INSTRUCTION MANUAL
Optima air curtains 04
SECURITY ADVICE SYMBOLS
¡Attention, Danger, Safety advice!
¡Danger from electric current or high voltage!!
¡Injuries risk!
¡Danger! Do not step under hanging load.
Important Information
AIRDOM05032-R2(02/02/06)
AIR CURTAINS
Air curtains are produced in accordance with the latest technical standards. Our quality assurance program
includes material controls and function tests in every steep of the process to obtain a high quality and reliable
final product with a long trouble-free life.
Air curtains are ideal for controlling the interior ambient of industrial and commercial premises that need to
maintain the doors open. Air curtains create a laminar air stream over the opening doorway and acts as an
invisible barrier which efficiently divides the interior ambient from the exterior; reduce heating and cooling
cost meanwhile increasing the employees and clients comfort. They contribute to a comfortable climate in the
entrances and interior of the premises, protect from the cold and the heat, repel gust of wind and minimize
the entrance of airborne dust, fumes, pollutants and flies.
The casing is made of zinc plated sheet steel finished in epoxi-polyester white, RAL 9016, as standard.
Microdrilled suction grill with washable dust filter functions. Aluminum blow-out nozzle, airfoil-like profiled. .
Optima models are equipped with direct drive external rotor motor of extremely low noise level, 100% speed
controllable, protected through thermal contact and directly connected to the tangential impeller.
High efficiency impeller statically and dynamically balanced according to DIN/ISO 1940, quality 2,5.
Water coils are available for pumped warm water 80/60ºC. The tested pressure is of 8 bars.
Electric heating coils are protected against overheat through thermal contacts and sensors and when the air
curtain is switched off, the fans continue working until the unit has cooled sufficiently. Electrical power supply
box and “plug and play” control connector plate are placed on top of the unit and makes unnecessary to open
the service door.
The communication between the air and heating control panel is digital through low-voltage cable with
telephone plugs (RJ45). Prepared for all kinds of accessories (thermostatic valves, room thermostats, door
contact, automatic controllers, anti-frost protectors, etc…).
WORKING CONDITIONS
Air curtains are designed for use with ambient air, pumped warm water or electric heat.
The standard heated versions are equipped with an electric heater or water coils of 80/60ºC or 60/40ºC
In order to avoid overheating in the motors and internal elements, the water circulation valve must be closed
while the air curtain is turned off. The ambient temperature should always be over +4ºC. For lower
temperatures the unit must be protected with anti-freeze thermostat.
The suction temperature shouldn’t be over 40ºC. The discharge air temperature shouldn’t be over 50ºC.
TRANSPORT AND STORAGE
Attention! Heavy load.
Do not steep under hanging load during the transport or assembly.
When carrying material, make sure it is not damaged by the forklift (fork penetration in the packaging).
Please observe the packaging instructions.
Store in dry place and weather protected in its original packing. Cover opened boxes with a tarpaulin and
protect the unit against the influence of dirt.
Don’t put heavy loads or steep on over the packed unit and avoid distortion of casing or other damages.
Storage temperatures are between -20ºC and +40ºC.
CHARACTERISTICS
Self-supporting housing made of galvanised steel, painted
epoxi-polyester structural white colour RAL 9016.
Cross-flow fans furnished with 2 speed external rotor motor.
Frontal micro-perforated inlet grille with regenerable filter
functions for easy use. No intensive filter servicing is
necessary.
"P" types include water coils. "E" types include electrical
shielded batteries, 2 power steeps with power switches
included. "A" types are without heating, air only.
Linear blow-out jets with aluminium anodised air controlled
lamella adjust, type airfoil.
Controller and regulation included.
SPECIFICATIONS
Optima
1000 A
Optima
1000 P
Optima
1000 E
Optima
1500 A
Optima
1500 P
Optima
1500 E
Power fan W 45/80 45/80 45/80 61/112 61/112 61/112
Current A 0,23/0,37 0,23/0,37 0,23/0,37 0,33/0,55 0,33/0,55 0,33/0,55
Voltage V 230~1 230~1 230~1 230~1 230~1 230~1
Speed r.p.m. 1.350 1.350 1.350 1.300 1.300 1.300
Air flow min./máx. m
3
/h 750/1.100 750/1.100 750/1.100 1.100/1.600 1.100/1.600 1.100/1.600
Power heating kW - 6,95 4/6 - 10,15 6/9
Voltage* V - - 400~3 - - 400~3
Strength 400V A - - 4,7/7,9 - - 6,8/13,4
Temperature rise. ºC - 11/15 11/15 - 11,5/16,5 11,5/16,5
Weight Kg 17 21 20 22 28 26
Noise level dB(A) 41/50 41/50 41/50 43/52 43/52 43/52
Maximum height ** m 2,2 2,2 2,2 2,2 2,2 2,2
(*) “E” models available with electrical heating coil 230V single phase.
(**) Depending on conditions of installation
DIMENSIONS
Optima
1000 A
Optima
1000 P
Optima
1000 E
Optima
1500 A
Optima
1500 P
Optima
1500 E
A mm 1000 1000 1000 1500 1500 1500
B mm 940 940 940 1440 1440 1440
MOUNTING INSTRUCTIONS
Installation work, electrical wiring, mechanical maintenance and service must be done by
qualified persons observing these instructions and in accordance with all applicable
norms and standards.
Each unit should be able to be disconnected according to the applied norms. If the unit
is operated with additional controller, please consider the instructions of operation
manual of controller.
For all electrical connections there is no need to open the service door. All necessary
connections are external and placed on the top of the unit.
Power supply
The connection of the power supply is made on the top-external part of the air curtain.
For an ambient air or water heated air curtain, only single phase 230V is needed. In case of an electric air
curtain you must connect both single (230V) and three-phase (380V) in white connection box.
Junction box for air only and water heated air
curtains: Terminals L, N, (230V) and Earth.
Junction box: terminals 2, 3, 4 (three-phase) for
electrical heating and L, N, (230V) and Earth for
fans.
Control connector plate
To connect the controller there is a plate located on the top of the unit. The communication between the
connector plate and the controller is digital through low-voltage cable with telephone plugs (RJ45). This
cable, 20m length, is included with the air curtain.
There are two types of connections: for water air curtains or only air with the telephone plugs and the green
terminal plate for the electric valve (photo on left) and for electric air curtains with telephone plugs and the
black connection box (photo on the right).
Ceiling or wall mounting
Units are provided with 4 suspension points (M8) located on the top of the unit and also 4 threaded ones at
the back of the unit (M8). This way there can be used ones or others depending on the installation (in-
ceilining mounting or wall-mounting). The exact situation of the fixation points is reflected in the curtain
dimensions paragraph.
A minimum of 150mm is recommended above de top of the unit to allow for wiring to power supply junction
box, connectors plate and service. The curtains should be assembled in the ceiling using threaded rods,
tensors, wall mounting brackets and other supports.
The anchor should be managed according to each unit weight shown on the technical data page.
Fixation angles can be supplied as described in the accessories paragraph.
Warm water heat exchangers
Two thread connectors of ½” inches are external and placed on the top of the unit.
It is recommended to install 2 shut-off water valves (supply and return) in order to close the circuit and avoid
water leakage during coil maintenance or repair.
In addition, it’s also recommended to install a draining point in the highest part of the heating water circuit.
When required, install a secondary pump in order to increase the efficiency of the thermal exchange.
Electrical heat exchanger
The electrical heat exchanger is already connected.
The part of maneuver works with 230V and the power with 400V three phase current. The heat exchanger
has 3 resistances in bar form that combined among them they give us 2 stages of power. The first stage
provide us 2/3 of the total power and the second one the maximum power.
All electrical heat exchangers are protected against overheats. They have a security that rearms automatic
when the temperature it’s over 50ºC and another with manual rearms for temperatures over 80ºC that blocks
only the electrical heat exchanger. Also, in case we turn off the air curtain and the temperature exceeds of
50ºC, the air curtain will start the fans until the temperature descends of this degrees.
The electric controllers have the option of external thermostat that turns on and off the heater in order to
control the temperature.
During the first uses it usually removes scent but it disappears in a few days.
Air curtains schemes connection
Following wiring diagrams are enclosed:
Only air and warm water air curtain.
Electric heating air curtain.
For connecting the air curtain to a PLC, the systems scheme would be supplied.
For connecting the air curtains in series with only one controller:
Connector plate with auxiliary output
To
controller
To next
curtain
ACCESSORIES
Connection cable
: Supplied in lengths of 20 (standard) or 50 meters (optional). It is a telephone cable of 8
lines with crossed connections assembled like this:
Connector RJ45 Phone cable 8 lines Connector RJ45
(Tongue facing up) (Unfolded plane) (Tongue facing up)
Extensión Adapter
(A): Two female connectors to
enlarges the cable between the air curtain and the
controller (not included)
Vibration absorbers
: ceiling fixation angles with
rubber vibration isolations (not included)
Wall support: For wall fixing.
WORKING INSTRUCTIONS
For security, the air curtains must always be stopped through the controller. Never stop
the air curtain disconnecting the main electricity supply.
We enclose wiring diagrams of air curtains with the corresponding controllers.
Connector plate characteristics:
(placed on top of the unit)
Relays and transformer: It adjusts the fan speed through voltage variation by transformer so we have a
high and medium speed.
Controller’s common characteristics:
Two speed air discharge.
Memory: Guarantees that in the event of a power shortage, the selected speed will be maintained
when the service is re-established.
Telephone cable and digital communication: “Plug and play” easy connection through telephone
cable and digital communication between the controller and the air curtain. Digital communication is
more reliable than analog, even at long distances.
External ON/OFF: Inside the controller there is potential free contact (normally open) for remote
ON/OFF by any other external device. The most common uses are, for example, the connection with
programmable clock timer, room thermostats, door contact, DDC, fire alarms, etc…
Water heating controller
Electrical controller’s common characteristics:
Two speed systems that adjust air volume and two different heat powers (C1, C2).
Thermal Limitation: Due to its special design, the only thermal limitation of this equipment is that, to
work the heating, there must be any speed selected, what allow us to choose the maximum heating
capacity with the minimum ventilation.
Thermostat of delay: When the equipment is stopped, and it has been working, the electrical
heater is still heating during several minutes by thermal inertia with the consequent increase of
temperature. In order to avoid internal damages by overheating, there is a delay thermostat settled at
50ºC having the function to keep running or turn on again the fans automatically until the temperature
inside the equipment goes under 50ºC.When done, the fans stop automatically. The emergency
speed is indicated by a flashing green LED
Safety thermostat: Thanks to this security system the heating won’t stop for an external temporally
reason and only will turn on against a real failure. For example, a delay in cleaning the inlet grill o a
high external temperature would be an external temporally reason. Instead, the motor damage could
be a failure capable of blocking the heating system.
If the internal temperature increases up to 50ºC the air curtain reacts increasing steep by steep the
fan speed until the temperatures goes under 50ºC. If the air curtain reaches the maximum speed and
the temperature inside is still over 50ºC, the air curtain automatically reduce the heating power steep
by steep until OFF position if necessary.
The air curtain returns automatically to the programmed fan speed and heat step if the temporally
failure cause disappears and the internal temperature decreases to 40ºC.
The programmed speed and heat are indicated by lighted green LED’s. The emergency speed is
indicated by a flashing green LED. The emergency heat disconnection in indicated by a red LED
“OFF”. The heat blockage is indicated by the same red LED “OFF” flashing at higher speed. In this
situation manual reset is needed.
Auxiliary functions controller:
In case of thermostat installation, the bridge must be removed from the inside of the controller between
Terminal 4 and 5.
Optional room thermostat: The curtain is equipped with the necessary contacts (4 and 5 terminal
block) to install a room thermostat for ON/OFF control of the heating elements that turns off when
reaching the temperature programmed. Installation of room thermostat is recommended when the air
curtain is installed in a small dimensions area or when the air curtain is used also as a heating element of
the premise. In case of the thermostat installation, the bridge inside the terminal 4 and 5 must be
removed.
MAINTENANCE INSTRUCTIONS
Air curtains don’t need any kind of maintenance except the cleaning the casing (inside and outside)
and the inlet grill.
The inlet grill has also filter functions to prevent dust settling in the internal elements. For an optimal
function is essential to clean the inlet grill regularly, we recommend every two weeks (depending on amount
of the incoming air dust). The cleaning can be easily done with a vacuum cleaner with a soft brush in order to
avoid damages in the micro drilled grill.
The casing of the air curtain can be cleaned with a wet cloth and non aggressive detergent. Don’t use
caustic soap, dissolvent or acids.(surface protection will be destroyed)
Don’t use water or steam for cleaning the internal parts and components of the air
curtain.
It is forbidden to open the service door in operation (risk of electrical
discharge and being trapped in fans).
Service and maintenance should be done only by skilled and
introduced workers.
REPAIRS
ı
Service and maintenance should be done only by skilled and introduced workers observing
these instructions:
Before any repairs are undertaking, please:
Advice people that there is work in progress.
Stop the air curtain through the controller and disconnect main supply.
Make sure that nobody can restart it accidentally (protect the thermal magnet).
Make sure there is no tension in the curtain.
Wait until the fans are stationary.
Use only original spare parts.
To open the service door, follow these steps:
1. Remove the lateral cover
2. Lever smoothly between the grid and the door
Motor or turbine replacement:
Before the motor replacement, advise people that there is work in progress,
Disconnect main supply, make sure that the unit is without tension and that the fans are stationary.
Next release the motor connector. Loosen the fixing screw to the turbine (allen 2.5 mm.) through the
discharge opening.
Remove motor loosening the fixation screws. Install the replacement motor following the process in reverse
order, making sure that the motor and the turbine fit perfectly, the turbine screw must fit in with the flat part of
the motor axle
Fuse and PCB (plate) replacement:
Before the replacement, advise people that there is work in
progress,
Disconnect main supply, make sure that the unit is without
tension and that the fans are stationary.
Fuse replacement: Open the service door and remove
the fuse from the fuse holder by hand or pulling with
screwdriver and replace.
Plate replacement: Open the service door and
unplug the visible cables from the plate and the
condenser.
Unscrew the power plate through the upper external
part of the air curtain to remove the plate and unplug the
internal cable (Just for electrical heating version) before
removing and then make the necessary reparation.
Heat exchanger replacement:
Before opening the service door, advise people that there is work in progress, stop the air curtain through the
controller and disconnect main supply. Make sure that the unit is without tension and the fans are stationary.
Before removing the screws that are fixed to the batteries, we must:
Water coil replacement:
Close the shut-off water valves of the building water circuit to the air curtain (supply and return). Open the
service door and drain the water from the coil simply removing the draining screw placed in the bottom of the
entrance manifold.
Electric heater replacement: With power supply disconnected, unplug the heater connectors from the plate
and junction box, remove the fixation screws, disassemble the heater and assemble the new heater following
the same process in reverse order.
Unplug cables 2, 3, 4 in the junction box Unplug the two connectors of plate pressing the fluke.
How to remove the electric heating or the water coils.
When we have the coil or heater ready, we proceed to remove the fixation screws of the inlet grill and the
screws of the battery to disassemble the coil or heater and assemble the new heater following the same
process in reverse order.
Then, for both heaters you can take it out carefully in the direction showed in the photo, with your hands
protected.
Air curtain identification:
Each air curtain is identified by a unique serial number printed in
a label located inside the door service.
There is also indicated the model and their technical
characteristics (flow, fans technical characteristics and power
heating)
It is indispensable to have this number to facilitate possible
replacements or technical information of the air curtain in
question
GUARANTEE
Your air curtain is guaranteed for a period of one year from the date of purchase. We will adjust, repair or
replace at our discretion from our warehouse any defect, system failure or part found to be defective. The
assembly cost out of our warehouse is at buyer expense. The products that, in our eyes, have been
inadequately used, incorrectly manipulated, improperly installed, connected to different nominal tensions,
modified, repaired by non-authorized workers or that have suffered damages during transport are totally
excluded from the guarantee.
To validate the guarantee it should be correctly filled and enclosed with the invoice that vouches for the buying date. If it is manipulated,
it will lose all validity.
It is the buyer’s responsibility to take the necessary safety measures because in case of a failure or mistake in one of one our products,
no damages to third parties, sets or installations will occur.
Guarantee draft
Air curtains data:
Model : ............................................... Series number......................................................
Invoice date: ............................ Invoice number:......................................................
Buyer data:
Name: .............................................................................................................................................................
Address: ...........................................................................................................................................................
:………………………… Phone:......................................... Fax: ........................................................
Seller data:
Name: .............................................................................................................................................................
Address: ...........................................................................................................................................................
Country: ………………………… Phone:......................................... Fax:
........................................................
Buyer signature and stamp
Seller signature and stamp
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Optima 1000 P User manual

Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI