi onal free air openings.
Consult the manufacturers for correct
sizing.
IMPORTANT:
The water heater must be secured
with brackets/straps as described in
Securing the Water Heater, page 16.
A discharge line must be installed
as described in the typical
installa on graphic. See COMPLETED
INSTALLATION (TYPICAL), page 2.
There must be adequate space
(clearances) for periodic servicing
(e.g., a minimum of 24 inches of
front clearance). The installa on
must allow a minimum clearance
from combus ble surfaces as stated
on the ra ng plate.
It is recommended that the water
heater be installed in a metal drain
pan. The drain pan should be piped
to an adequate drain or through the
structural oor of the enclosure.
Do not obstruct the combus on and
ven la on air openings.
If the water heater is installed directly
on carpe ng, it shall be installed on
10 • Residen al Gas Water Heater Use and Care Guide for Manufactured Homes
GETTING STARTED
a metal or wood panel extending
beyond the full width and depth
of the water heater by at least 3 in
(76.2mm) in any direc on. If the
water heater is installed in an alcove
or closet, the en re oor shall be
covered by the aforestated panel.
Prevent the water lines and
discharge lines from freezing.
General Requirements
The water heater shall not be
installed in the occupied space of
the manufactured (mobile) home.
Inspect and maintain your water
heater in accordance with this
manual’s instruc ons. Inspect the
drain pan, pipes, and surrounding
area regularly and x any leaks
found.
Gas Piping
Requirements
Gas piping must be installed according
to local and state codes or, in the
absence of local and state codes,
the NaƟ onal Fuel Gas Code, ANSI
Z223.1(NFPA 54)-current edi on.
Manufactured home manufacturers
must conform with The Manufactured
Home ConstrucƟ on and Safety
Standard, Title 24 CFR, Part 3280.
NOTICE: When installing gas piping,
apply pipe joint compound or Te on®
tape approved for fuel gases.
Figure 4: Gas Piping
1. Install a readily accessible manual
shut-o valve in the gas supply
line as recommended by the local
u lity. Know the loca on of this
valve and how to turn o the gas to
this unit.
2. Install a Sediment Trap as shown
in the Gas Piping gure
(page 10). The Sediment Trap
must be no less than three inches
long for the accumula on of
dirt, foreign material, and water
droplets.
3. Install a ground joint union
between the gas control valve and
the manual gas shut-o valve. This
is to allow easy removal of the gas
control valve.
4. Turn the gas supply on and check
for leaks. Use a small, so -
bristled brush to apply a hand
dishwashing soap and water
mixture (1 part soap to 15 parts
water) or children’s soap bubbles
to all connec on points of the gas
piping. Saturate all the connec ons
and check for gas leaks (which will
appear as small bubbles). If any
leaks are detected, ghten the
appropriate connec on(s) and
re-check.
Gas Pressure
NOTICE: When tes ng gas pipes with
a test pressure of more than ½ psi (3.5
kPa), disconnect the gas line at the
manual shut o valve and cap the gas
line. Do not subject the water heaters
gas control valve or manual shut o
valve to more than ½ psi (3.5 kPa)
pressure for any reason. If you are
pressure tes ng the gas line with test
pressure of ½ psi (3.5 kPa) or less, you
may isolate the water heater from the
gas line by closing the manual shut o
valve.
LP Gas Only
Lique ed petroleum gas is over 50%
heavier than air and in the occurrence
of a leak in the system, the gas will
se le at oor level. Basements, crawl
spaces, skirted areas under mobile
homes (even when ven lated), closets
and areas below ground level will serve
as pockets for the accumula on of gas.
Before ligh ng an L.P. gas water heater,
smell all around the appliance at oor
level. If you smell gas, do not a empt
to light the water heater. Follow the
instruc ons as given in the warning on
the front cover of this manual.
When your L.P. tank runs out of fuel,
turn o the gas at all gas appliances
including pilot lights. A er the tank is
re lled, all appliances must be re-lit
according to their manufacturers
instruc ons.
WARNING! Have a quali ed person
make sure that the L.P. gas opera ng
pressure does not exceed 13” water
column. Examples of a quali ed
person include: licensed plumbers,
authorized gas company personnel,
and authorized service personnel.
Failure to do so can result in death,
explosion, or re.
GETTING STARTED
Residen al Gas Water Heater Use and Care Guide for Manufactured Homes • 11
INSTALLATION
INSTALLATION
Step 1:
Verify that your
home is equipped
and up-to-date for
proper opera on
Installing a new water heater is the
perfect me to examine your home’s
plumbing system and make sure the
system is up to current code standards.
There have likely been plumbing code
changes since the old water heater
was installed. We recommend install-
ing the following accessories and any
other needed changes to bring your
home up to the latest code require-
ments. Upda ng your plumbing system
can help extend the life of your water
heater, avoid damage to your home
and property, and reduce the risk of
serious injuries or death. Inspect your
home and install any devices you need
to comply with current codes and as-
sure that your new water heater per-
forms at its best. Check with your local
plumbing o cial for more informa on.
Water pressure
Most codes allow a maximum
incoming water pressure of 80 psi
(we recommend a working pressure
no higher than 50-60 psi). Check your
home’s water pressure with a pressure
gauge and adjust if necessary. High
water pressure can damage the water
heater, piping, and other appliances.
HOW: Purchase an inexpensive water
pressure gauge at your local plumbing
supplier. Connect the water pres-
sure gauge to an outside faucet and
measure the maximum water pressure
experienced throughout a 24-hour
period (highest water pressures o en
occur at night).
Figure 5:Use a Water Pressure Gauge to make
sure your home’s water pressure is not too high.
To adjust your home’s water pressure:
Locate your home’s Pressure Reduc-
ing Valve (PRV) on the main incoming
(cold) water supply line and adjust the
water pressure control to between 50
and 60 psi. If your home does not have
a Pressure Reducing Valve, install a
PRV on the home’s main water supply
line and set it to between 50 and 60
psi. Pressure Reducing Valves are avail-
able at your local plumbing supplier.
BACKGROUND: Over the years, many
u li es have increased water sup-
ply pressures so they can serve more
homes. In some homes today, pres-
sures can exceed 100 psi. High water
pressures can damage water heaters,
causing premature leaks. If you have
replaced toilet valves, had a water
heater leak, or had to repair applianc-
es connected to the plumbing system,
pay par cular a en on to your home’s
water pressure. When purchasing a
PRV, make sure the PRV has a built-in
bypass.
Water pressure
increase caused by
thermal expansion
Verify that you have a properly sized
Thermal Expansion Tank. We recom-
mend installing an expansion tank if
your home does not have one. Plumb-
ing codes require a properly pressur-
ized, properly sized Thermal Expansion
Tank in almost all homes.
Figure 6:A Thermal Expansion Tank helps protect
the home’s plumbing system from pressure
spikes.
HOW: Connect the Thermal Expan-
sion Tank (available at most hardware
stores.) to the cold water supply line
near the water heater. The expansion
tank contains a bladder and an air
charge. To work properly, the Thermal
Expansion Tank must be sized accord-
ing to the water heaters tank capacity
and pressurized to match the home’s
incoming water pressure. Refer to the
instruc ons provided with the Thermal
Expansion Tank for installa on details.
BACKGROUND: Water expands when
heated, and the increased volume
of water must have a place to go, or
thermal expansion will cause large
increases in water pressure (despite
12 • Residen al Gas Water Heater Use and Care Guide for Manufactured Homes
INSTALLATION
INSTALLATION
the use of a Pressure Reducing Valve
in the home’s main water supply line).
The Safe Drinking Water Act of 1974
requires the use of back ow preven-
ters and check valves to restrict water
from your home reentering the public
water system. Back ow preventers
are o en installed in water meters
and may not be readily visible. As
a result, most all plumbing systems
today are now “closed,” and almost all
homes now need a Thermal Expan-
sion Tank.
A Thermal Expansion Tank is a prac -
cal and inexpensive way to help avoid
damage to the water heater, washing
machine, dishwasher, ice maker, and
even toilet valves. If your toilet oc-
casionally runs for no apparent reason
(usually brie y at night), that may be
due to thermal expansion increasing
the water pressure temporarily.
Water Pipe and
Tank Leaks
Metal Drain Pan
Piped to Drain
Figure 7:A metal drain pan piped through the
floor to the outside (or to an adequate drain)
can help protect flooring from leaks and drips.
Leaks from plumbing pipes or from
the water heater itself can damage
property and could cause a re risk.
Install an automa c leak detec on
and shuto device (available at your
local plumbing supplier ). These de-
vices can detect water leaks and can
shut o the water heaters water
supply if a leak occurs.
Install a metal drain pan ( available at
your local plumbing supplier) under
the water heater to catch conden-
sa on or leaks from the piping
connec ons or tank. Most codes
require, and we recommend, install-
ing the water heater in a metal drain
pan that is piped through the oor
to the outside or to an adequate
drain. The drain pan must be at least
two inches wider than the diameter
of the water heater. Install the drain
pan so the water level would be lim-
ited to a maximum depth of 1-3/4”.
The pan must not restrict air ow to
the burner.
Water
Temperature
Regula on
Install Thermosta c Mixing Valves to
regulate the temperature of the water
supplied to each point-of-use (for
example, kitchen sink, bathroom sink,
bath, shower). Install and adjust the
mixing valve according to its manufac-
turers instruc ons.
WARNING! Even if the water
heater’s thermostat is set to a
rela vely low temperature, hot water
can scald. Install Thermosta c Mixing
Valves at each point-of-use to reduce
the risk of scalding.
Figure 8:Thermostatic Mixing Valves installed at
each point-of-use can help avoid scalding
BACKGROUND: A Thermosta c Mix-
ing Valve, installed at each point-
of-use, mixes hot water from the
water heater with cold water to more
precisely regulate the temperature of
hot water supplied to xtures. If you
aren’t sure if your plumbing system is
equipped with properly installed and
adjusted Thermosta c Mixing Valves
at each point where hot water is used,
contact a quali ed person.
Step 2:
Ensure that the
enclosure is prepared
for installa on
WARNING! Do not store or use
ammable materials, vapors, or
liquids in the same loca on where this
water heater is installed.
Before installing your water heater,
ensure that the water heater can be:
Installed in an enclosure that
meets the requirements
outlined in Enclosure InstallaƟ on
Requirements (page 9).
Protected from freezing.
Set in a metal drain pan piped to
an adequate drain.
Residen al Gas Water Heater Use and Care Guide for Manufactured Homes • 13
INSTALLATION
INSTALLATION
Provided with adequate space
(clearances) for periodic servicing.
(There must be a minimum of 24
inches of front clearance.)
Installed with a minimum clear-
ance from combus ble surfaces as
stated on the ra ng plate.
Installed on a oor that can sup-
port the weight of a water heater
full of water.
A 3-1/2” (8.89 cm) diameter oor
opening beneath the water heater
is required to accommodate the
air intake duct assembly for 30 and
40 Gallon models. A 4-1/2” (11.43
cm) diameter oor opening is
required beneath the water heater
for 50 Gallon models. The weight
of the water heater itself seals the
water heater to the air intake duct
assembly.
NOTICE: The state of California requires
bracing, anchoring, or strapping the
water heater to avoid its moving during
an earthquake. Contact local utilities
for code requirements in your area,
visit http://www.dsa.dgs.ca.gov, or call
1-916-445-8100 and request instruc-
tions. Other locations may have similar
requirements. Check with your local and
state authorities. See also Securing the
Water Heater (page 16).
Step 3:
Removing the old
water heater
1
Read each installa on step and
decide if you have the necessary
skills to install the water heater.
Only proceed if you are comfortable you
can safely perform the work. If you are
not sure, have a quali ed person perform
the installa on.
2
On the old water heater, turn
the control knob on the gas
control valve to the
OFF posi on.
Figure 9:Turn gas control/temperature knob OFF.
3
Turn the manual gas valve for
the water heaters supply line
OFF.
4
Open a hot water faucet and
let the hot water run un l it is
cool. (This may take 10
minutes or longer.)
Figure 10:Let the hot water run until it is cool.
WARNING! Be sure the water runs
cool before draining the tank to reduce
the risk of scalding.
5
Connect a garden hose to the
drain valve and place the
other end of the hose in a
drain, outside, or in buckets. (Sedi-
ment in the bo om of the tank may
clog the valve and prevent it from
draining. If you can’t get the tank to
drain, contact a quali ed person.)
6
Turn the cold water supply
valve OFF.
Figure 11:Cold water supply in off position.
7
Using a standard at-blade
screwdriver, open the drain
valve. Sediment build up in
the bo om of the water heater may
hinder or prevent draining.
Figure 12:Draining the old water heater.
8
Also open a hot water faucet
to help the water in the tank
drain faster.
9
When the tank is empty,
disconnect the Temperature &
Pressure (T&P) Relief Valve
discharge pipe. You may be able to
reuse the discharge pipe, but do not
reuse the old T&P Relief Valve. A new
T&P Relief Valve comes with your new
water heater.
14 • Residen al Gas Water Heater Use and Care Guide for Manufactured Homes
INSTALLATION
INSTALLATION
Figure 13:Removing the T&P Relief Valve
discharge pipe.
10
Allow the vent pipe (roof
jack) and dra hood to cool.
Once cooled, disconnect the
vent pipe from the dra hood. You
may need to support the vent pipe
un l the new water heater is in place.
Figure 14:Disconnect the vent pipe (roof jack)
from the draft hood.
11
Disconnect the water pipes.
Many water pipes are
connected by a threaded
union which can be disconnected with
wrenches. If you must cut the water
pipes, cut the pipes close to the water
heater’s inlet and outlet connec ons,
leaving the water pipes as long as
possible. If necessary, you can make
them shorter later when you install the
new water heater.
12
Con rm the manual gas valve
for the water heater’s supply
line is turned o . Disconnect
the gas line from the water heaters
gas control valve and cap it.
13
Remove the old water heater.
Use an appliance dolly or
hand truck to move the water
heater.
WARNING! Use two or more
people to remove or install a water
heater. Failure to do so can result in
back or other injury.
Step 4:
Installing the New
Water Heater
1
Completely read all instruc-
ons before beginning. If you
are not sure you can safely
complete the installa on, seek assis-
tance from any of the following sources:
Schedule an appointment with
a quali ed person to install your
water heater.
Contact the manufacturer listed on the
water heaters ra ng plate .
2
Locate the posi on of the
3-1/2” (8.9 cm) or 4-1/2”
(11.4 cm) hole to be cut in the
oor, see Figures 15 and 16.
METAL
DRAIN
PAN
“A” = 4-3/8” (11.11 cm) 30 GAL.
“A” = 5-3/8” (13.65 cm) 40 GAL.
“A” = 5-3/8” (13.65 cm) 50 GAL.
CENTERLINE
OF WATER
HEATER
3-1/2” (8.89cm) DIA. HOLE
(30 & 40 GALLON)
4-1/2” (11.43cm) DIA. HOLE
(50 GALLON)
APPLY 4” (10.2 cm) OR
5” (12.7 cm) CIRCLE OF
SILICONE AROUND THE
BOTTOM OF PLATE
FOR PROPER WATER
TIGHT SEALING
AFTER ADJUSTING LENGTH OF DUCT
ASSEMBLY AS SHOWN ABOVE, CAULK
ALL AROUND PIPING WITH RTV SILICON
SEALANT FOR AIR TIGHT SEAL BEFORE
INSTALLING IN FLOOR CAVITY.
ALTERNATIVE: USE 2” (5 cm) WIDE BAND
OF .002 ALUMINUM TAPE.
2-1/2” (6.35 cm) MIN.
BOTTOM OF FLOOR
“A”
SCREWS (2)
Figure 15:Air Intake Duct Sizing Dimensions
3
Set the water heater in place
taking care not to damage the
drain pan. When installing
directly on carpet, the water heater
must be installed on a wood or metal
base that extends beyond the dimen-
sions of the water heater (width and
depth) by at least 3 inches (76.2 mm)
in any direc on. If the water heater is
installed on carpet in an alcove or
closet, the en re oor must be covered
by a wood or metal panel.
NOTICE: Most codes require se ng
the water heater in a metal drain pan
piped to an adequate drain or external
to the structure. The drain pan helps
avoid property damage which may oc-
cur from condensa on or leaks in the
piping connec ons or tank. The drain
pan must be at least two inches wider
than the diameter of the water heater.
Install the drain pan so the water level
is limited to a maximum depth of
1-3/4”.
Residen al Gas Water Heater Use and Care Guide for Manufactured Homes • 15
INSTALLATION
INSTALLATION
4
Verify that the water heater is
set in place properly. Check
that:
There is adequate space to install
the T&P Relief Valve discharge
pipe and that it can be piped to a
separate drain (and not into the
drain pan).
There is adequate access and
space around the water heater for
future maintenance.
The water heater is installed ver cally.
Figure 16:Air Intake Duct Installation - Drain Pan
CENTER
LINE OF
FLUE
GAS CONTROL VALVE/
THERMOSTAT
DIRECTION IN WHICH WATER HEATER CAN BE PLACED
WHEN INCREASED SIDE CLEARANCE IS AVAILABLE
9”(22.86 cm) MIN. -30 GAL.
10”(25.4 cm) MIN. -40 GAL.
11”(27.9 cm) MIN. -50 GAL.
9”(22.86 cm) MIN. -30 GAL.
10”(25.4 cm) MIN. -40 GAL.
11”(27.9 cm) MIN. -50 GAL.
0” MIN.
30 GAL. 13-13/32”
(34 cm) MIN.
40 GAL. 15-13/32”
(39.1 cm) MIN.
50 GAL. 16-13/32”
(41.7 cm) MIN.
2-1/2” 6.35 cm
4-13/32”(11.2 cm) - 30 GAL.
5-13/32”(13.7 cm) - 40 GAL.
5-13/32”(13.7 cm) - 50 GAL.
4”(10.16 cm) MIN. - 30 GAL.
0” MIN. - 40 & 50 GAL.
0” MIN.
BASE DIAMETER
14”(35.56 cm) MIN. 30 GAL.
16”(40.64 cm) MIN. 40 GAL.
16”(40.64 cm) MIN. 50 GAL.
JACKET DIAMETER
18”(45.72 cm) MIN. 30 GAL.
20”(50.80 cm) MIN. 40 GAL.
22”(55.88 cm) MIN. 50 GAL.
30 GAL. T&P LOC.
AIR INTAKE
4” (10.2cm) MIN.
Figure 17:Water Heater Installation - Enclosure
2-7/32” (5.59 cm)
12-13/16”
(32.54 cm)
9”
(22.86 cm)
3-13/16”
(9.68 cm)
4” (10.16 cm)
GAS CONTROL VALVE / THERMOSTAT
DIRECTION IN WHICH WATER HEATER MUST BE
PLACED WHEN MINIMUM CLEARANCES ARE USED
(30 GALLON ONLY)
0” MIN.
0” MIN.
0” MIN.
BASE DIA. - 14”
(35.56 cm)
JACKET DIA. - 18”
(45.72 cm)
60°
30°
TOP VIEW
Figure 18:Water Heater Installation - Enclosure Alternate Position
16 • Residen al Gas Water Heater Use and Care Guide for Manufactured Homes
INSTALLATION
INSTALLATION
5
Insert the duct assembly as
shown in Figure 19 with lip
facing forward, and using only
nails, secure the duct assembly to
the oor.
FRONT
APPLY 4” (10.16 cm) OR 5” (12.7 cm)
CIRCLE OF SILICONE AROUND OPENING
FOR AIR TIGHT SEAL.
Figure 19:Air Intake Duct Sizing Installation
6
Set the water heater in place
against the lip of the duct
assembly as shown in Figure 20.
Figure 20: Setting the Water Heater in place.
7
Secure the water heater to the
duct assembly using the screw
provided.
NOTICE: See pages 17 and 18 for
installing an air intake through an
outside wall when the manufactured
home is located over a basement or
crawl space.
SECURING WATER
HEATER TO THE FLOOR
AND WALL (USE
METHOD A OR B)
The water heater must be secured to
the floor and to the wall of the enclo-
sure.
METHOD A: use the three mounting
brackets and screws packaged in the
carton with the water heater. The two
small brackets are used to attach the
water heater to the floor and the one
large bracket is used to secure the
top of the water heater to the wall.
METHOD B: use metal tape also
called “plumbers tape” to secure the
water heater to the enclosure. See
the figure below as reference for
attaching the tape.
Because of installation variances,
these brackets can be located at any
points around the circumference of
the jacket. When the bracket loca-
tions are determined, use a 1/8 inch
SAE drill bit to set a pattern. Drill only
through the outer jacket of the water
heater. Then using the screws pro-
vided, secure the bracket to the water
heater, floor and wall. See Figure 21.
ONE LARGE MOUNTING
BRACKET AT TOP
TWO SMALL MOUNTING
BRACKETS AT BOTTOM
TWO STRAPS OF METAL
TAPE AT THE TOP
TWO STRAPS OF METAL
TAPE AT THE BOTTOM
METHOD A METHOD B
Figure 21:Methods to secure the water heater
Residen al Gas Water Heater Use and Care Guide for Manufactured Homes • 17
INSTALLATION
INSTALLATION
MANUFACTURED
HOME INSTALLED OVER
BASEMENT OR CRAWL
SPACE - AIR INTAKE
THROUGH AN OUTSIDE
WALL
ALL 30 AND 40 GALLON MODELS
3” (76 mm) PVC Schedule 40 intake air
vent piping:
Op onal Kit No. 100109072 contains a
3” (76 mm) PVC Schedule 40-45° vent
cap with screen and two 3” (76 mm)
wall collars.
ALL 50 GALLON MODELS
4” (102 mm) PVC Schedule 40 intake air
vent piping:
Op onal Kit no. 100109073 contains a
4” (102 mm) PVC Schedule 40-45° vent
cap with screen and two 4” (102 mm)
wall collars.
ALL MODELS
1. PVC, ABS or CPVC Schedule 40
piping and ngs are acceptable
materials for the air intake vent
system.
2. The intake air vent system must
terminate horizontally to the
outdoors.
3. Remove the screws which a ach
the wind ba e to the exis ng
metal air intake vent pipe
underneath the home. Discard the
wind ba e and screws. See Figure
22.
IF ATTACHING INLET PIPING, REMOVE AND
DISCARD SCREWS AND WIND BAFFLE
Figure 22:Wind Baffle
4. A ach a 3” (76 mm) or 4” (102
mm) PVC street elbow to the metal
air intake vent using 3 sheet metal
screws. Con nue PVC piping to
outside wall and terminate with
vent cap and screen. See
Figure 23 and Table 3.
3” (76 mm) size - 30 and 40 gallon
models.
4” (102 mm) size - 50 gallon models.
See pages 13 and 14 for cementing
instructions.
SEE MAXIMUM
COMBINED
LENGTHS IN
TABLE 1.
SLOPE INLET PIPING
DOWNWARD TOWARD
VENT CAP TO PREVENT
CONDENSATION BUILDUP.
Figure 23:Inlet Air Installation
NOTICE: Vent cap must be located a
minimum of 12” (30.48 cm) above the
ground or an cipated snow level.
Table: 3
Water
Heater Gas
Vent
Dia.
Do Not
Exceed:
30 Gal NAT
3”
(76mm)
17 . (5.18 m)
length; 3 elbows
30 Gal LP
3”
(76mm)
12 . (3.66 m)
length; 3 elbows
40 Gal NAT
3”
(76mm)
30 . (9.1 m)
length; 3 elbows
40 Gal LP
3”
(76mm)
20 . (6.1 m)
length; 3 elbows
50 Gal NAT
4”
(102mm)
30 . (9.1 m)
length; 3 elbows
50 Gal LP
4”
(102mm)
30 . (9.1 m)
length; 3 elbows
5. Ver cal and horizontal runs must
be securely supported at 3-1/2 foot
(1.07 m) intervals. See Figure 20.
SLOPE INLET PIPING
DOWNWARD TOWARD
VENT CAP TO PREVENT
CONDENSATION BUILDUP.
Figure 24:Inlet Air Pipe Supports
6. The intake air vent piping can be
installed with no more than 3
elbows. See Figure 25.
Figure 25: Air Intake
18 • Residen al Gas Water Heater Use and Care Guide for Manufactured Homes
INSTALLATION
INSTALLATION
CUTTING OPENING THROUGH
AN OUTSIDE WALL AND COLLAR
INSTALLATION
Determine the loca on for the opening
in the wall. For a 30 or 40 gallon
model, cut a 3-3/4” (9.5 cm) hole
through the outside wall. For a 50
Gallon model, cut a 4-3/4” (12 cm)
hole through the outside wall.
The 3” (76 mm) or 4” (102 mm) PVC,
ABS or CPVC Schedule 40 vent pipe can
be run from the water heater through
the wall or from the wall to the water
heater, whichever is most convenient.
The vent pipe must extend a minimum
of 1-1/2” (3.81 cm) through the
exterior wall. Note that the inside
collar must be slipped over the vent
piping before loca ng the pipe through
the wall. Before securing the inside
and outside collars to the wall, use
a silicone sealer between pipe and
opening to ensure a water and air ght
seal. See Figure 26.
INSTALLATION SHOWING USE
OF PVC, ABS OR CPVC PIPE
SILICONE
SEALER
EXTERIOR WALL
SCREW SCREW
SCREW
SCREW
1-1/2” (3.81cm) MIN. EXTENSION
THROUGH EXTERIOR WALL
COLLAR
COLLAR
SILICONE
SEALER
SCREEN
VENT CAP MUST BE
POSITIONED DOWNWARD
INLET PIPE SURFACE
MIN. CLEARANCE 0” (0cm)
Figure 26:Outside Wall Inlet Air Installation
NOTICE: Wall collars are for aesthetic
purposes and are not required for the
heater to operate.
CEMENTING PVC, ABS OR CPVC
PIPE AND FITTINGS
Read and observe all safety
informa on printed on primer, cleaner,
and cement containers.
Primer, cleaner, and cements are
extremely ammable. They are
harmful or fatal if swallowed. The
vapors are harmful. They may irritate
eyes and skin and can be absorbed
through the skin.
Always store primer, cleaner, and
cements in cool, dry, well ven lated
places. Keep containers closed. Use
them in well ven lated areas. Wear
impervious clothing while handling.
Do not smoke, eat, or drink while
handling. Wash thoroughly a er
handling and before ea ng. Wear
eye protec on when handling. If
swallowed, drink water, do not induce
vomi ng, and call a physician or
poison control center immediately. If
inhaled, get fresh air and seek medical
a en on if ill feelings persist. In case
of eye and skin contact, immediately
ush with plenty of water for 15
minutes and seek medical a en on if
irrita on persists. KEEP OUT OF REACH
OF CHILDREN.
All primers, cleaners, and cements
must meet all local codes and
applicable standards of the American
Society For Tes ng Materials
Standards.
Before using primers, cleaners and
cements, s r or shake, making sure
contents are liquid. Do not use if found
to be lumpy or jelly-like.
1. Cut pipe ends squarely removing all
burrs and dirt.
2. Dry t pipe and ngs to be
connected for proper t.
3. Clean pipe and ng with primer/
cleaner.
4. Apply a thin coat of cement to
ng, avoiding puddling inside.
5. Apply a liberal coat of cement to
pipe, leaving no voids.
6. QUICKLY assemble parts while
cement is uid! If you wait too long,
recoat pipes.
7. Push pipe completely into socket
of ng, turning as it goes un l it
bo oms.
8. Hold pipe and ng together for
30 seconds. Then carefully clean
o excess with a cloth. Allow
connec ons a su cient me to cure
before disturbing.
9. Remember that vent pipes must be
adequately and securely supported.
TABLE 4: APPROX. SETTING TIME
FOR 2-1/2” (63.5mm) TO 4” (102mm)
PIPE JOINTS
MOVEMENT
OF JOINT
COMPLETE
SET
90°F
(32.2°C)
TO 150°F
(65.6°C)
3/4HR. 8 HRS.
50°F (10°C)
TO 90°F
(32.2°C)
1 HR. 15 HRS.
0°F
(-17.77°C)
TO 50°F
(10°C)
1-1/3 HR. 18 HRS.
Residen al Gas Water Heater Use and Care Guide for Manufactured Homes • 19
INSTALLATION
ROOF JACK KIT MODELS VENT KIT- 12 INCH (100288331), VENT KIT - 32 INCH (100285333),
VENT KIT - 60 INCH (100285412) AND VENT KIT - 95 INCH (100285414)
INLET VENT: SURFACE OF PIPE HAS MINIMUM CLEARANCE OF 0” (0 CM)
VENT KIT / 95” (241.3 cm)
VENT KIT / 60”
(152.4 cm)
ADJ. 0-30.26°
MAX. PITCH 7-12
VENT KIT / 32” (81.28 cm)
VENT KIT / 12” (30.48 cm)
95” (241.3 cm)
36” (91.4 cm)
2” (5 cm) MIN.
136” (345.44 cm) MAX. 100” (254 cm) MAX.
55” (139.7 cm) MIN.
2” (5 cm) MIN. 2” (5 cm) MIN. 2” (5 cm) MIN.
40” (101.6 cm) MIN.
72” (182.88 cm) MAX.
25” (63.5 cm) MIN.
52” (132.08 cm) MAX.
18” (45.72 cm) MIN.
23” (58.42 cm) MAX.
30.26° MAX.
ROOF JACK: SURFACE OF OUTER PIPE
HAS A MINIMUM CLEARANCE OF 0” (0 CM).
60” (152.4 cm)
32” (81.28 cm)
32” (81.28 cm)
18” (45.72 cm)
12” (30.48 cm)
Figure 27:Roof Jack Installation
TABLE 5: ROOF JACK KITS
KIT NUMBER MAXIMUM LENGTH
BETWEEN ROOF
AND CEILING
100285331 12”
100285333 32”
100285412 60”
100285414 95”
A cer ed roof jack (vent kit) from
the manufacturer must be installed
with the water heaters covered by
this manual. Roof jack kits are ordered
separately. See Figure 27 to determine
which roof jack is needed for the
installa on.
NOTICE: Install the roof jack according
to its manufacturers instruc ons.
An op onal Roof jack Extension Pipe
(100108866) may be required where
local codes require the roof jack cap
(outlet) to terminate above the peak of
the roof.
NOTICE: DO NOT common vent this
water heater with any other appliance.
1. Cut a 5-1/2” (14 cm) diameter hole
through the roof and ceiling directly
in line with the ue connec on on
top of the water heater. For a sloped
roof, the roof hole may have to be
enlarged to allow the roof jack to be
installed ver cally.
2. Telescope down the ue pipe in the
roof jack assembly to a length that
will project at least 6” (15.24 cm)
below the nished ceiling before
installing the roof jack assembly.
NOTICE: Flue pipe joints have silicone
seals that must remain in place. A soapy
water solu on sprayed around the seal
area will enable the ue pipe and outer
pipe below to telescope more freely.
3. Telescope down the outer pipe of
the roof jack assembly to a length
that will project at least 2” (5 cm)
below the nished ceiling before
installing the roof jack assembly.
See Figure 28.
INSTALLATION
20 • Residen al Gas Water Heater Use and Care Guide for Manufactured Homes
INSTALLATION
INSTALLATION
TELESCOPE
OUTER PIPE
AND FLUE
PIPE DOWN
OUTER PIPE
FLUE PIPE
Figure 28: Roof Jack Placement
4. Ease the roof jack assembly
through the roof and ceiling
openings. The roof jack ashing
lts up to 30.26° degrees for use
on a sloping roof.
5. Use sealant or caulk on the roof to
seal under ashing of the roof jack
assembly. Use roof nails or screws
on wood construc on or sheet
metal screws on metal roofs (nails
and screws not provided). See
Figure 29.
USE SEALANT OR
CAULK TO SEAL
UNDER ROOF
JACK FLASHING
Figure 29:Sealing Roof Jack
6. Extend the ue pipe downward
un l it is close to the ue reducer.
See Figure 30.
FLUE PIPE
FLUE
REDUCER
Figure 30:Attach Flue Pipe to Vent Reducer
7. Fit the bo om opening of the pipe
over the top opening of the ue
reducer. See Figure 31. Ensure
that there is no gap and that the
seal is complete.
8. Secure the ue pipe to the reducer
with three (3) evenly-spaced sheet
metal screws (Figure 31). Do not
leave any open holes in the ue
reducer or ue pipe.
SECURE VENT WITH
THREE (3)
EVENLY -SPACED
SHEET METAL SCREWS
Figure 31:Securing the Flue to Vent Reducer
NOTICE: All joints for vent piping
between roof jack and water heater
are sealed from the manufacturer.
No addi onal sealing of vent pipe is
necessary.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36

State GS6-30-MDV250, GS6-40-MDV- 250, GS6-50-MDV-250 User manual

Category
Water heaters & boilers
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI