eder MCM-M5-6 User manual

Type
User manual

This manual is also suitable for

1
ANTON EDER GMBH
Weyerstraße 350
A-5733 Bramberg
www.eder-heizung.at
Ver.10/2019-en
Supplement to instruction manual , _1MCK MCM
Instruction manual
MULTICONTROL
MMC -_2 ... _9
2
Table of contents
1. General
. Mounting2
.1 Installing the device2
.2 degassing module multicontrol makeup module multicontrol2,MAE MCF
. Hydraulic diagrams3
4. Wiring diagrams
. Commissioning5
. Technical data6
. Spare parts list7
Appendix8.
ECON
NOTE!
Figures in this document can vary due to model and configuration of the delivered
multicontrol device.
i
INFORMATION!
This document refers to multicontrol series devices with software version V1.26.
Design and operation can vary slightly due to the existing software version.
i
Table of contents
Disclaimer
We improve our products permanently and so we reserve the right to make modifications
anytime and without previous announcements. We do not assume any guarantee for the
correctness and completeness of this document.
Any claims, particularly claims for damage and loss of profit or financial losses must be excluded!
3
1. General
1.1. Tender text
multicontrol modular for lossless storage of the expansion volume and for pressureMCM
maintenance in closed heating, climate and cooling systems. Designed and manufactured acc.
to regulations of 12828 and 93-1.EN SWKI
The multicontrol device is a nicely shaped, self-contained unit with a pleasing design. It isMCM
designed for a modular combination with external expansion vessels (max. 0.5 bar). The
connections for suction pipe and overflow pipe are situated at the back of the device.
The control unit is built very compact with one resp. two low-noise pressure maintenance
pump(s) (model Solo 1x100%, model Duo 2x50%, model Maxi 2x100%) which is/are executed as
multistage centrifugal pump(s) with high quality floating-ring type shaft seal. Also the
multicontrol hydraulics includes one resp. two continuously regulating, mechanically set
overflow valve(s) (models Solo, Duo and Maxi 1x100% of the expansion flow, models Duo-twin
and Maxi-twin 2x100%). High-precision measuring of the plant pressure. Hydraulic connections
and necessary shutoff devices for on-site piping are factory provided on the left side of the
control unit (possibility for rebuilding to the right side of the control unit). Temperature
monitoring of the media streaming into the vessel.
Prepared connection point for mounting a makeup module for litre accurate measuring.
Combinable with water softening for standardized makeup water.
Prepared connection point for mounting a degassing module for automatic and economic low
pressure degassing, based on the principle of pressure drop. The connection and the necessary
shutoff device for the degassing pipe is situated at the back of the control unit.
All operations are controlled by the microprocessor electronics. The operator panel is situated
ergonomically and containes a illuminated 4-line text display. The handling is thought-out and a
lot of languages are supported. The measure- and control unit is executed in a closed electrical
cabinet. Four potential-free signalling contacts (fault, warning, makeup in operation, device
operation enabled).
For more signals two additional expansion modules can be installed easily in prepared mounting
positions. Remote monitoring can be done also via multicontrol module or multicontrol busSMS
module. External temperature monitoring via an optional temperature sensor at the connection
point is prepared too.
max. operation temperature of the plant: 110 °C (with cooling vessel)EV
max. temperature at the connection point: 70 °C
1. General
4
2. Mounting
2. Mounting
2.1. Installing the device
The multicontrol device must be installed on a horizontal and solid floor and it must be set up
vertically by using the adjustable stands (1). The four holes on side of the socket can be used to
transport the device (for example by inserting 2 pipes, max. 1").
figure adjustable stands and transportation example1:
The implementation into the system return must be executed acc. to the hydraulic diagrams in
chapter 3 - ”Hydraulic diagrams”.
multicontrol modular series devices can be used in plants with max. temperature of 70 °CMCM
at the connection point. If the max. temperature at the connection point exceeds 70 °C, EV
cooling vessels must be installed!
The implementation into the system return must be done at a position where no external
pressure can occur. External pressures could affect the trouble-free operation of the pressure
maintenance device.
NOTE!
For detailled information about hydraulic connection of multicontrol modular MCM
and (Z)-M expansion vessels see chapter 8.EG
i
INFORMATION!
Dimensioning of the expansion pipe according to H 5151-1, see appendix A inÖNORM
instruction manual multicontrol , -_1. With multicontrol modular all theMCK MCM MCM
piping must be made on-site according to the appropriate hydraulic diagram in chapter 3.
i
5
2. Mounting
2.2. degassing module multicontrol , makeup module multicontrolMAE MCF
multicontrol modular series devices factory provided are delivered without degassingMCM
module resp. makeup module . The mounting of these modules is done acc. to theMAE MCF
assembly instruction which is delivered with the module.
connection point MCF
connection point MAE
figure 2: degassing module MAE
notes
6
3. Hydraulic diagrams
multicontrol with degassing:modular
Options: second main vessel -M, additional vessels , expansion modules,EG EGZ-M
degassing module , makeup module , water treatment sensor T2MAE MCF ,
1 ... makeup water 7 ... gas-side vessel connection 20DN
4 ... discharge hopper for vessel safety valve expansion pipe from/to system return8 ...
5 ... suction pipe from expansion vessel degassing pipe from system return9 ...
6 ... overflow pipe from expansion vessel
3. Hydraulic diagrams
7
multicontrol without degassing:modular
Options: second main vessel -M, additional vessels , expansion modules,EG EGZ-M
makeup module , water treatment sensor T2MCF ,
3. Hydraulic diagrams
1 ... makeup water 7 ... gas-side vessel connection 20DN
4 ... discharge hopper for vessel safety valve expansion pipe from/to system return8 ...
5 ... suction pipe from expansion vessel
6 ... overflow pipe from expansion vessel
8
1 ... makeup water 7 ... gas-side vessel connection 20DN
4 ... discharge hopper for vessel safety valve expansion pipe from/to system return8 ...
5 ... suction pipe from expansion vessel
6 ... overflow pipe from expansion vessel
multicontrol without degassing:modular
Options: second main vessel -M, additional vessels , expansion modules,EG EGZ-M
makeup module , water treatment sensor T2, cooling vesselMCF EV,
3. Hydraulic diagrams
9
4. Wiring diagrams
4. Wiring diagrams
10
4. Wiring diagrams
11
4. Wiring diagrams
12
4. Wiring diagrams
13
4. Wiring diagrams
notes
14
12|||
5. Commissioning
5. Commissioning
Commissioning procedure:
step 1 Determine the upper working pressure.
This upper working pressure is also the
set pressure of the overflow valve.
figure : determination of the upper and lower3
working pressure
step 2 Shut all connections from/to system return (expansion overflow pipe, expansion
pressure pipe, makeup water)
: Do shut suction pipe and overflow pipe at series!CAUTION NOT MCM
step 3 Fill and ventilate the system to the upper working pressure as determined in step 1.
step 4 Check the correctness of all hydraulic and electric connections, especially the
expansion pipe.
step 5 Open the makeup water connection to makeup module and set theMCF
pressure reducing valve to 1,5 bar - max. 2,0 bar.
Loosen the screw (1) at the pressure reducing valve
and set the scale to 1,5 bar - max. 2,0 bar.
To fix the setting, the screw must be tightened again.
NOTE!
Steps 1-3 must be completed on site in preparation for the commissioning.
i
NOTE!
Commissioning by the eder customer service resp. an authorized partner and training of
the operating personell is recommended!
i
static height
+ vapour pressure
+ __m working pressure
+ min. 5m safety margin
upper working pressure
lower working pressure
max. operating pressure
blow off pressure of safety valve
10 m wc (meter water column) ~ 1 bar
+ 5m safety margin
1
15
5. Commissioning
step 6 Switch on power supply and check if the red control lamp beside the key ”0”
glows. If not, deactivate the device by pressing the key ”0” and following
confirmation by pressing the key ”F1” (red control lamp beside the key ”0”
must glow!)
step 7 Fill and ventilate the pressure maintenance pump(s) and the piping.
- The Shut off devices at the intake side of the pump(s) must be opened com-
pletely and the regulating valve at the pumps outlet side must be closed
completely.
- Open the ventilating valve at the pump(s)
figure : ventilation valve at the pump4
- If a makeup module is installed, go to manual mode (user level 3), seeMCF
instruction manual , -_1, chapter 5.7, ”user level 3”.MCK MCM
- Switch on the output ”makeup valve Y1” (”output: on”) and fill the vessel until
a continuous water jet leaks from the ventilation valve at the pressure mainte-
nance pump. After this set the output ”makeup valve Y1” to automatic mode
(”output: auto”).
figure : ventilation of the pressure maintenance pump(s)5
Detail A
SW 9
Detail A
B
A
16
- If a makeup module is not installed, you have to fill the vessel (e.g. viaMCF
the emptying at the connection of the overflow pipe - see figure 5, detail B) until
a continuous water jet leaks from the ventilation valve (detail A) at the pressure
maintenance pump.
- To ensure a complete ventilation of the pump start and stop the pump in manual
mode (”output: Test”, operate with ”F1”) several times.
- In the course of these pump starts you have to check the direction of the rotation
of the pump motor. The fan wheel must rotate according to the sticker on top of
the motor cover. You can see the fan wheel through the holes of the pump cover.
figure 5: Checking the direction of rotation of the pump motor
- If the fan wheel doesn‘t rotate in the right direction, you have to change 2 of the 3
phases to weaken the rotating field and the direction of the rotation.
- Close the ventilation valve of the pressure maintenance pump.
- At devices with 2 pressure maintenance pumps (system Duo and Maxi) repeat
the above steps for the second pump (pump 1 = left side, pump 2 = right side).
step 8 Configuration of the multicontrol device
- Press the key “F2” (operate) in main display
- select menu item “code input”
- Enter the code (see instruction manual multicontrol , -_1,MCK MCM
chapter 5.7 “user level 3”)
- User level 3 is unlocked
- Go to menu item “device setup”
(if already done: „settings” „device setup”)g
5. Commissioning
INFORMATION!
Shut off all expansion vessels except the first -M vessel previously toEG
accelerate the filling.
i
17
User level 3
.))) device set-up
/))) vessel code
* .))) acc. to the sticker at the vessel
/))) correction value 1oPL
* .))) acc. to the sticker at the upper pressure transmitter
/))) correction value 1uPL
* .))) acc. to the sticker at the lower pressure transmitter
/))) makeup
* /))) not available (default setting)
* .))) is available
/))) water treatment (only if makeup is available)MCF
* /))) not available (default setting)
* /))) softening 6 resp. softening 12MWE MWE
* .))) desalination 2 resp. desalination 4MVE MVE
/))) degassing
* /))) not available (default setting)
* .))) degassing module
/))) binary signalling (only if module is installed)
* /))) not available (default setting)
* .))) is available
/))) remote acknowledgement (only if module is installed)
* /))) not available (default setting)
* .))) is available
/))) analog signalling (only if module is installed)
* /))) not available (default setting)
* .))) is available
/))) temperature sensor T2
* /))) not available (default setting)
* .))) is available
/))) level measurement L2
* /))) not available (default setting)
* .))) is available
/))) correction value 2oPL
* .))) acc. to the sticker at the upper pressure transmitter
*only displayed if level measurement L2 is available
/))) correction value 2uPL
* .))) acc. to the sticker at the lower pressure transmitter
*only displayed if level measurement L2 is available
/))) communication
* /))) not available (default setting)
* /))) SMS-Module
* /))) ASCII-Logger
* .))) Busmodule
/))) enable contact
* /))) not available (default setting)
* .))) is available
optional inputs
(accessories etc.)
mandatory inputs for
a correct function of
the device
5. Commissioning
18
.))) digital input
/))) not available (default setting)
/))) warning: contact open
/))) warning: contact closed
/))) error: contact open
.))) error: contact closed
step 9 Enable the device by pressing the key “I” in main display and confirm it by
pressing the key ”F1” (Yes) (green control lamp beside the key „I” must glow!)
step 10 Adjust the pressure maintenance pump(s)
Due to the necessary working pressure the pump(s) must be adjusted on the
output side. This adjustment must be done because the delivery rate of the
pump(s) (acc. to their characteristic curve) rises at low pressures.
A hint for a necessary adjustment could be:
After pump stop the overflow valve doesn‘t close completely before approx.
0,5 bar under the upper working pressure.
The setting (1) of the regulating valve(s) must be notated
at the plant- resp. commissioning record.
1: _________setting regulating valve pump
2: _________setting regulating valve pump (1)
INFORMATION!
If device setup was completed successfully (only mandatory inputs necessary) this menu
item is removed permanently. The device setup always is available in ”user level 3" g
”settings”.
i
5. Commissioning
NOTE!
The adjustment of the pressure maintenance pump(s) must be done before the setting of the
working pressure! After this neither the working pressure nor the adjustment must be
changed!
If the adjustment was done subsequently the working pressure must be set new!
i
optional inputs
(accessories etc.)
19
- +
pressure
(a)
- +
pressure
(b)
+ -
pressure
(c)
step 11 Set the working pressure
- Open the shut off devices from/to system return expansion pipe, makeup).(
If a degassing module is installed, the ball valve at its intake side must beMAE
closed.
Due to the size of the system the setting of the working pressure can take up a
lot of time because the pressure has to extend into the entire connected system
to be stable for the setting.
- Go to user level 3 (see step 9).
- Select “settings” “pressure maintenance” “working pressure”gg
- The display shows the current settings (complies with the last set working
pressure, e.g. default value ex factory)
: Independent to the displayed values the working pressure mustCAUTION
be set again in the course of commissioning!
- Press the key “F1” (change) to start the pump.
- Set the overflow valve to the upper working pressure (determined in step 1), the
current pressure is shown at the display.
5. Commissioning
The setting of the setpoint at the
overflow valve via
(a) ,black hand wheel
(b) hexagonal nut at the spring cap
(c) set point adjustment
(depends on the used type of the
overflow valve).
- Do not confirm the set upper wor-
king pressure until the desired
pressure is not stable for a few
minutes! (confirm with “F1” (apply)
- Enter the hysteresis (default value: 0,5 bar)
Difference between the set upper working pressure (set at the overflow valve)
and the start-up pressure of the pump (=lower working pressure).
- In devices with 2 overflow valves (system Twin), both valves must be set one by
one. One of these valves must be shut off, at the other one the upper working
pressure can be set. Then the set valve must be shut off and the other one can be
set - repeat the above steps (set both valves to the same pressure!)
figure 7: setting of the overflow valve
NOTE!
In Twin devices only one overflow valve must be in operation, the other one must be shut
off at its intake side. If both valves are in operation at the same time, the control behaviour
can be influenced negatively (e.g. too big hysteresis). Therefore this must be avoided!
i
20
step 12 If a makeup module is installed, the operating mode must be selected.MCF
The operating mode is depending on several criteria such as size of the system,
age of the system, possible known leakage and so on.
If there are known and regular leakages (e.g. a known makeup amount within a
known period) we recommend to use the operating mode ”time-controlled”.
For a description of the different operating modes see instruction manual
multicontrol , -_1, chapter 5.7 - “user level 3”.MCK MCM
step 13 If a degassing module is installed, the operating mode ”degassing module”MAE
must be selected. If the selection happened incorrectly, degassing can‘t work
correctly!
:Adjustment of the degassing module
- Shut off the regulating valve and the ball valve at the degassing module.
- Go to manual mode (user level 3) see instruction manual ,( multicontrol MCK
-_1 chapter 5.7 “user level 3”) and switch on the output ”degassing valve”MCM ,
(”output: on”)
- Wait until the motor valve opened completely (ca. 35 sec.; the scale resp., the
red axis at the electric actuator must not rotate anymore).
- Open the ball valve at the intake side.
- Open the regulating valve slowly until you hear a flow (ca. 1/4 turn). The plant
pressure decreases, the pressure maintenance pump starts.
- Look for the plant pressure shown at the display.
- The regulating valve is set correctly, if pump 1 is able to increase the plant
pressure and stops. If the pump can‘t increase the plant pressure resp. the
second pump (systems Duo, Maxi) starts, the regulating valve is set incorrectly
(opened too much).
- After this, the output ”degassing valve” must be set to ”Auto” again.
- (1)The setting of the regulating valve must be notated
at the plant- resp. commissioning record.
: _________setting regulating valve MAE (1)
step 14 The device is now ready for operation.
All shut off devices from/to system return must be secured against unintended
closing (e.g. by dismantling the handle,...)
Further settings (e.g. water treatment, operating modes etc.) must be done in
menu ”settings” (see instruction manual , -_1).MCK MCM
5. Commissioning
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32

eder MCM-M5-6 User manual

Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI