Tork 7300 Installation And Operating Instructions Manual

Type
Installation And Operating Instructions Manual

This manual is also suitable for

TORK MODEL 7100
24 HR. TIME SWITCH
WITH SKIP-A-DAY
SWITCH: SPST
CONTACT RATINGS:
40 AMP 120-277VAC
20 AMP INDUCTIVE
120-277VAC SINGLE PHASE
40 AMP TUNGSTEN 120VAC
1000VA (120-277) PILOT DUTY
2HP 120VAC; 5HP 240VAC
TIMING MOTOR: 120VAC 60Hz
POWER CONSUMPTION: 3 WATTS MAX.
INSTALLATION AND OPERATING INSTRUCTIONS
TO SET ON AND OFF TIMES:
Light trippers turn ON. Dark trippers turn OFF. Place tripper on
dial edge as shown in figure and set point of each tripper to
desired operating time. CAUTION: Note if selected time is AM
or PM. Hold tripper against dial edge and firmly tighten
knurled screw.
Disconnect power at main panel prior to installing or servicing this
time switch or the equipment connected to it.
Connect in accordance with national and local electrical codes.
Supply Connections: Use gauge specified (AWG # 8-14) suitable for
75 degrees C (167 degrees F)
O
F
F
O
N
TORK
Dial Calibrations
Knurled Screw
OFF TIME
(Dark Tripper)
ON TIME
(Light Tripper)
MANUAL
ON
LEVER
MANUAL
OFF
LEVER
TIME
TORK
®
1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542
FAX: 914-664-5052
LI-565(A)
L
1X
2
LOAD
M
H
N
TO SET DIAL TO TIME: Turn dial counter-clockwise until correct time is indicated by arrow on nameplate.
FOR MANUAL OPERATIONS: Press down lever on right of nameplate to turn ON. Press down lever
on left of nameplate to turn OFF.
TO OMIT ON OPERATION: 7 spoke wheel at lower left of 24 hour dial moves ahead once each day,
about 5 hours before the first ON tripper is set to operate. Insert brass knurled screws in appropriate
spokes on days when ON operations are to be omitted.
TO SET OMITTING WHEEL TO CORRECT DAY: Hold down OFF lever on left of name-
plate. The red stud on this lever is the day-indicator. If the ON tripper has already passed
the omitting wheel, turn omitting wheel clockwise until the present day of the week is indi-
cated. If ON tripper has not passed omitting wheel, set omitting wheel so preceding day
is indicated (24 hour dial turns counter-clockwise).
TO REMOVE MECHANISM FROM CASE: Press lever near case latch to release mainplate and
swing the movement out. To replace, insert mainplate projections in slots opposite latch and swing
movement in until it latches.
RED
STUD
GREEN
ACTUATOR
TORK MODEL 7102
24 HR. TIME SWITCH
WITH SKIP-A-DAY
SWITCH: SPST
CONTACT RATINGS:
40 AMP 120-277VAC 40 AMP TUNGSTEN 120VAC
20 AMP INDUCTIVE 1000VA (120-277) PILOT DUTY
120-277VAC SINGLE PHASE 2HP 120VAC; 5HP 240VAC
TIMING MOTOR:
208-277VAC 60Hz
POWER CONSUMPTION:
3 WATTS MAX.
INSTALLATION AND OPERATING INSTRUCTIONS
TO SET ON AND OFF TIMES:
Light trippers turn ON. Dark trippers turn OFF. Place tripper on
dial edge as shown in figure and set point of each tripper to
desired operating time. CAUTION: Note if selected time is AM
or PM. Hold tripper against dial edge and firmly tighten
knurled screw.
TO SET DIAL TO TIME: Turn dial counter-clockwise until correct time is indicated by arrow on name-
plate.
FOR MANUAL OPERATIONS: Press down lever on right of nameplate to turn ON. Press down lever
on left of nameplate to turn OFF.
TO OMIT ON OPERATION: 7 spoke wheel at lower left of 24 hour dial moves ahead once each day,
about 5 hours before the first ON tripper is set to operate. Insert brass knurled screws in appropriate
spokes on days when ON operations are to be omitted.
TO SET OMITTING WHEEL TO CORRECT DAY: Hold down OFF lever on left of
nameplate. The red stud on this lever is the day-indicator. If the ON tripper has
already passed the omitting wheel, turn omitting wheel clockwise until the present
day of the week is indicated. If ON tripper has not passed omitting wheel, set omit-
ting wheel so preceding day is indicated (24 hour dial turns counter-clockwise).
TO REMOVE MECHANISM FROM CASE: Press lever near case latch to release mainplate and
swing the movement out. To replace, insert main-plate projections in slots opposite latch and swing
movement in until it latches.
Disconnect power at main panel prior to installing or servicing this
time switch or the equipment connected to it.
Connect in accordance with national and local electrical codes.
Supply Connections: Use gauge specified (AWG # 8-14) suitable for
75 degrees C (167 degrees F)
O
F
F
O
N
TORK
Dial Calibrations
Knurled Screw
OFF TIME
(Dark Tripper)
ON TIME
(Light Tripper)
MANUAL
ON
LEVER
MANUAL
OFF
LEVER
TIME
TORK
®
1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542
FAX: 914-664-5052
LI-589(A)
RED
STUD
GREEN
ACTUATOR
L
1X
2
LOAD
M
H
N
TORK MODEL 7120
24 HR. TIME SWITCH
WITH SKIP-A-DAY
SWITCH: SPDT
CONTACT RATINGS:
40 AMP 120-277VAC
40 AMP TUNGSTEN 120VAC
20 AMP INDUCTIVE
120-277VAC SINGLE PHASE
1000VA (120-277) PILOT DUTY
2HP 120VAC; 5HP 240VAC
TIMING MOTOR: 120VAC 60Hz
POWER CONSUMPTION:
3 WATTS MAX.
INSTALLATION AND OPERATING INSTRUCTIONS
TO SET ON AND OFF TIMES:
Light trippers turn ON. Dark trippers turn OFF. Place tripper on
dial edge as shown in figure and set point of each tripper to
desired operating time. CAUTION: Note if selected time is AM
or PM. Hold tripper against dial edge and firmly tighten
knurled screw.
TO SET DIAL TO TIME: Turn dial counter-clockwise until correct time is indicated by arrow on name-
plate.
FOR MANUAL OPERATIONS: Press down lever on right of nameplate to turn ON. Press down lever
on left of nameplate to turn OFF.
TO OMIT ON OPERATION: 7 spoke wheel at lower left of 24 hour dial moves ahead once each day,
about 5 hours before the first ON tripper is set to operate. Insert brass knurled screws in appropriate
spokes on days when ON operations are to be omitted.
TO SET OMITTING WHEEL TO CORRECT DAY: Hold down OFF lever on left of
nameplate. The red stud on this lever is the day-indicator. If the ON tripper has
already passed the omitting wheel, turn omitting wheel clockwise until the present
day of the week is indicated. If ON tripper has not passed omitting wheel, set omit-
ting wheel so preceding day is indicated (24 hour dial turns counter-clockwise).
TO REMOVE MECHANISM FROM CASE: Press lever near case latch to release mainplate and
swing the movement out. To replace, insert main-plate projections in slots opposite latch and swing
movement in until it latches.
Disconnect power at main panel prior to installing or servicing this
time switch or the equipment connected to it.
Connect in accordance with national and local electrical codes.
Supply Connections: Use gauge specified (AWG # 8-14) suitable for
75 degrees C (167 degrees F)
O
F
F
O
N
TORK
Dial Calibrations
Knurled Screw
OFF TIME
(Dark Tripper)
ON TIME
(Light Tripper)
MANUAL
ON
LEVER
MANUAL
OFF
LEVER
TIME
TORK
®
1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542
FAX: 914-664-5052
LI-594(A)
RED
STUD
GREEN
ACTUATOR
L 1 X 2
M
LOAD
A
N
H
LOAD
B
H
N
TORK MODEL 7122
24 HR. TIME SWITCH
WITH SKIP-A-DAY
SWITCH: SPDT
CONTACT RATINGS:
40 AMP 120-277VAC
20 AMP INDUCTIVE
120-277VAC SINGLE PHASE
40 AMP TUNGSTEN 120VAC
1000VA (120-277) PILOT DUTY
2HP 120VAC; 5HP 240VAC
TIMING MOTOR:
208-277VAC 60Hz
POWER CONSUMPTION:
3 WATTS MAX.
INSTALLATION AND OPERATING INSTRUCTIONS
TO SET ON AND OFF TIMES:
Light trippers turn ON. Dark trippers turn OFF. Place tripper on
dial edge as shown in figure and set point of each tripper to
desired operating time. CAUTION: Note if selected time is AM
or PM. Hold tripper against dial edge and firmly tighten
knurled screw.
TO SET DIAL TO TIME: Turn dial counter-clockwise until correct time is indicated by arrow on name-
plate.
FOR MANUAL OPERATIONS: Press down lever on right of nameplate to turn ON. Press down lever
on left of nameplate to turn OFF.
TO OMIT ON OPERATION: 7 spoke wheel at lower left of 24 hour dial moves ahead once each day,
about 5 hours before the first ON tripper is set to operate. Insert brass knurled screws in appropriate
spokes on days when ON operations are to be omitted.
TO SET OMITTING WHEEL TO CORRECT DAY: Hold down OFF lever on left of
nameplate. The red stud on this lever is the day-indicator. If the ON tripper has
already passed the omitting wheel, turn omitting wheel clockwise until the present
day of the week is indicated. If ON tripper has not passed omitting wheel, set omit-
ting wheel so preceding day is indicated (24 hour dial turns counter-clockwise).
TO REMOVE MECHANISM FROM CASE: Press lever near case latch to release mainplate and
swing the movement out. To replace, insert main-plate projections in slots opposite latch and swing
movement in until it latches.
Disconnect power at main panel prior to installing or servicing this
time switch or the equipment connected to it.
Connect in accordance with national and local electrical codes.
Supply Connections: Use gauge specified (AWG # 8-14) suitable for
75 degrees C (167 degrees F)
O
F
F
O
N
TORK
Dial Calibrations
Knurled Screw
OFF TIME
(Dark Tripper)
ON TIME
(Light Tripper)
MANUAL
ON
LEVER
MANUAL
OFF
LEVER
TIME
TORK
®
1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542
FAX: 914-664-5052
LI-595(A)
RED
STUD
GREEN
ACTUATOR
H
H
L1 X2
M
H
H
LOAD
A
LOAD
B
Typical for 240VAC supply.
TORK MODEL 7202
24 HR. TIME SWITCH
WITH SKIP-A-DAY
SWITCH: DPST
CONTACT RATINGS:
40 AMP 120-277VAC
40 AMP TUNGSTEN 120VAC
20 AMP INDUCTIVE
120-277VAC SINGLE PHASE
1000VA (120-277) PILOT DUTY
2HP 120VAC; 5HP 240VAC
TIMING MOTOR:
208-277VAC 60Hz
POWER CONSUMPTION:
3 WATTS MAX.
INSTALLATION AND OPERATING INSTRUCTIONS
TO SET ON AND OFF TIMES:
Light trippers turn ON. Dark trippers turn OFF. Place tripper on
dial edge as shown in figure and set point of each tripper to
desired operating time. CAUTION: Note if selected time is AM
or PM. Hold tripper against dial edge and firmly tighten
knurled screw.
TO SET DIAL TO TIME: Turn dial counter-clockwise until correct time is indicated by arrow on name-
plate.
FOR MANUAL OPERATIONS: Press down lever on right of nameplate to turn ON. Press down lever
on left of nameplate to turn OFF.
TO OMIT ON OPERATION: 7 spoke wheel at lower left of 24 hour dial moves ahead once each day,
about 5 hours before the first ON tripper is set to operate. Insert brass knurled screws in appropriate
spokes on days when ON operations are to be omitted.
TO SET OMITTING WHEEL TO CORRECT DAY: Hold down OFF lever on left of
nameplate. The red stud on this lever is the day-indicator. If the ON tripper has
already passed the omitting wheel, turn omitting wheel clockwise until the present
day of the week is indicated. If ON tripper has not passed omitting wheel, set omit-
ting wheel so preceding day is indicated (24 hour dial turns counter-clockwise).
TO REMOVE MECHANISM FROM CASE: Press lever near case latch to release mainplate and
swing the movement out. To replace, insert main-plate projections in slots opposite latch and swing
movement in until it latches.
Disconnect power at main panel prior to installing or servicing this
time switch or the equipment connected to it.
Connect in accordance with national and local electrical codes.
Supply Connections: Use gauge specified (AWG # 8-14) suitable for
75 degrees C (167 degrees F)
O
F
F
O
N
TORK
Dial Calibrations
Knurled Screw
OFF TIME
(Dark Tripper)
ON TIME
(Light Tripper)
MANUAL
ON
LEVER
MANUAL
OFF
LEVER
TIME
TORK
®
1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542
FAX: 914-664-5052
LI-590(A)
RED
STUD
GREEN
ACTUATOR
H
M
L
1
X
2
H
LOAD LOAD
LOAD
208-240V
SUPPLY
277V
SUPPLY
H
M
L
1
X
2
N
H
MUST BE
SAME PHASE
TORK MODEL 7202L
24 HR. TIME SWITCH
WITH SKIP-A-DAY
SWITCH: DPST
CONTACT RATINGS:
40 AMP 120-277VAC
40 AMP TUNGSTEN 120VAC
20 AMP INDUCTIVE
120-277VAC SINGLE PHASE
1000VA (120-277) PILOT DUTY
2HP 120VAC; 5HP 240VAC
TIMING MOTOR:
208-277VAC 60Hz
POWER CONSUMPTION:
3 WATTS MAX.
SYNCHRONOUS POWER
WITH RESERVE:
Should your power supply be
interrupted, this switch will continue
to operate on time for several hours.
INSTALLATION AND OPERATING INSTRUCTIONS
TO SET ON AND OFF TIMES:
Light trippers turn ON. Dark trippers turn OFF. Place tripper on
dial edge as shown in figure and set point of each tripper to
desired operating time. CAUTION: Note if selected time is AM
or PM. Hold tripper against dial edge and firmly tighten
knurled screw.
TO SET DIAL TO TIME: Turn dial counter-clockwise until correct time is indicated by arrow on name-
plate.
FOR MANUAL OPERATIONS: Press down lever on right of nameplate to turn ON. Press down lever
on left of nameplate to turn OFF.
TO OMIT ON OPERATION: 7 spoke wheel at lower left of 24 hour dial moves ahead once each day,
about 5 hours before the first ON tripper is set to operate. Insert brass knurled screws in appropriate
spokes on days when ON operations are to be omitted.
TO SET OMITTING WHEEL TO CORRECT DAY: Hold down OFF lever on left of
nameplate. The red stud on this lever is the day-indicator. If the ON tripper has
already passed the omitting wheel, turn omitting wheel clockwise until the present
day of the week is indicated. If ON tripper has not passed omitting wheel, set omit-
ting wheel so preceding day is indicated (24 hour dial turns counter-clockwise).
TO REMOVE MECHANISM FROM CASE: Press lever near case latch to release
mainplate and swing the movement out. To replace, insert main-plate projections in slots opposite
latch and swing movement in until it latches.
Disconnect power at main panel prior to installing or servicing this time switch or the
equipment connected to it.
Connect in accordance with national and local electrical codes.
Supply Connections: Use gauge specified (AWG # 8-14) suitable for 75 degrees C (167
degrees F)
O
F
F
O
N
TORK
Dial Calibrations
Knurled Screw
OFF TIME
(Dark Tripper)
ON TIME
(Light Tripper)
MANUAL
ON
LEVER
MANUAL
OFF
LEVER
TIME
TORK
®
1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542
FAX: 914-664-5052
LI-591(A)
RED
STUD
GREEN
ACTUATOR
H
M
L
1
X
2
H
LOAD LOAD
LOAD
208-240V
SUPPLY
277V
SUPPLY
H
M
L
1
X
2
N
H
MUST BE
SAME PHASE
TORK MODEL 7220
24 HR. TIME SWITCH
WITH SKIP-A-DAY
SWITCH: DPDT
CONTACT RATINGS:
40 AMP 120-277VAC
20 AMP INDUCTIVE
120-277VAC SINGLE PHASE
40 AMP TUNGSTEN 120VAC
1000VA (120-277) PILOT DUTY
2HP 120VAC; 5HP 240VAC
TIMING MOTOR:
120VAC 60Hz
POWER CONSUMPTION:
3 WATTS MAX.
INSTALLATION AND OPERATING INSTRUCTIONS
TO SET ON AND OFF TIMES:
Light trippers turn ON. Dark trippers turn OFF. Place tripper on
dial edge as shown in figure and set point of each tripper to
desired operating time. CAUTION: Note if selected time is AM
or PM. Hold tripper against dial edge and firmly tighten
knurled screw.
TO SET DIAL TO TIME: Turn dial counter-clockwise until correct time is indicated by arrow on name-
plate.
FOR MANUAL OPERATIONS: Press down lever on right of nameplate to turn ON. Press down lever
on left of nameplate to turn OFF.
TO OMIT ON OPERATION: 7 spoke wheel at lower left of 24 hour dial moves ahead once each day,
about 5 hours before the first ON tripper is set to operate. Insert brass knurled screws in appropriate
spokes on days when ON operations are to be omitted.
TO SET OMITTING WHEEL TO CORRECT DAY: Hold down OFF lever on left of
nameplate. The red stud on this lever is the day-indicator. If the ON tripper has
already passed the omitting wheel, turn omitting wheel clockwise until the present
day of the week is indicated. If ON tripper has not passed omitting wheel, set omit-
ting wheel so preceding day is indicated (24 hour dial turns counter-clockwise).
TO REMOVE MECHANISM FROM CASE: Press lever near case latch to release
mainplate and swing the movement out. To replace, insert main-plate projections in slots opposite
latch and swing movement in until it latches.
Disconnect power at main panel prior to installing or servicing this
time switch or the equipment connected to it.
Connect in accordance with national and local electrical codes.
Supply Connections: Use gauge specified (AWG # 8-14) suitable for
75 degrees C (167 degrees F)
O
F
F
O
N
TORK
Dial Calibrations
Knurled Screw
OFF TIME
(Dark Tripper)
ON TIME
(Light Tripper)
MANUAL
ON
LEVER
MANUAL
OFF
LEVER
TIME
TORK
®
1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542
FAX: 914-664-5052
LI-596(A)
RED
STUD
GREEN
ACTUATOR
M
1X2
L
3
45
LOADS
N
LOADS
TYPICAL FOR 120VAC SUPPLY
H
H
N
H
N
FRONT
REAR
L
TORK MODEL 7222
24 HR. TIME SWITCH
WITH SKIP-A-DAY
SWITCH: DPDT
CONTACT RATINGS:
40 AMP 120-277VAC
20 AMP INDUCTIVE
120-277VAC
SINGLE PHASE
40 AMP TUNGSTEN 120VAC
1000VA (120-277) PILOT DUTY
2HP 120VAC; 5HP 240VAC
TIMING MOTOR:
208-277VAC 60Hz
POWER CONSUMPTION:
3 WATTS MAX
.
INSTALLATION AND OPERATING INSTRUCTIONS
TO SET ON AND OFF TIMES:
Light trippers turn ON. Dark trippers turn OFF. Place tripper on
dial edge as shown in figure and set point of each tripper to
desired operating time. CAUTION: Note if selected time is AM
or PM. Hold tripper against dial edge and firmly tighten
knurled screw.
TO SET DIAL TO TIME: Turn dial counter-clockwise until correct time is indicated by arrow on name-
plate.
FOR MANUAL OPERATIONS: Press down lever on right of nameplate to turn ON. Press down lever
on left of nameplate to turn OFF.
TO OMIT ON OPERATION: 7 spoke wheel at lower left of 24 hour dial moves ahead once each day,
about 5 hours before the first ON tripper is set to operate. Insert brass knurled screws in appropriate
spokes on days when ON operations are to be omitted.
TO SET OMITTING WHEEL TO CORRECT DAY: Hold down OFF lever on left of
nameplate. The red stud on this lever is the day-indicator. If the ON tripper has
already passed the omitting wheel, turn omitting wheel clockwise until the present
day of the week is indicated. If ON tripper has not passed omitting wheel, set omit-
ting wheel so preceding day is indicated (24 hour dial turns counter-clockwise).
TO REMOVE MECHANISM FROM CASE: Press lever near case latch to release
mainplate and swing the movement out. To replace, insert main-plate projections in slots opposite
latch and swing movement in until it latches.
Disconnect power at main panel prior to installing or servicing this
time switch or the equipment connected to it.
Connect in accordance with national and local electrical codes.
Supply Connections: Use gauge specified (AWG # 8-14) suitable for
75 degrees C (167 degrees F)
O
F
F
O
N
TORK
Dial Calibrations
Knurled Screw
OFF TIME
(Dark Tripper)
ON TIME
(Light Tripper)
MANUAL
ON
LEVER
MANUAL
OFF
LEVER
TIME
TORK
®
1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542
FAX: 914-664-5052
LI-597(A)
RED
STUD
GREEN
ACTUATOR
M
1
X
2
2
1
L
3
4
45
Typical for 277VAC supply
H
N
FRONT
REAR
3
L
LOADS
LOADS
M
1
X
2
L
3
B
45
Typical for 208-240VAC supply
H
H
H
H
FRONT
REAR
A
L
LOADS
TORK MODEL 7300
24 HR. TIME SWITCH
WITH SKIP-A-DAY
SWITCH: 3PST
CONTACT RATINGS:
40 AMP 120-277VAC
20 AMP INDUCTIVE
120-277VAC SINGLE PHASE
40 AMP TUNGSTEN 120VAC
1000VA (120-277)
PILOT DUTY
2HP 120VAC; 5HP 240VAC
TIMING MOTOR:
120VAC 60Hz
POWER CONSUMPTION:
3 WATTS MAX.
INSTALLATION AND OPERATING INSTRUCTIONS
TO SET ON AND OFF TIMES:
Light trippers turn ON. Dark trippers turn OFF. Place tripper on
dial edge as shown in figure and set point of each tripper to
desired operating time. CAUTION: Note if selected time is AM
or PM. Hold tripper against dial edge and firmly tighten
knurled screw.
TO SET DIAL TO TIME: Turn dial counter-clockwise until correct time is indicated by arrow on name-
plate.
FOR MANUAL OPERATIONS: Press down lever on right of nameplate to turn ON. Press down lever
on left of nameplate to turn OFF.
TO OMIT ON OPERATION: 7 spoke wheel at lower left of 24 hour dial moves ahead once each day,
about 5 hours before the first ON tripper is set to operate. Insert brass knurled screws in appropriate
spokes on days when ON operations are to be omitted.
TO SET OMITTING WHEEL TO CORRECT DAY: Hold down OFF lever on left of
nameplate. The red stud on this lever is the day-indicator. If the ON tripper has
already passed the omitting wheel, turn omitting wheel clockwise until the present
day of the week is indicated. If ON tripper has not passed omitting wheel, set omit-
ting wheel so preceding day is indicated (24 hour dial turns counter-clockwise).
TO REMOVE MECHANISM FROM CASE: Press lever near case latch to release
mainplate and swing the movement out. To replace, insert main-plate projections in slots opposite
latch and swing movement in until it latches.
Disconnect power at main panel prior to installing or servicing this
time switch or the equipment connected to it.
Connect in accordance with national and local electrical codes.
Supply Connections: Use gauge specified (AWG # 8-14) suitable for
75 degrees C (167 degrees F)
O
F
F
O
N
TORK
Dial Calibrations
Knurled Screw
OFF TIME
(Dark Tripper)
ON TIME
(Light Tripper)
MANUAL
ON
LEVER
MANUAL
OFF
LEVER
TIME
TORK
®
1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542
FAX: 914-664-5052
LI-592(A)
RED
STUD
GREEN
ACTUATOR
L
LOADS
1 X
M
2
3
5
4
6
L
L
L
N
For use with 3 phase 4-wire120/208V. systems
FRONT
MIDDLE
REAR
TORK MODEL 7300
24 HR. TIME SWITCH
WITH SKIP-A-DAY
SWITCH: 3PST
CONTACT RATINGS:
40 AMP 120-277VAC
20 AMP INDUCTIVE
120-277VAC SINGLE PHASE
40 AMP TUNGSTEN 120VAC
1000VA (120-277)
PILOT DUTY
2HP 120VAC; 5HP 240VAC
TIMING MOTOR:
120VAC 60Hz
POWER CONSUMPTION:
3 WATTS MAX.
INSTALLATION AND OPERATING INSTRUCTIONS
TO SET ON AND OFF TIMES:
Light trippers turn ON. Dark trippers turn OFF. Place tripper on
dial edge as shown in figure and set point of each tripper to
desired operating time. CAUTION: Note if selected time is AM
or PM. Hold tripper against dial edge and firmly tighten
knurled screw.
TO SET DIAL TO TIME: Turn dial counter-clockwise until correct time is indicated by arrow on name-
plate.
FOR MANUAL OPERATIONS: Press down lever on right of nameplate to turn ON. Press down lever
on left of nameplate to turn OFF.
TO OMIT ON OPERATION: 7 spoke wheel at lower left of 24 hour dial moves ahead once each day,
about 5 hours before the first ON tripper is set to operate. Insert brass knurled screws in appropriate
spokes on days when ON operations are to be omitted.
TO SET OMITTING WHEEL TO CORRECT DAY: Hold down OFF lever on left of
nameplate. The red stud on this lever is the day-indicator. If the ON tripper has
already passed the omitting wheel, turn omitting wheel clockwise until the present
day of the week is indicated. If ON tripper has not passed omitting wheel, set omit-
ting wheel so preceding day is indicated (24 hour dial turns counter-clockwise).
TO REMOVE MECHANISM FROM CASE: Press lever near case latch to release
mainplate and swing the movement out. To replace, insert main-plate projections in slots opposite
latch and swing movement in until it latches.
Disconnect power at main panel prior to installing or servicing this
time switch or the equipment connected to it.
Connect in accordance with national and local electrical codes.
Supply Connections: Use gauge specified (AWG # 8-14) suitable for
75 degrees C (167 degrees F)
O
F
F
O
N
TORK
Dial Calibrations
Knurled Screw
OFF TIME
(Dark Tripper)
ON TIME
(Light Tripper)
MANUAL
ON
LEVER
MANUAL
OFF
LEVER
TIME
TORK
®
1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542
FAX: 914-664-5052
LI-592(A)
RED
STUD
GREEN
ACTUATOR
L
LOADS
1 X
M
2
3
5
4
6
L
L
L
N
For use with 3 phase 4-wire120/208V. systems
FRONT
MIDDLE
REAR
TORK MODEL 7302
24 HR. TIME SWITCH
WITH SKIP-A-DAY
SWITCH: 3PST
CONTACT RATINGS:
40 AMP 120-277VAC
20 AMP INDUCTIVE
120-277VAC
SINGLE PHASE
40 AMP TUNGSTEN 120VAC
1000VA (120-277) PILOT DUTY
2HP 120VAC; 5HP 240VAC
TIMING MOTOR:
208-277VAC 60Hz
POWER CONSUMPTION:
3 WATTS MAX.
INSTALLATION AND OPERATING INSTRUCTIONS
TO SET ON AND OFF TIMES:
Light trippers turn ON. Dark trippers turn OFF. Place tripper on
dial edge as shown in figure and set point of each tripper to
desired operating time. CAUTION: Note if selected time is AM
or PM. Hold tripper against dial edge and firmly tighten
knurled screw.
TO SET DIAL TO TIME: Turn dial counter-clockwise until correct time is indicated by arrow on name-
plate.
FOR MANUAL OPERATIONS: Press down lever on right of nameplate to turn ON. Press down lever
on left of nameplate to turn OFF.
TO OMIT ON OPERATION: 7 spoke wheel at lower left of 24 hour dial moves ahead once each day,
about 5 hours before the first ON tripper is set to operate. Insert brass knurled screws in appropriate
spokes on days when ON operations are to be omitted.
TO SET OMITTING WHEEL TO CORRECT DAY: Hold down OFF lever on left of
nameplate. The red stud on this lever is the day-indicator. If the ON tripper has
already passed the omitting wheel, turn omitting wheel clockwise until the present
day of the week is indicated. If ON tripper has not passed omitting wheel, set omit-
ting wheel so preceding day is indicated (24 hour dial turns counter-clockwise).
TO REMOVE MECHANISM FROM CASE: Press lever near case latch to release
mainplate and swing the movement out. To replace, insert main-plate projections in slots opposite
latch and swing movement in until it latches.
Disconnect power at main panel prior to installing or servicing this
time switch or the equipment connected to it.
Connect in accordance with national and local electrical codes.
Supply Connections: Use gauge specified (AWG # 8-14) suitable for
75 degrees C (167 degrees F)
O
F
F
O
N
TORK
Dial Calibrations
Knurled Screw
OFF TIME
(Dark Tripper)
ON TIME
(Light Tripper)
MANUAL
ON
LEVER
MANUAL
OFF
LEVER
TIME
TORK
®
1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542
FAX: 914-664-5052
LI-593(A)
RED
STUD
GREEN
ACTUATOR
L
1 X
M
2
3
5
4
L
L
L
N
REAR
MIDDLE
FRONT
6
LOADS
L
LOADS
1 X
M
2
3
5
4
6
H
N
REAR
MIDDLE
FRONT
Typical for 277VAC
For use with 3 phase 4-wire,
120/208VAC.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11

Tork 7300 Installation And Operating Instructions Manual

Type
Installation And Operating Instructions Manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI