SERVICE NANUAL TNC 351/355
Page 10
Kundendienst
Flashing display
/GROSS POSITIONING ERROR A 1
/GROSS POSITIONING ERROR B 1
GROSS POSITIONING ERROR C
GROSS POSITIONING ERROR D
GROSS POSITIONING ERROR E
Fault cause
Position (trailing error) supervision
- Speed precontrol operation: Exceeding
position supervision determined by
machine parameter 57.
- Trailing error operation:
Exceeding trailing error supervision
determined by machine parameter 174.
Supervision of analog voltage limit
- The nominal value of the voltage calcu-
lated by the control reached the f 10
volt limit (only with speed precontrol).
Move8ent supervision
- The voltage difference calculated by the
control reached the limit programmed in
machine parameter 234.
Standstill supervision
- The position deviation from the nominal
position of an axis at standstill is
greater than programmed in machine para-
meter 169.
- When positioning beyond the target point
programmed the value of the nominal
position is greater than programmed
in machine parameter 169.
Supervision of offset voltage
- The offset voltage limit of 100 mV was
reached with an automatic offset adjust-
ment by machine parameter 252.
Possible location of error with the error message “GROSS POSITIONING ERROR
A/B/C/D/E":
With “Gross Positioning Error” the error can be due to any
component of the closed loop.
e.g. : - control error (e.g. CLP PROCESSOR Board)
- excessive offset voltage at servo amplifier
- wrong speed adjustment at servo amplifier
- supervision of servo amplifier is effective (e.g. current supervision)
- electrical defect of servo amplifier
- motor defective, tacho, measuring system or cabling
- mechanical defect (bearing, spindle or guidance error)
- excessive mechanical forces on drive