Agni AGNI-202 User manual

  • Hello! I am an AI chatbot trained to assist you with the Agni AGNI-202 User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
CONVENTIONAL SMOKE DETECTOR
AGNI-202
'AGNI’ CONVENTIONAL OPTICAL SMOKE
DETECTOR uses an optical sensing
chamber to detect smoke, which responds
quickly and reliably to a wide range of fire
types. The Detector is highly sensitive and
responsive to different types of smoke
patterns. It does not operate without
electrical power. The device is incorporated
with a pulsing LED located within the
detector chamber which shows its status.
Manufactured in line with EN54 Part 7
European Standard and ideal to support the
modern construction designs. It is capable
of performing comprehensive self
diagnostics and storing results. The detector
has algorithm map for faster
response which provides digital signaling
through intelligent 32 Bit processors
provided therein. When there is smoke
/increase of smoke due to rapid fire, the
integral microprocessor analysis the signal
and enables the detector to switch over to
alarm mode invoking the fire alarm. The
detector base features twist and lock
detector installation.
Features.....
?Easy installation and maintenance
?Sleek low-profile housing design.
?Algorithm map for faster detection and
discrimination
?Algorithm map for false alarm rejection
?Built-in 32 Bit Microprocessor
?Built-in Remote Indicator output
?EN54compliance
?LED for 360° visibility
?Sensing chamber for dust proof ability
?To ensure constant sensitivity provision of
drift compensation.
TECHNICAL DATA SHEET
PARAMETER DATA
Agni Instruments Engineers (I) Pvt. Ltd.
Agni-202
58°C
10mA i 30mA
(2s Min, 2.5VDC Max)
-10°C ~ +50°C
Dia : 100mm; H : 41.8mm (w/o base)
Red Flashes periodically (2s~4s) in polling,
illuminates in alarming.
IP-23
2V (peak-to-peak)
ABS ; White
45mm ~ 75mm
9VDC-34VDC
s10s
95% non condensing
Directly connecting with remote indicator
(built-in 2k resistor In series. Output
voltage 5V). Do not illuminate when
in polling. Illuminate in alarming.
3°C/min.
60 ì a
1. Make
2. Model
3. Action Temperature
4. Alarm Current
5. Alarm Reset Instantaneous Cut out
6. Ambiant Temp.
7. Dimension
9. Fire LED:
10. Ingress Protection Rating
11. Maximum Ripple Voltage
12. Material and color of enclosure
13. Mounting hole spacing
14. Operating Voltage
15. Power-up Time
16. Relative Humidity
17. Remote Indication Output
18. Response Velocity
19. Standby Current
20. Weight
21. Wiring:
about 120 g
Two-wire ; Polarity sensitive
Y-51, OKHLA INDUSTRIAL AREA PAHSE.-II NEW DELHI 110020 (INDIA)
L1
I
N
R
1
L2
L
1
I
N
R
1
L
2
L
1
I
N
R
1
L2
END OF LINE DEVICE
REMOTE
INDICATOR
FACP
+VE
-VE
L1
I
N
R
1
L
2
L1
I
N
R
1
L2
L1 I
N
R
1
L
2
END OF LINE DEVICE
COM. REMOTE
INDICATOR
FACP
+VE
-VE
Schematic Wiring Diagram of AGNI-205 (Base) Monitored Detector Circuit With Remote Indicator.
Schematic Wiring Diagram of (Base) Monitored Detector Circuit With Common Remote Indicator. AGNI-205
WIRING DIAGRAM
COMPATIBILITY
DETECTOR BASE
INSTALLATION
AGNI Conventional Smoke Detector are compatible with all type of Conventional Semi
Addressable and Addressable (using module) Fire Alarm Control Panels.
The AGNI-205 Base made of ABS Plastic, is a conductive base. It has one way locking
mechanism with the detector. The flame class is V-0, The base is required to be fixed before
connecting cables and mounting of Detector.
Technical Specification:-
Operating Temperature (Environmental) : 10C + 50C
Relative Humidity : <95% No condensation
Height : 16mm
Diameter : 100mm
Colour : White
Material : ABS
?As the detector dose not operate without electrical power, it is advised to check regularly and
ensure that there is no interruption of power supply to the device.
?The detector should be stored within the recommended range and allowed to stabilize to
room temperature before applying power for successful operation.
?Installation of the device should be carried out as described in the installation sheet.
?Detector should be installed in compliance with Bs5389 Part 1 and En54.
?check the wiring and fix the base of the detector firm to the roof/wall.
?Fix the detector in the base by the mark-line and rotate the detector clockwise until it reaches
the locked position and ensure that it is tightly fixed to the base.
?Till completion of installation, do not remover the red plastic dust cover.
?Calibration sensitivity test per NFPA code is required to be carried out once the installation of
device is complete.
Y-51, OKHLA INDUSTRIAL AREA PAHSE.-II NEW DELHI 110020 (INDIA)
/