Generac 8 kW 0056100 User manual

  • Hello! I am an AI chatbot trained to assist you with the Generac 8 kW 0056100 User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Owner’s Manual
8, 10, 12, 14, 16, 17 & 20kW Air-cooled,
Automatic Standby Generators
DANGER
DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY!
Not intended for use as Primary Power in place of utility
or in life-support applications.
L
I
S
T
E
D
C
U
S
DO NOT LIFT UNIT BY ROOF!
INTRODUCTION
Thank you for purchasing this compact, high performance, air-
cooled, engine-driven generator. It is designed to automatically
supply electrical power to operate critical loads during a utility
power failure.
This unit is factory installed in an all-weather, metal enclosure and
is intended exclusively for outdoor installation. This generator
will operate using either vapor withdrawn liquid propane (LP) or
natural gas (NG).
NOTE:
This generator is suitable for supplying typical residential loads
such as Induction Motors (sump pumps, refrigerators, air con-
ditioners, furnaces, etc.), Electronic Components (computer,
monitor, TV, etc.), Lighting Loads and Microwaves.
READ THIS MANUAL THOROUGHLY
If any portion of this manual is not understood, contact the nearest
Dealer for starting, operating and servicing procedures.
Throughout this publication, and on tags and decals affixed to the
generator, DANGER, WARNING, CAUTION and NOTE blocks are
used to alert personnel to special instructions about a particular
operation that may be hazardous if performed incorrectly or care-
lessly. Observe them carefully. Their definitions are as follows:
DANGER
After this heading, read instructions that, if not
strictly complied with, will result in serious per-
sonal injury, including death.
After this heading, read instructions that, if not
strictly complied with, could result in serious per-
sonal injury, including death.
After this heading, read instructions that, if not
strictly complied with, might result in minor or mod-
erate injury.
NOTE:
After this heading, read instructions that, if not strictly complied
with, may result in damage to equipment and/or property.
These safety warnings cannot eliminate the hazards that they
indicate. Common sense and strict compliance with the special
instructions while performing the service are essential to pre-
venting accidents.
Four commonly used safety symbols accompany the DANGER,
WARNING and CAUTION blocks. The type of information each
indicates follows:
This symbol points out important safety
information that, if not followed, could endanger
personal safety and/or property of others.
This symbol points out potential explosion
hazard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock
hazard.
The operator is responsible for proper and safe use of the equip-
ment. The manufacturer strongly recommends that the operator
read this Owner's Manual and thoroughly understand all instruc-
tions before using this equipment. The manufacturer also strongly
recommends instructing other users to properly start and operate
the unit. This prepares them if they need to operate the equipment
in an emergency.
CONTENTS
This manual contains pertinent owner’s information for these
models:
7 kW NG, 8 kW LP, single-cylinder GH-410 Engine
9 kW NG, 10 kW LP, V-twin GT-530 Engine
12 kW NG, 12 kW LP, V-twin GT-990 Engine
13 kW NG, 14 kW LP, V-twin GT-990 Engine
16 kW NG, 16 kW LP, V-twin GT-990 Engine
16 kW NG, 17 kW LP, V-twin GT-990 Engine
18 kW NG, 20 kW LP, V-twin GT-999 Engine
OPERATION AND MAINTENANCE
It is the operator's responsibility to perform all safety checks, to
make sure that all maintenance for safe operation is performed
promptly, and to have the equipment checked periodically by a
Dealer. Normal maintenance service and replacement of parts
are the responsibility of the owner/operator and, as such, are not
considered defects in materials or workmanship within the terms
of the warranty. Individual operating habits and usage contribute to
the need for maintenance service.
Proper maintenance and care of the generator ensures a minimum
number of problems and keep operating expenses at a minimum.
See a Dealer for service aids and accessories.
HOW TO OBTAIN SERVICE
When the generator requires servicing or repairs, contact a Dealer
for assistance. Service technicians are factory-trained and are
capable of handling all service needs.
When contacting a Dealer about parts and service, always supply
the complete model number and serial number of the unit as given
on its data decal, which is located on the generator. See section "The
Generator" for decal location.
Model No. _________________ Serial No. ______________
Table of Contents
Air-cooled Generators
1
Introduction .................... Inside Front Cover
Read This Manual Thoroughly .............................................IFC
Contents ............................................................................IFC
Operation and Maintenance.................................................IFC
How to Obtain Service ........................................................IFC
Table of Contents ........................................ 1
Safety Rules .................................................2
Standards Index .....................................................................3
Section 1 – General Information ................. 4
1.1 Unpacking/Inspection .....................................................4
1.2 Protection Systems ........................................................4
1.3 NEC Requirement for Arc Fault Circuit
Interruption Breaker for Bedrooms ..................................4
1.4 Emission Information......................................................5
1.5 The Generator ................................................................6
1.6 Specifications ................................................................7
1.7 System Set LED .............................................................8
1.8 Fuel Requirements and Recommendations ......................8
1.9 Fuel Consumption ..........................................................8
1.10 Reconfiguring the Fuel System ........................................9
1.11 Location .......................................................................10
1.12 Battery Requirements ...................................................11
1.13 Battery Installation ........................................................13
1.14 The Battery ..................................................................13
1.15 Battery Charger ............................................................14
Section 2 – Post Installation Start-up
and Adjustments ....................14
2.1 Before Initial Startup .....................................................14
2.2 Check Transfer Switch Operation ..................................14
2.3 Electrical Checks ..........................................................14
2.4 Generator Tests Under Load ..........................................15
2.5 Checking Automatic Operation ......................................15
2.6 Engine Governor Adjustment ........................................16
2.7 Voltage Regulator Adjustment .......................................16
Section 3 – Operation ................................ 17
3.1 Control Panel Interface .................................................17
3.2 Automatic Transfer Operation ........................................18
3.3 Sequence of Automatic Operation .................................19
3.4 Manual Transfer Operation ............................................20
3.5 Side Compartment (V-twin Only) ..................................20
3.6 Protection Systems ......................................................21
Section 4 – Maintenance ...........................22
4.1 Fuse .............................................................................22
4.2 Checking the Engine Oil Level .......................................22
4.3 Changing the Engine Oil ................................................23
4.4 Changing the Engine Air Cleaner ...................................24
4.5 Spark Plug(s) ...............................................................25
4.6 Battery Maintenance .....................................................25
4.7 Adjusting GH-410/GT-530/990/999 Valve Clearance ......26
4.8 Cooling System ............................................................27
4.9 Attention After Submersion ...........................................27
4.10 Corrosion Protection.....................................................27
4.11 Out of Service Procedure ..............................................27
4.12 Service Schedule .........................................................29
Section 5 – Troubleshooting ..................... 30
5.1 Troubleshooting Guide ..................................................30
Section 6 – Appendix ................................ 31
6.1 Menu System Navigation ..............................................31
Section 7 – Installation Diagrams ............. 33
Section 8 – Warranty ................................. 36
2
Study these SAFETY RULES carefully before installing, operating
or servicing this equipment. Become familiar with this Owner’s
Manual and with the unit. The generator can operate safely, effi-
ciently and reliably only if it is properly installed, operated and
maintained. Many accidents are caused by failing to follow simple
and fundamental rules or precautions.
The manufacturer cannot anticipate every possible circumstance
that might involve a hazard. The warnings in this manual, and on
tags and decals affixed to the unit are, therefore, not all-inclusive. If
using a procedure, work method or operating technique the manu-
facturer does not specifically recommend, ensure that it is safe for
others. Also make sure the procedure, work method or operating
technique utilized does not render the generator unsafe.
DANGER
Despite the safe design of this generator,
operating this equipment imprudently, neglecting
its maintenance or being careless can cause
possible injury or death. Permit only responsible
and capable persons to install, operate and main-
tain this equipment.
Potentially lethal voltages are generated by
these machines. Ensure all steps are taken to
render the machine safe before attempting to
work on the generator.
Parts of the generator are rotating and/or hot
during operation. Exercise care near running
generators.
Installation must always comply with applicable
codes, standards, laws and regulations.
A running generator gives off carbon monoxide,
and odorless, colorless poison gas. Breathing in
carbon monoxide can cause headaches, fatigue,
diziness, nausea, vomitting, confusion, fainting,
siezures or death.
GENERAL HAZARDS
For safety reasons, the manufacturer recommends that this equip-
ment be installed, serviced and repaired by a Service Dealer or
other competent, qualified electrician or installation technician who
is familiar with applicable codes, standards and regulations. The
operator also must comply with all such codes, standards and
regulations.
The engine exhaust fumes contain carbon monoxide, which
can be DEADLY. This dangerous gas, if breathed in sufficient
concentrations, can cause unconsciousness or even death.
Do NOT alter or add to the exhaust system or do anything that
might render the system unsafe or in noncompliance with appli-
cable codes and standards.
Install a battery operated carbon monoxide alarm indoors,
according to manufacturer's instructions/recommendations.
Adequate, unobstructed flow of cooling and ventilating air is
critical to correct generator operation. Do not alter the instal-
lation or permit even partial blockage of ventilation provisions,
as this can seriously affect safe operation of the generator. The
generator MUST be installed and operated outdoors only.
Keep hands, feet, clothing, etc., away from drive belts, fans,
and other moving or hot parts. Never remove any drive belt or
fan guard while the unit is operating.
When working on this equipment, remain alert at all times.
Never work on the equipment when physically or mentally
fatigued.
Inspect the generator regularly, and contact the nearest Dealer
for parts needing repair or replacement.
Before performing any maintenance on the generator, discon-
nect its battery cables to prevent accidental start up. Disconnect
the cable from the battery post indicated by a NEGATIVE, NEG
or (–) first, then remove the POSITIVE, POS or (+) cable. When
reconnecting the cables, connect the POSITIVE cable first, the
NEGATIVE cable last.
Never use the generator or any of its parts as a step. Stepping
on the unit can stress and break parts, and may result in dan-
gerous operating conditions from leaking exhaust gases, fuel
leakage, oil leakage, etc.
ENGINE EXHAUST HAZARDS
Generator engine exhaust contains DEADLY carbon monox-
ide, an odorless, colorless poisonous gas. Breathing carbon
monoxide can cause: dizziness, throbbing temples, nausea,
muscular twitching, headache, vomiting, weakness and sleepi-
ness, inability to think clearly, fainting, unconsciousness or
even death. If you experience any carbon monoxide poisoning
symptoms, move into fresh air and immediately seek medical
attention.
Never operate the generator set with the vehicle inside any
garage or other enclosed area.
IMPORTANT SAFETY INSTRUCTIONS
Air-cooled Generators
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted near
the unit’s installation site. Safety should be stressed to all operators and potential operators of this equipment.
The engine exhaust from this product
contains chemicals known to the state
of California to cause cancer, birth
defects or other reproductive harm.
WARNING:
This product contains or emits chemicals
known to the state of California to cause
cancer, birth defects or other reproductive harm.
WARNING:
3
ELECTRICAL HAZARDS
All generators covered by this manual produce dangerous
electrical voltages and can cause fatal electrical shock. Utility
power delivers extremely high and dangerous voltages to the
transfer switch as does the standby generator when it is in
operation. Avoid contact with bare wires, terminals, connec-
tions, etc., while the unit is running. Ensure all appropriate
covers, guards and barriers are in place, secured and/or locked
before operating the generator. If work must be done around
an operating unit, stand on an insulated, dry surface to reduce
shock hazard.
Do not handle any kind of electrical device while stand-
ing in water, while barefoot, or while hands or feet are wet.
DANGEROUS ELECTRICAL SHOCK MAY RESULT.
The National Electrical Code (NEC) requires the frame and external
electrically conductive parts of the generator to be connected to
an approved earth ground. Local electrical codes also may require
proper grounding of the generator electrical system.
After installing this home standby electrical system, the genera-
tor may crank and start at any time without warning. When this
occurs, load circuits are transferred to the STANDBY (genera-
tor) power source. To prevent possible injury if such a start and
transfer occur, always set the generator’s AUTO/OFF/MANUAL
switch to its OFF position before working on equipment and
remove the 15A fuse from the generator control panel.
In case of accident caused by electric shock, immediately shut
down the source of electrical power. If this is not possible,
attempt to free the victim from the live conductor. AVOID DIRECT
CONTACT WITH THE VICTIM. Use a nonconducting implement,
such as a dry rope or board, to free the victim from the live
conductor. If the victim is unconscious, apply first aid and get
immediate medical help.
Never wear jewelry when working on this equipment. Jewelry
can conduct electricity resulting in electric shock, or may get
caught in moving components causing injury.
FIRE HAZARDS
For fire safety, the generator must be installed and maintained
properly. Installation must always comply with applicable
codes, standards, laws and regulations. Adhere strictly
to local, state and national electrical and building codes.
Comply with regulations the Occupational Safety and Health
Administration (OSHA) has established. Also, ensure that the
generator is installed in accordance with the manufacturer’s
instructions and recommendations. Following proper installa-
tion, do nothing that might alter a safe installation and render
the unit in noncompliance with the aforementioned codes,
standards, laws and regulations.
Keep a fire extinguisher near the generator at all times.
Extinguishers rated “ABC” by the National Fire Protection
Association are appropriate for use on the standby electric
system. Keep the extinguisher properly charged and be familiar
with its use. Consult the local fire department with any ques-
tions pertaining to fire extinguishers.
EXPLOSION HAZARDS
Do not smoke around the generator. Wipe up any fuel or oil
spills immediately. Ensure that no combustible materials are left
in the generator compartment, or on or near the generator, as
FIRE or EXPLOSION may result. Keep the area surrounding the
generator clean and free from debris.
Gaseous fluids such as natural gas and liquid propane (LP)
gas are extremely EXPLOSIVE. Install the fuel supply system
according to applicable fuel-gas codes. Before placing the
home standby electric system into service, fuel system lines
must be properly purged and leak tested according to applica-
ble code. After installation, inspect the fuel system periodically
for leaks. No leakage is permitted.
STANDARDS INDEX
In the absence of pertinent standards, codes, regulations and
laws, the published information listed below may be used for
installation guidance for this equipment.
1. NFPA No. 37, STATIONARY COMBUSTION ENGINES AND
GAS TURBINES, available from the National Fire Protection
Association, 470 Atlantic Avenue, Boston, MA 02210.
2. NFPA No. 76A, ESSENTIAL ELECTRICAL SYSTEMS FOR
HEALTH CARE FACILITIES, available same as Item 1.
3. NFPA No. 54, NATIONAL FUEL GAS CODE, available same as
Item 1.
4. NFPA No. 58, AMERICAN NATIONAL STANDARD FOR
STORAGE AND HANDLING OF LIQUEFIED PETROLEUM GAS,
available same as Item 1.
5. NFPA No. 70, NFPA HANDBOOK OF NATIONAL ELECTRIC
CODE, available same as Item 1.
6. Article X, NATIONAL BUILDING CODE, available from the
American Insurance Association, 85 John Street, New York,
N.Y. 10038.
7. AGRICULTURAL WIRING HANDBOOK, available from the Food
and Energy Council, 909 University Avenue, Columbia, MO
65201.
8. ASAE EP-3634, INSTALLATION AND MAINTENANCE OF
FARM STANDBY ELECTRICAL SYSTEMS, available from the
American Society of Agricultural Engineers, 2950 Niles Road,
St. Joseph, MI 49085.
9. NFPA No. 30, FLAMMABLE AND COMBUSTIBLE LIQUIDS
CODE, available same as Item 1.
IMPORTANT SAFETY INSTRUCTIONS
Air-cooled Generators
DANGER
Only qualified electricians or contractors should
attempt such installations, which must comply
strictly with applicable codes, standards and regu-
lations.
1.1 UNPACKING/INSPECTION
After unpacking, carefully inspect the contents for damage.
This standby generator set is ready for installation with a factory
supplied and pre-mounted base pad and has a weather protec-
tive enclosure that is intended for outdoor installation only.
This UL listed standby generator set may be packaged with an
automatic transfer switch with built in load center. The combi-
nation transfer switch and load center is pre-wired with a two
foot and 30 foot conduit. Circuit breakers for emergency circuit
connections are included (if equipped).
This UL listed, 2-pole switch is rated at 100 or 200 AC amperes
at 250 volts maximum. The 100 Amp transfer switch is for
indoor use only. The 200 Amp transfer switch is for indoor/
outdoor use (if equipped).
If this generator is used to power electrical load
circuits normally powered by a utility power
source, it is required by code to install a transfer
switch. The transfer switch must effectively isolate
the electrical system from the utility distribution
system when the generator is operating (NEC 700,
701 & 702). Failure to isolate an electrical system
by such means will result in damage to the gen-
erator and also may result in injury or death to
utility power workers due to backfeed of electrical
energy.
If any loss or damage is noted at time of delivery, have the
person(s) making the delivery note all damage on the freight bill
or affix their signature under the consignor's memo of loss or
damage.
If a loss or damage is noted after delivery, separate the damaged
materials and contact the carrier for claim procedures.
“Concealed damage” is understood to mean damage to the con-
tents of a package that is not in evidence at the time of delivery,
but is discovered later.
To properly open the roof, press down on the center top lip and
release the latch. If pressure is not applied from the top, the roof
may appear stuck. Always verify that the side lock is unlocked
before attempting to lift the roof.
1.2 PROTECTION SYSTEMS
Unlike an automobile engine, the generator may have to run for
long periods of time with no operator present to monitor engine
conditions. For that reason, the engine is equipped with the fol-
lowing systems that protect it against potentially damaging condi-
tions:
1. Low Oil Pressure Sensor
2. High Temperature Sensor
3. Overcrank
4. Overspeed
5. RPM Sensor
6. Low Battery
There are readouts on the control panel to notify personnel that
one of these failures has occurred. There is also a System Set LED
(single cylinder) or a Status message on the display (V-twins) that
displays when all of the conditions described in the "System Set
LED" section are true.
1.3 NEC REQUIREMENT FOR ARC FAULT
CIRCUIT INTERRUPTION BREAKER FOR
BEDROOMS
In 2001, the National Electric Code (NEC) introduced a requirement
for new construction. This new requirement indicates the need for
Arc Fault Circuit Interrupters to be used to protect the complete
branch circuit that feeds a dwelling bedroom. The actual NEC
requirement is indicated below.
1.3.1 SECTION 210.12 ARC FAULT CIRCUIT INTER-
RUPTER PROTECTION
1. Definition: An arc fault circuit interrupter is a device intended
to provide protection from the effects of arc faults by recog-
nizing characteristics unique to arcing and by functioning to
de-energize the circuit when an arc fault is detected.
2. Dwelling Unit Bedrooms: All branch circuits that supply 125
volt, single-phase, 15 and 20 ampere outlets installed in
dwelling unit bedrooms shall be protected by an arc fault cir-
cuit interrupter listed to provide protection of the entire branch
circuit.
Section 210.12 requires that AFCI protection be provided on branch
circuits that supply outlets (receptacle, lighting, etc.) in dwell-
ing bedrooms. The requirement is limited to 15 and 20 ampere,
125 volt circuits. There is no prohibition against providing AFCI
protection on other circuits or in locations other than bedrooms.
Because circuits are often shared between a bedroom and other
areas such as closets and hallways, providing AFCI protection on
the complete circuit would comply with 210.12.
Section 1 — General Information
Air-cooled Generators
4
Section 1 — General Information
Air-cooled Generators
5
If during the installation of the home standby system the decision
is made to provide back up power to a bedroom branch circuit,
then the circuit breaker in the transfer switch should be replaced
with an Arc Fault Circuit Interrupter.
It is most important that breakers only be switched like for like.
For instance, if replacing a 15A breaker, it MUST be replaced with
a 15A AFCI breaker. Likewise, a 20A breaker MUST be replaced
with a 20A AFCI.
These AFCI breakers are available at the nearest hardware store.
Siemens Item # Description
Q115AF 15A Single Pole AFCI
Q120AF 20A Single Pole AFCI
1.4 EMISSION INFORMATION
The Environmental Protection Agency requires that this generator
complies with exhaust emission standards. This generator is certi-
fied to meet the applicable EPA emission levels. Additional infor-
mation regarding the requirements set by the EPA is as follows:
The generator is certified for use as a stationary engine for standby
power generation. Any other use may be a violation of federal
and/or local laws. It is important that to follow the maintenance
specifications in the "Maintenance" section to ensure that the
engine complies with the applicable emission standards for the
duration of the engine’s life. This engine is certified to operate on
Liquid Propane fuel and pipeline Natural Gas. The emission control
system on the generator consists of the following:
Fuel Metering System
Carburetor/mixer assembly
Fuel regulator
Air Induction System
Intake pipe/manifold
Air cleaner
Ignition System
Spark plug
Ignition module
The Emissions Compliance Period referred to on the Emissions
Compliance Label indicates the number of operating hours for
which the engine has been shown to meet Federal emission
requirements. See the table below to determine the compliance
period for the generator. The displacement of the generator is listed
on the Emissions Compliance Label.
Displacement Category Compliance Period
< 66 cc
A 300 Hours
B 125 Hours
C 50 Hours
66 cc -
< 225 cc
A 500 Hours
B 250 Hours
C 125 Hours
225 cc
A 1000 Hours
B 500 Hours
C 250 Hours
6
Section 1 — General Information
Air-cooled Generators
1.5 THE GENERATOR
Data Label
(see sample)
Oil
Dipstick
Exhaust
Enclosure
Composite Base Oil Filter Battery Compartment
Fuel
Regulator
Fuel Inlet
(back)
Air Filter
Circuit
Breaker
Control
Panel
Data Label
(see sample)
Oil
Dipstick
Exhaust
Enclosure
Composite Base Oil Filter Battery Compartment
Fuel
Regulator
Fuel Inlet
(back)
Air Filter
Circuit
Breakers
Control
Panel
Figure 1.3 – 12, 14, 16, 17 and 20kW, V-twin,
GT-990/GT-999 Engine (door removed)
Figure 1.1 – 8kW, Single Cylinder, GH-410 Engine
(door removed)
Data Label
(see sample)
Oil
Dipstick
Exhaust
Enclosure
Composite Base Oil Filter Battery Compartment
Fuel
Regulator
Fuel Inlet
(back)
Air
Filter
Circuit
Breaker
Control
Panel
Figure 1.2 – 10kW, V-twin, GT-530 Engine
(door removed)
Data Label Sample
7
Section 1 — General Information
Air-cooled Generators
1.6 SPECIFICATIONS
1.6.1 GENERATOR
Model 8kW 10kW 12kW 14kW 16kW 17kW 20kW
Rated Maximum
Power Capacity (Watts*)
7,000 NG
8,000 LP
9,000 NG
10,000 LP
12,000 NG
12,000 LP
13,000 NG
14,000 LP
16,000 NG
16,000 LP
16,000 NG
17,000 LP
18,000 NG
20,000 LP
Rated Voltage 120/240
Rated Maximum Load Current (Amps)
120 Volts** (NG/LP) 58.3/66.6 75.0/83.3 100.0/100.0 108.3/116.6 133.3/133.3 133.3/141.6 150.0/166.6
240 Volts (NG/LP) 29.2/33.3 37.5/41.6 50.0/50.0 54.2/58.3 66.6/66.6 66.6/70.8 75.0/83.3
Main Circuit Breaker 35 Amp 45 Amp 50 Amp 60 Amp 65 Amp 65 Amp 100 Amp
Circuits*** 50A, 240V - - - 1 1 1 -
40A, 240V - - 1 1 1 1 -
30A, 240V 1 1 1 - - - -
20A, 240V - 1 - 1 1 1 -
20A, 120V 1 3 3 4 5 5 -
15A, 120V 5 3 5 4 5 5 -
Phase 1
Number of Rotor Poles 2
Rated AC Frequency 60 Hz
Battery Requirement
Group 26R, 12
Volts and 350 CCA
Minimum
Group 26R, 12 Volts and 525 CCA Minimum
Weight (unit only in lbs.) 340 387 439 439 439 455/421 450
Enclosure Steel Steel Steel Steel Steel Steel/Aluminum Aluminum
Normal Operating Range -20° F (-28.8° C) to 77° F (25° C)
* Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc. Maximum power decreases about
3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 6 C (10 F) above 16 C (60 F) ambient temperature.
** Load current values shown for 120 volts are maximum TOTAL values for two separate circuits. The maximum current in each circuit must not exceed the value stated for the 240 volts.
*** Circuits to be moved must be protected by same size breaker. For example, a 15 amp circuit in the main panel must be a 15 amp circuit in the transfer switch.
1.6.2 ENGINE
Model 8 kW 10 kW 12/14/16/17 kW 20 kW
Type of Engine GH-410 GT-530 GT-990 GT-999
Number of Cylinders 1 2 2 2
Rated Horsepower @ 3,600 rpm 14.8 18 32 36
Displacement 410cc 530cc 992cc 999cc
Cylinder Block Aluminum w/Cast Iron Sleeve
Valve Arrangement Overhead Valves
Ignition System Solid-state w/Magneto
Recommended Spark Plug RC14YC BPR6HS RC14YC RC12YC
Spark Plug Gap 0.76 mm (0.030 inch) 0.76 mm (0.030 inch) 1.02 mm (0.040 inch) 0.76 mm (0.030 inch)
Compression Ratio 8.6:1 9.5:1 9.5:1 9.5:1
Starter 12 VDC
Oil Capacity Including Filter Approx. 1.5 Qts Approx. 1.7 Qts Approx. 1.7 Qts Approx. 1.7 Qts
Recommended Oil Filter Part # 070185F
Recommended Air Filter Part # 0G3332 Part # 0E9581 Part # 0C8127 Part # 0G5894
Operating RPM 3,600
1.7 SYSTEM SET LED
The “System Set” LED (single cylinder) or "Ready to Run" on the
display (v-twin) is ready when all of the following conditions are
true:
1. The AUTO/OFF/MANUAL switch is set to the AUTO position.
2. The utility voltage being supplied to the unit is being sensed
by the PCB. If the utility sense voltage is not connected to the
unit or if it is below approximately 150-160 volts AC, then the
system set light will flash rapidly (8kW). This indicates that if
the AUTO/OFF/MANUAL switch is placed in the Auto position,
the generator will start.
3. No alarms are present, for example, low oil pressure, high
temperature, etc.
1.8 FUEL REQUIREMENTS
AND RECOMMENDATIONS
With LP gas, use only the vapor withdrawal system. This type of
system uses the vapors formed above the liquid fuel in the storage
tank.
The engine has been fitted with a fuel carburetion system that
meets the specifications of the 1997 California Air Resources
Board for tamper-proof dual fuel systems. The unit will run on
natural gas or LP gas, but it has been factory set to run on natural
gas. Should the primary fuel need to be changed to LP gas, the
fuel system needs to be reconfigured. See the reconfiguring the
Fuel System section for instructions on reconfiguration of the fuel
system.
Recommended fuels should have a Btu content of at least 1,000
Btus per cubic foot for natural gas; or at least 2,520 Btus per
cubic foot for LP gas. Ask the fuel supplier for the Btu content of
the fuel.
Required fuel pressure for natural gas is five (5) inches to seven
(7) inches water column (0.18 to 0.25 psi); and for liquid pro-
pane, 10 inches to 12 inches of water column (0.36 to 0.43 psi).
The primary regulator for the propane supply is NOT INCLUDED
with the generator.
NOTE:
All pipe sizing, construction and layout must comply with NFPA
54 for natural gas applications and NFPA 58 for liquid propane
applications. Once the generator is installed, verify that the fuel
pressure NEVER drops below four (4) inches water column for
natural gas or 10 inches water column for liquid propane.
Prior to installation of the generator, the installer should consult
local fuel suppliers or the fire marshal to check codes and regula-
tions for proper installation. Local codes will mandate correct rout-
ing of gaseous fuel line piping around gardens, shrubs and other
landscaping to prevent any damage.
Special considerations should be given when installing the unit
where local conditions include flooding, tornados, hurricanes,
earthquakes and unstable ground for the flexibility and strength of
piping and their connections.
Use an approved pipe sealant or joint compound on all threaded
fitting.
All installed gaseous fuel piping must be purged and leak tested
prior to initial start-up in accordance with local codes, standards
and regulations.
1.9 FUEL CONSUMPTION
Unit
Nat. Gas LP Vapor
1/2 Load Full Load 1/2 Load Full Load
7/8 kW 77 140 0.94/34 1.68/62
9/10 kW 102 156 1.25/46 1.93/70
12/12 kW 152 215 1.53/56 2.08/76
13/14 kW 156 220 1.56/58 2.30/84
16/16 kW 183 261 1.59/58 2.51/91
16/17 kW 183 261 1.61/59 2.57/94
18/20 kW 206 294 1.89/69 2.90/106
* Natural gas is in cubic feet per hour.
** LP is in gallons per hour/cubic feet per hour.
*** Values given are approximate.
Verify that gas meter is capable of providing enough fuel flow to
include household appliances.
1.9.1 BTU FLOW REQUIREMENTS -
NATURAL GAS
BTU flow required for each unit based on 1000 BTU per cubic
foot.
7kW — 140,000 BTU/Hour
9kW — 156,000 BTU/Hour
12kW — 215,000 BTU/Hour
13kW — 220,000 BTU/Hour
16kW — 261,000 BTU/Hour
18kW — 294,000 BTU/Hour
DANGER
Gaseous fuels such as natural gas and liquid
propane (LP) gas are highly explosive. Even the
slightest spark can ignite such fuels and cause
an explosion. No leakage of fuel is permitted.
Natural gas, which is lighter than air, tends to
collect in high areas. LP gas is heavier than air
and tends to settle in low areas.
NOTE:
A minimum of one approved manual shut-off valve must be
installed in the gaseous fuel supply line. The valve must be eas-
ily accessible. Local codes determine the proper location.
Section 1 — General Information
Air-cooled Generators
8
9
1.10 RECONFIGURING THE
FUEL SYSTEM
1.10.1 8 KW, 410CC ENGINE
To reconfigure the fuel system from NG to LP, follow these steps
(Figure 1.4):
NOTE:
The primary regulator for the propane supply is NOT INCLUDED
with the generator. A fuel pressure of 10 to 12 inches of water
column (0.36 to 0.43 psi) to the fuel inlet of the generator MUST
BE SUPPLIED.
1. Turn off the main gas supply (if connected).
2. Open the roof and remove the door.
3. Remove the battery (if installed).
4. Take the plastic T-handle fuel selector in the poly bag supplied
with the generator.
5. Locate the selector knob on the air box cover, behind the
yellow air filter door and power bulge. The unit comes from
the factory in the NG (Natural Gas) position. Grasping the
T-handle, insert the pin end into the hole in the selector knob
and pull out to overcome spring pressure and then twist
clockwise 90 degrees and allow the selector to return in once
aligned with the LP (Liquid Propane) position.
6. Save this tool with the Owner's Manual.
7. Install the battery, door and close the roof.
8. Reverse the procedure to convert back to natural gas.
Figure 1.4 – Fuel Selector
NOTE:
Use an approved pipe sealant or joint compound on all threaded
fittings to reduce the possibility of leakage.
1.10.2 10, 12, 14, 16, 17 AND 20KW, V-TWIN
ENGINES
To reconfigure the fuel system from NG to LP, follow these steps:
NOTE:
The primary regulator for the propane supply is NOT INCLUDED
with the generator. A fuel pressure of 10 to 12 inches of water
column (0.36 to 0.43 psi) to the fuel inlet of the generator MUST
BE SUPPLIED.
1. Open the roof.
2. For 10kW units: Loosen clamp and slide back the air inlet
hose.
Slide fuel selector on carburetor out towards the back of the
enclosure (Figures 1.5 and 1.6).
Return the inlet hose and tighten clamp securely.
For 12, 14, 16, 17 and 20kW units: remove the air cleaner
cover.
Slide the selector lever out towards the back of the enclosure
(Figures 1.7 and 1.8).
Return the air cleaner cover and tighten the two thumb
screws.
Figure 1.5 - 10kW, GT-530 (Inlet Hose Slid Back)
Fuel Selection
Lever - "In"
Position for
Natural Gas
Fuel
Figure 1.6 - 10kW, GT-530 (Inlet Hose Slid Back)
Fuel Selection
Lever - "Out"
Position for
Liquid Propane
(Vapor) Fuel
Section 1 — General Information
Air-cooled Generators
10
3. Close the roof.
4. Reverse the procedure to convert back to natural gas.
Figure 1.7 - 12, 14, 16, 17, & 20kW,
GT-990/GT-999 (Airbox Cover Removed)
Fuel Selection Lever - "In" Position for Natural Gas Fuel
Figure 1.8 - 12, 14, 16, 17, & 20kW,
GT-990/GT-999 (Airbox Cover Removed)
Fuel Selection Lever - "Out" Position for Liquid Propane
(Vapor) Fuel
1.11 LOCATION
DANGER
The engine exhaust fumes contain carbon mon-
oxide, which can be DEADLY. This dangerous
gas, if breathed in sufficient concentrations,
can cause unconsciousness or even death. This
generator must be installed properly, in strict
compliance with applicable codes and stan-
dards. Following installation, do nothing that
might render the system unsafe or in noncom-
pliance with such codes and standards.
• Operate the generator outdoors ONLY.
Keep exhaust gases from entering a confined
area through windows, doors, ventilation, crawl
spaces or other openings (Figure 1.9).
Generac Power Systems as a responsible manu-
facturer highly recommends that carbon monox-
ide detector(s) be installed indoors according to
the manufacturer's instructions/recommendations.
The generator must me mounted safely per appli-
cable codes and the manufacturer's specifica-
tions. Do NOT alter or add to the exhaust system,
or do anything that might render the exhaust sys-
tem unsafe or in noncompliance with applicable
codes and standards.
1.11.1 GENERATOR
Install the generator set, in its protective enclosure, outdoors,
where adequate cooling and ventilating air is always available
(Figure 1.9). Consider these factors:
The installation of the generator must comply strictly with
NFPA 37, NFPA 54, NFPA 58, and NFPA 70 standards.
Install the unit where air inlet and outlet openings will not
become obstructed by leaves, grass, snow, etc.. If prevailing
winds will cause blowing or drifting, consider using a wind-
break to protect the unit.
Install the generator on high ground where water levels will not
rise and endanger it.
Allow sufficient room on all sides of the generator for mainte-
nance and servicing. This unit must be installed in accordance
with current applicable NFPA 37 and NFPA 70 standards; as
well as any other federal, state and local codes for minimum
distances from other structures. DO NOT install under wooden
decks or structures unless there is at least four (4) feet of clear-
ance above the generator, three (3) feet of clearance on sides
and front, and 18 inches of clearance at back of unit.
Install the unit where rain gutter down spouts, roof run-off,
landscape irrigation, water sprinklers or sump pump discharge
does not flood the unit or spray the enclosure, including any air
inlet or outlet openings.
Install the unit where services will not be affected or obstructed,
including concealed, underground or covered services such as
electrical, fuel, phone, air conditioning or irrigation.
Where strong prevailing winds blow from one direction, face the
generator air inlet openings to the prevailing winds.
Install the generator as close as possible to the fuel supply, to
reduce the length of piping.
Install the generator as close as possible to the transfer switch.
REMEMBER THAT LAWS OR CODES MAY REGULATE THE
DISTANCE AND LOCATION.
The genset must be installed on a level surface. The base frame
must be level within two (2) inches all around.
The generator is typically placed on pea gravel or crushed
stone. Check local codes if a concrete slab is required. If a
concrete base slab is required, all federal, state and local codes
should be followed. Special attention should be given to the
concrete base slab which should exceed the length and width
of the generator by a minimum of six (6) inches (0.152 meters)
on all sides.
Section 1 — General Information
Air-cooled Generators
11
Figure 1.9 – Generator Clearances
1.11.2 NEW INSTALLATION GUIDELINES FOR
STATIONARY AIR-COOLED 8, 10, 12, 14, 16,
17 AND 20 KW GENERATORS.
The National Fire Protection Association has a standard for the
installation and use of stationary combustion engines. That
standard is NFPA 37 and its requirements limit the spacing of an
enclosed generator set from a structure or wall (Figure 1.10).
NFPA 37, Section 4.1.4, Engines Located Outdoors. Engines, and
their weatherproof housings if provided, that are installed outdoors
shall be located at least 5 ft. from openings in walls and at least 5
ft. from structures having combustible walls. A minimum separa-
tion shall not be required where the following conditions exist:
1. The adjacent wall of the structure has a fire resistance rating
of at least 1 hour.
2. The weatherproof enclosure is constructed of noncombus-
tible materials and it has been demonstrated that a fire within
the enclosure will not ignite combustible materials outside the
enclosure.
Annex A — Explanatory Material
A4.1.4 (2) Means of demonstrating compliance are by means
of full scale fire test or by calculation procedures.
Because of the limited spaces that are frequently available for
installation, it has become apparent that exception (2) would be
beneficial for many residential and commercial installations. With
that in mind, the manufacturer contracted with an independent
testing laboratory to run full scale fire tests to assure that the
Carrier enclosure would not ignite combustible materials outside
the enclosure.
The criteria was to determine the worst case fire scenario within
the generator and to determine the ignitability of items outside
the engine enclosure at various distances. The Carrier enclosure
is constructed of non-combustible materials and the results and
conclusions from the independent testing lab indicated that any
fire within the generator enclosure would not pose any ignition risk
to nearby combustibles or structures, with or without fire service
personnel response.
Based on this testing and the requirements of NFPA 37, Sec 4.1.4,
the guidelines for installation of the generators listed above are
changed to 18 inches (457mm) from the back side of the genera-
tor to a stationary wall or building. For adequate maintenance and
airflow clearance, the area above the generator should be at least
4 feet with a minimum of 3 feet at the front and ends of the enclo-
sure. This would include trees, shrubs and vegetation that could
obstruct airflow. See the diagram on the reverse of this page and
the installation drawing within the owner’s manual for details.
Generator exhaust contains DEADLY carbon monoxide gas. This
dangerous gas can cause unconsciousness or death. Do not place
the unit near windows, doors, fresh air intakes (furnaces, etc.) or
any openings in the building or structure, including windows and
doors of an attached garage.
1.11.3 TRANSFER SWITCH ( if included)
1.11.3.1 8, 10, 12, 14, 16, 17 and 20kW Units
(if equipped)
The transfer switch that may have shipped inside the carton with
the 8, 10, 12, 14, 16 or 17kW generator is enclosed in a NEMA
1 (indoor rated only) enclosure. The transfer switch that may
have shipped with the 20kW generator is enclosed in a NEMA 3R
(indoor/outdoor rated) enclosure.
Install the transfer switch indoors on a firm, sturdy supporting
structure.
To prevent switch distortion, level the switch if necessary. This
can be done by placing washers between the switch enclosure
and mounting surface.
Never install the switch where water or any corrosive substance
might drip onto the enclosure.
Protect the switch at all times against excessive moisture, dust,
dirt, lint, construction grit and corrosive vapors.
If the AUTO/OFF/MANUAL switch is not set to its
OFF position, the generator can crank and start
as soon as the battery cables are connected. If
the utility power supply is not turned off, spark-
ing can occur at the battery posts and cause an
explosion.
1.12 BATTERY REQUIREMENTS
See the Specifications section for correct battery size and rating.
Section 1 — General Information
Air-cooled Generators
12
Section 1 — General Information
Air-cooled Generators
Figure 1.10 – Installation Guidelines
18 inches
Minimum Distance
36 inches
36 inches
36 inches
60 inches 60 inches
Existing Wall
No windows or openings in the wall permitted
within 5 feet from any point of the generator.
Top of Generator
48” Minimum
60” Recommended
Minimum From Ends
18 inches
Minimum
Generator
Clearance from windows,
doors, any openings in the
wall, shrubs or vegetation
over 12” in height
Clearance from the ends and front of the
generator should be 36 inches. This
would include shrubs, trees and any
kind of vegetation. Clearance at the top
should be a minimum of 48 inches from
any structure, overhang or projections
from the wall. The generator should not
be placed under a deck or other
structure that is closed in and would limit
or contain air flow.
These guidelines are based upon fire
testing of the generator enclosure and
the manufacturer’s requirement for air
flow for proper operation. Local codes
may be different and more restrictive
than what is described here.
This drawing supersedes installation instructions in all Carrier air-cooled installation and owner’s manuals dated
previous to May 26, 2007.
13
1.13 BATTERY INSTALLATION
Fill the battery with the proper electrolyte fluid if necessary and
have the battery fully charged before installing it.
Before installing and connecting the battery, complete the follow-
ing steps:
1. Set the generator's AUTO/OFF/MANUAL switch to OFF.
2. Turn off utility power supply to the transfer switch.
3. Remove the 7.5A fuse from the generator control panel.
Battery cables were factory connected at the generator (Figure
1.10). Connect cables to battery posts as follows:
4. Connect the red battery cable (from starter contactor) to the
battery post indicated by a positive, POS or (+).
5. Connect the black battery cable (from frame ground) to the
battery post indicated by a negative, NEG or (—).
Figure 1.10 – Battery Cable Connections
NOTE:
Dielectric grease should be used on battery posts to aid in the
prevention of corrosion.
NOTE:
Damage will result if battery connections are made in reverse.
NOTE:
In areas where temperatures regularly fall below 10° F (-12° C)
it is recommended that a pad type battery heater be installed to
aid in cold climate starting.
1.14 THE BATTERY
DANGER
Do not dispose of the battery in a fire. The
battery is capable of exploding.
A battery presents a risk of electrical shock
and high short circuit current. The following pre-
cautions are to be observed when working on
batteries:
Remove the 7.5A fuse from the generator control
panel.
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
Do not lay tools or metal parts on top of the
battery; and
Disconnect charging source prior to connecting or
disconnecting battery terminals.
Do not open or mutilate the battery. Released
electrolyte has been known to be harmful to the
skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is
harmful to the skin and eyes. It is electrically
conductive and corrosive.
The following procedures are to be observed:
• Wear full eye protection and protective clothing;
Where electrolyte contacts the skin, wash it off
immediately with water;
Where electrolyte contacts the eyes, flush thor-
oughly and immediately with water and seek medi-
cal attention; and
Spilled electrolyte is to be washed down with an
acid neutralizing agent. A common practice is to
use a solution of 1 pound (500 grams) bicarbonate
of soda to 1 gallon (4 liters) of water. The bicar-
bonate of soda solution is to be added until the
evidence of reaction (foaming) has ceased. The
resulting liquid is to be flushed with water and the
area dried.
Lead-acid batteries present a risk of fire
because they generate hydrogen gas. The fol-
lowing
procedures are to be followed:
• DO NOT SMOKE when near the battery;
• DO NOT cause flame or spark in battery area; and
Discharge static electricity from body before
touching the battery by first touching a grounded
metal surface.
Be sure the AUTO/OFF/MANUAL switch is set to
the OFF position before connecting the battery
cables. If the switch is set to AUTO or MANUAL,
the generator can crank and start as soon as
the battery cables are connected.
Section 1 — General Information
Air-cooled Generators
14
Be sure the utility power supply is turned off
and the 7.5A fuse is removed from the generator
control panel, or sparking may occur at the bat-
tery posts as the cables are attached and cause
an explosion.
Servicing of the battery is to be performed or supervised by per-
sonnel knowledgeable of batteries and the required precautions.
Keep unauthorized personnel away from batteries.
See the Specifications section for the correct size and rating when
replacing the battery. Have these procedures performed at the
intervals specified in the “Service Schedule.” A negative ground
system is used. Battery connections are shown on the wiring dia-
grams. Make sure the battery is correctly connected and terminals
are tight. Observe battery polarity when connecting the battery to
the generator set.
1.15 BATTERY CHARGER
NOTE:
These generators DO NOT contain an internal battery charger.
NOTE:
The manufacturer provides a battery trickle charger that is
active when the unit is set up for automatic operation. With
the battery installed and utility power source voltage available
to the transfer switch, the battery receives a trickle charge to
prevent self-discharge. The trickle charger is designed to help
extend the life of the battery by maintaining the battery. The
trickle charge feature cannot be used to recharge a discharged
battery.
For units shipped with a transfer switch/load center, the battery
charger is pre-installed in the transfer switch enclosure.
For units shipped without a transfer switch/load center, a separate
battery charger module is included with the generator.
(For battery charger installation, see the Generator Install Guidelines
and Battery Charger Instructions included with the unit.)
2.1 BEFORE INITIAL START-UP
NOTE:
These units have been run and tested at the factory prior to
being shipped and do not require any type of break-in.
NOTE:
This unit comes filled with oil from the factory. Check the oil
level and add the appropriate amount if necessary.
Before starting, complete the following:
1. Set the generator’s main circuit breaker to its OFF (or OPEN)
position.
2. Set the generator's AUTO/OFF/MANUAL switch to the OFF
position.
3. Turn OFF all breakers on the load center of the transfer box (T1
and T2).
4. Turn OFF all loads connected to the transfer switch terminals
T1 and T2.
5. Check the engine crankcase oil level and, if necessary, fill to
the dipstick FULL mark with the recommended oil. Do not fill
above the FULL mark.
6. Check the fuel supply. Gaseous fuel lines must have been
properly purged and leak tested in accordance with applicable
fuel-gas codes. All fuel shutoff valves in the fuel supply lines
must be open.
During initial start up only, the generator may exceed the normal
number of start attempts and experience an “over crank” fault (See
the "Overcrank" section). This is due to accumulated air in the fuel
system during installation. Reset the control board and restart up
to two more times, if necessary. If unit fails to start, contact the
local dealer for assistance.
Never operate the engine with the oil level
below the “Add” mark on the dipstick. Doing this
could damage the engine.
2.2 CHECK TRANSFER SWITCH
OPERATION
Refer to the "Manual Transfer Operation" section, of the owner’s
manual for procedures.
DANGER
Do not attempt manual transfer switch operation
until all power voltage supplies to the transfer
switch have been positively turned off. Failure to
turn off all power voltage supplies will result in
extremely hazardous and possibly fatal electri-
cal shock.
2.3 ELECTRICAL CHECKS
Complete electrical checks as follows:
1. Set the generator's main circuit breaker to its OFF (or OPEN)
position.
2. Set the generator's AUTO/OFF/MANUAL switch to the OFF
position.
3. Turn OFF all breakers on the load center of the transfer box (T1
and T2).
4. Turn on the utility power supply to the transfer switch using
the means provided (such as a utility main line circuit break-
er).
DANGER
The transfer switch is now electrically “hot.”
Contact with “hot” parts will result in extremely
hazardous and possibly fatal electrical shock.
Proceed with caution.
5. Use an accurate AC voltmeter to check utility power source
voltage across transfer switch terminals N1 and N2. Nominal
line-to-line voltage should be 240 volts AC.
Section 2 — Post Installation Start-up and Adjustments
Air-cooled Generators
15
6. Check utility power source voltage across terminals N1 and
the transfer switch neutral lug; then across terminal N2 and
neutral. Nominal line-to-neutral voltage should be 120 volts
AC.
7. When certain that utility supply voltage is compatible with
transfer switch and load circuit ratings, turn OFF the utility
power supply to the transfer switch.
8. On the generator panel, set the Auto/Off/ Manual switch to
MANUAL. The engine should crank and start.
9. Let the engine warm up for about five minutes to allow inter-
nal temperatures to stabilize. Then, set the generator’s main
circuit breaker to its ON (or closed) position.
DANGER
Proceed with caution! Generator power voltage
is now supplied to the transfer switch. Contact
with live transfer switch parts will result in dan-
gerous and possibly fatal electrical shock.
10. Connect an accurate AC voltmeter and a frequency meter
across transfer switch terminal lugs E1 and E2. 8kW voltage
should be 230-240 volts at a frequency of 61-63 Hertz. 12,
14, 16, 17 and 20kW voltage should be 247-249 at a fre-
quency of 59.5-60.5 Hertz. 10kW voltage should be 220-230
volts at a frequency of 59.5-60.5 Hertz.
11. Connect the AC voltmeter test leads across terminal lugs E1
and neutral; then across E2 and neutral. In both cases, volt-
age reading should be 121-126 volts AC (8kW), and 125-126
volts AC (10, 12, 14, 16, 17 and 20kW).
12. Set the generator’s main circuit breaker to its OFF (or OPEN)
position. Let the engine run at no-load for a few minutes to
stabilize internal engine generator temperatures.
13. Set the generator's AUTO/OFF/MANUAL switch to OFF. The
engine should shut down.
NOTE:
It is important not to proceed until certain that generator AC
voltage and frequency are correct and within the stated limits.
Generally, if both AC frequency and voltage are high or low,
the engine governor requires adjustment* (*GH410 only). If
frequency is correct, but voltage is high or low, the generator’s
voltage regulator requires adjustment.
2.4 GENERATOR TESTS UNDER LOAD
To test the generator set with electrical loads applied, proceed as
follows:
1. Set generator’s main circuit breaker to its OFF (or OPEN) posi-
tion.
2. Turn OFF all breakers on the load center of the transfer box (T1
and T2).
3. Set the generator's AUTO/OFF/MANUAL switch to OFF.
4. Turn OFF the utility power supply to the transfer switch,
using the means provided (such as a utility main line circuit
breaker).
Do not attempt manual transfer switch operation
until all power voltage supplies to the transfer
switch have been positively turned off. Failure to
turn off all power voltage supplies will result in
extremely hazardous and possibly fatal electri-
cal shock.
5. Manually set the transfer switch to the STANDBY position, i.e.,
load terminals connected to the generator's E1/E2 terminals.
The transfer switch operating lever should be down.
6. Set the generator's AUTO/OFF/MANUAL switch to MANUAL.
The engine should crank and start immediately.
7. Let the engine stabilize and warm up for a few minutes.
8. Set the generator’s main circuit breaker to its ON (or CLOSED)
position. Loads are now powered by the standby generator.
9. Turn ON the load center of the transfer switch (T1 and T2).
10. Connect an accurate AC voltmeter and a frequency meter
across terminal lugs E1 and E2.
8kW voltage should be greater than 230 volts and frequency
should be greater than 58 Hz.
10, 12, 14, 16, 17 and 20kW voltage should be greater than
240 volts and frequency should be 60 Hz.
11. Let the generator run at full rated load for 20-30 minutes.
Listen for unusual noises, vibration or other indications of
abnormal operation. Check for oil leaks, evidence of overheat-
ing, etc.
12. When testing under load is complete, turn OFF electrical
loads.
13. Set the generator's main circuit breaker to its OFF (or OPEN)
position.
14. Let the engine run at no-load for a few minutes.
15. Set the AUTO/OFF/MANUAL switch to OFF. The engine should
shut down.
2.5 CHECKING AUTOMATIC
OPERATION
To check the system for proper automatic operation, proceed as
follows:
1. Set generator’s main circuit breaker to its OFF (or OPEN) posi-
tion.
2. Check that the AUTO/OFF/MANUAL switch is set to OFF.
3. Turn OFF the utility power supply to the transfer switch, using
means provided (such as a utility main line circuit breaker).
4. Manually set the transfer switch to the UTILITY position, i.e.,
load terminals connected to the utility power source side.
5. Turn ON the utility power supply to the transfer switch,
using the means provided (such as a utility main line circuit
breaker).
6. Set the generator's main circuit breaker to its ON (or CLOSED)
position.
7. Set the AUTO/OFF/MANUAL switch to AUTO. The system is
now ready for automatic operation.
Section 2 — Post Installation Start-up and Adjustments
Air-cooled Generators
16
8. Turn OFF the utility power supply to the transfer switch.
With the AUTO/OFF/MANUAL switch at AUTO, the engine should
crank and start when the utility source power is turned OFF after
a 10 second delay. After starting, the transfer switch should
connect load circuits to the standby side after a five (5) second
delay. Let the system go through its entire automatic sequence of
operation.
With the generator running and loads powered by generator AC
output, turn ON the utility power supply to the transfer switch. The
following should occur:
After about 15 seconds, the switch should transfer loads back
to the utility power source.
About one minute after re-transfer, the engine should shut
down.
2.6 ENGINE GOVERNOR ADJUSTMENT
If both AC frequency and voltage are correspondingly high or low,
adjust the engine governor as follows:
2.6.1 8 KW UNITS
The engine must be OFF to perform steps 1 and
2.
1. Loosen the governor clamp bolt (Figure 2.1).
2. Hold the governor lever at its wide open throttle position
(clockwise), and rotate the governor shaft clockwise as far
as it will go. Then, tighten the governor lever clamp bolt to 70
inch-pounds (8 N-m).
3. Start the generator; let it stabilize and warm up at no-load.
4. Connect a frequency meter across the generators AC output
leads.
Figure 2.1 — Engine Governor Adjustment
Single Cylinder Engines
GOVERNOR
SHAFT
PRIMARY
ADJUST
SCREW
GOVERNOR
CLAMP
BOLT
SECONDARY
ADJUST SCREW
5. Turn the primary adjust screw to obtain a frequency reading
of 61.5 Hertz. Turn the secondary adjust screw to obtain a
frequency of 62.5 Hz.
2.6.2 12, 14, 16, 17 & 20KW UNITS
NOTE:
All V-twin units DO NOT require an engine governor adjustment
due to their design.
2.6.3 ADDITIONAL CORROSION
PROTECTION
Periodically spray all engine linkage parts and brackets with corro-
sion inhibiting spray such as WD-40 or a comparable product.
2.7 VOLTAGE REGULATOR
ADJUSTMENT
2.7.1 8 & 10KW UNITS
Due to the brushless design of these two alternators, no voltage
regulator is used and therefore no voltage adjustment is required.
2.7.2 12, 14, 16, 17 & 20KW UNITS
With the frequency between 59.5 -60.5 Hertz at no-load, slowly
turn the slotted potentiometer (Figure 2.2) until line voltage reads
247-249 volts.
Figure 2.2 – Voltage Adjustment Potentiometer
Turn to
adjust voltage.
NOTE:
The access panel on top of the control panel must be removed
to adjust the voltage regulator.
NOTE:
The voltage regulator is housed behind the generator's control
panel. The regulator maintains a voltage in direct proportion to
frequency at a 2-to-1 ratio. For example, at 60 Hertz, line-to-
neutral voltage will be 124 volts.
Section 2 — Post Installation Start-up and Adjustments
Air-cooled Generators
17
Section 3 — Operation
Air-cooled Generators
3.1 CONTROL PANEL INTERFACE
3.1.1 USING THE AUTO/OFF/MANUAL SWITCH
(FIGURES 3.1 & 3.2)
With the switch set to AUTO, the engine may
crank and start at any time without warning.
Such automatic starting occurs when utility
power source voltage droops below a preset
level or during the normal exercise cycle. To
prevent possible injury that might be caused
by such sudden starts, always set the switch to
OFF and remove the fuses before working on or
around the generator or transfer switch. Then,
place a “DO NOT OPERATE” tag on the genera-
tor panel and on the transfer switch.
1. AUTO” Position – Selecting this switch activates fully auto-
matic system operation. It also allows the unit to automati-
cally start and exercise the engine every seven days with the
setting of the exercise timer (see the Setting the Exercise
Timer section).
2. “OFF” Position – This switch position shuts down the engine.
This position also prevents automatic operation.
3. “MANUAL” Position – Set the switch to MANUAL to crank
and start the engine. Transfer to standby power will not occur
unless there is a utility failure.
Figure 3.1 – 8kW Generator Control Panel
SET
EXERCISE
SYSTEM READY
LOW BATTERY
LOW OIL PRESSURE
HIGH OIL TEMPERATURE
OVERSPEED
RPM SENSOR LOSS
OVERCRANK
Figure 3.2 – 10/12/14/16/17 & 20kW Generator
Control Panel
ENTER
ECS
3.1.2 SETTING THE EXERCISE TIMER
This generator is equipped with an exercise timer. Once it is set,
the generator will start and exercise every seven days, on the day
of the week and at the time of day specified. During this exercise
period, the unit runs for approximately 12 minutes and then shuts
down. Transfer of loads to the generator output does not occur
during the exercise cycle unless utility power is lost.
8kW
A switch on the control panel (see Figure 3.1) permits selection of
the day and time for the system to exercise. At the chosen time,
perform the following sequence to select the desired day and time
of day the system will exercise. Remember seasonal time changes
affect the exercise settings.
1. Verify that the AUTO/OFF/MANUAL switch is set to AUTO.
2. Press and hold the “Set Exercise” switch for several seconds.
All the red LED’s will stop flashing immediately and the gen-
erator will start.
3. The generator will start and run for approximately 12 minutes
and then shut down. The exerciser is now set to run at this
time of day each week.
Example: If the “Set Exercise” pressed on Saturday afternoon at
2:00 p.m., the generator will start and exercise for approximately
12 minutes every Saturday at 2:00 p.m.
NOTE:
The exerciser will only work in the AUTO mode and will not work
unless this procedure is performed. The exerciser will need to
be reset every time the 12 volt battery is disconnected and then
reconnected, and when the fuse is removed and/or replaced.
18
10 to 20 KW - INSTALLATION ASSISTANT
Interconnect System Self Test Feature (follow the on-screen
prompts)
Upon power up, this controller will go through a system self test
which will check for the presence of utility voltage on the DC
circuits. This is done to prevent damage if the installer mistakenly
connects AC utility power sense wires into the DC terminal block.
If utility voltage is detected, the controller will display a warning
message and lock out the generator, preventing damage to the
controller. Power to the controller must be removed to clear this
warning.
Utility voltage must be turned on and present at the N1 and N2
terminals inside the generator control panel for this test to be
performed and pass.
NOTE:
DAMAGE CAUSED BY MISWIRING OF THE INTERCONNECT
WIRES IS NOT WARRANTABLE!
This test will be performed each time the controller is powered
up.
Upon first power up of the generator, the display interface will
begin an installation assistant. The assistant will prompt the user
to set the minimum settings to operate. These settings are sim-
ply: Current Date/Time and Exercise Day/Time. The maintenance
intervals will be initialized when the exercise time is entered (Figure
3.2).
The exercise settings can be changed at any time via the "EDIT"
menu (see Appendix, "Menu System").
If the 12 volt battery is disconnected or the fuse removed, the
Installation Assistant will operate upon power restoration. The
only difference is the display will only prompt the customer for the
current Time and Date.
IF THE INSTALLER TESTS THE GENERATOR PRIOR TO
INSTALLATION, PRESS THE “ENTER” KEY TO AVOID SETTING
UP THE EXERCISE TIME. THIS WILL ENSURE THAT WHEN
THE CUSTOMER POWERS UP THE UNIT, HE WILL STILL BE
PROMPTED TO ENTER AN EXERCISE TIME.
NOTE:
The exerciser will only work in the AUTO mode and will not work
unless this procedure is performed. The current date/time will
need to be reset every time the 12 volt battery is disconnected
and then reconnected, and/or when the fuse is removed.
3.1.3 DISPLAY INTERFACE
8 kW LED Display
Seven (7) LED’s are provided for user status indications. The LED
functions are:
1. System Ready (green)
2. Low Battery (red)
3. Low Oil Pressure (red)
4. High Oil Temperature (red)
5. Over Speed (red)
6. RPM Sensor Loss (red)
7. Over Crank (red)
See the Protection Systems section for details.
10 to 20KW DISPLAY INTERFACE MENUS
The LCD display is organized as detailed below:
The “Home” page, this page is the default page which will be
displayed if no keys are pressed for 30 seconds. This page
normally shows the current Status message and the current
date and time. The highest priority active Alarm and/or Warning
will be automatically posted on this page as well as flashing
the backlight when such an event is detected. In the case of
multiple Alarms or Warnings, only the first message will be
displayed. To clear an Alarm or Warning, see the Protection
Systems section - Clear Alarm.
The display backlight is normally off. If the user presses any
key, the backlight will come on automatically and remain on for
30 seconds after the last key was pressed.
The “Main Menu” page will allow the user to navigate to all other
pages or sub-menus by using the Left/Right and Enter keys.
This page can be accessed at any time with several presses of
the dedicated Escape key. Each press of the Escape key takes
you back to the previous menu until the main menu is reached.
This page displays the following options: HISTORY; STATUS;
EDIT; AND DEBUG. (See the Appendix - "Menu System".)
3.2 AUTOMATIC TRANSFER OPERATION
To select automatic operation, do the following:
1. Make sure the transfer switch main contacts are set to their
UTILITY position, i.e., loads connected to the utility power
source (Figure 3.2).
2. Be sure that normal UTILITY power source voltage is avail-
able to transfer switch terminal lugs N1 and N2 (Refer to the
Electrical Data section).
3. Set the generator’s AUTO/OFF/MANUAL switch to AUTO.
4. Set the generator’s main circuit breaker to its ON (or CLOSED)
position.
With the preceding steps complete, the generator will start auto-
matically when utility source voltage drops below a preset level.
After the unit starts, loads are transferred to the standby power
source. Refer to the Sequence of Automatic Operation section.
Section 3 — Operation
Air-cooled Generators
1/82