Specicationssubjecttochangewithoutnotice.
©Nottobereproducedwithoutpermission.
Unit6,691GardenersRoadMascot2020Australia.
ABN33097246921
PPS640-KNX Installation Manual
Rev A March 2012
PPS640-KNX
Network Power Supply
INSTALLATIONMANUAL
Warranty Policy
Philipswarranttotheoriginalpurchaserforaperiodoftwentyfour(24)monthsfromthedateofshipmentex-factoryoftheequipmentthatshouldtheequipmentprovedefectiveby
reasonofimproperworkmanshipormaterial,Philipswillrepairorreplacethesamewithoutchargeprovidedtheequipmenthasnotbeenimproperlyinstalled,operated,repaired,damaged
orabused.Thewarrantygrantedhereinislimitedtorepairorreplacementonly.Philipshastherighttosubstituteanywarrantyitemnotonthecurrentprice/equipmentlist.Asfarasthelaw
permits,Philipsshallnotbeliableforanylossordamagecausedtopropertyorpersonsarisingfromanycausewhatsoever.ThiswarrantyissubjecttothereturnoftheequipmenttoPhilips,
orthePhilipsauthoriseddistributorwhosuppliedtheequipment(the‘Supplier’),byprepaidfreightwithinthetwentyfour(24)monthswarrantyperiod.WherePhilips,ortheSupplier,agree
toasitevisitduringthewarrantyperiodanditisfoundtobeanoperationalproblem,andnotsubjecttowarrantyinthatevent,thenaeldservicecalloutchargewillapply.ContactPhilips
ortheSupplierfordetails.
Connecting KNX Data Cabling
ConnectDataCableinaDaisyChain
KNXBusPermanentConnections
Installation Steps
1. MountthedeviceonaDINrailinsideanapproved
enclosure.
2. Connectasinglephasefeedtothesupplyterminals.
Thisdevicemustbeearthed.
3. ConnectKNXTP
1
buscables.Ensurecorrectcable
typeandlengths.Ensurerequiredcablesegregationto
othercircuits.
4. ConnectAuxSupplycablesifrequired.Ensurecorrect
polarityandrequiredsegregationtoothercircuits.
5. Re-checkallterminationspriortoenergizingand
energizethesupply.
6. Checksupply,KNXbusvoltageandAuxsupplyusing
amultimeter.Loadsupplyshallbewithintheload
specication,KNXbusshallbebetween21-30Vdc,
Auxsupplyshallbebetween24-30Vdc.
Product Specications
Supply
120-250V50/60Hzat0.5A
Output
640mA@29VdcfordirectKNXBUSsupply
Protection
Overloadprotection
Shortcircuitproof
Supply Terminals
Line,Neutral,EarthScrewTerminal
1x1.5mm
2
maxconductorsize
Output Terminals
Wago243(Red/Grey)forKNXBus
Wago243(Yellow/White)forauxiliarysupply
0.6-0.8mmwirediametersinglecoreKNXcable
Compliance
CE,KNX
Operating Environment
-5°to45°Cambienttemperature
0%to90%RHnoncondensing
Construction
Plasticenclosure
Dimensions
6Pole:H107mmxW91mmxD62mm