EPH Controls FF81 – FF84, FF84 Operating instructions

  • Hello! I am an AI chatbot trained to assist you with the EPH Controls FF81 – FF84 Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
FLOW SWITCHES FF81 for pipes from G1 to G4
FF84 for pipes from G1 to G10 FF81-FF84
FANTINI COSMI S.p.A.
Via dell’Osio, 6 20090 Caleppio di Settala, Milano
ITALY - Ph. +39 02 956821 - Fax +39 02 95307006
info@fantinicosmi.it
EXPORT DPT: Ph. +39 02 95682229
export@fantinicosmi.it
GENERALCHARACTERISTICS
Flow switches are suitable to control and adjust air in conditioning.
FUNCTIONING AND INSTALLATION
A flexible paddle works on a lever starting a microswitch in SPDT. The electrical
connection can be prearranged to control pumps, burnes, compressors,
motoroperated valve, signalling alarms.
It is installed on sections of horizontal pipe, far from valves, elbows, irregular
flows or discharges.
The straight pipe must be at least 5 times of the long of the of the pipe. The
flow direction must follow the arrow designed on the instrument. Check the
correct installation and the correct functioning, pretending the flow inside the
pipe manually pushing the lever untill you close the C-NO contact. Then check
the opening of the contact.
ON PIPELINES G1 ON PIPELINES FROM G2 TO G10
TECHNICAL CHARACTERISTICS
FF81: with shock-resistant enclosure, protection degree IP54, sealedgland
in nylon G 3/8”, lever group from G1” to G4” (the G1” and G2” levers are already
mounted).
FF84: with a inox enclosure, protection degree IP54, sealed-gland in nickel-
plated brass G 3/8”, lever group from G1” to G10” already mounted).
TECHNICAL CHARACTERISTICS OF BOTH MODELS
Lever group for pipelines in inox AISI 301.
G1” connection.
Electrical connections on 6.3 Faston (on issue).
Calibration screw for the regulation of the intervention point.
Max. temperature of the controlled fluid 110 °C.
Working temperature -20 to 70 °C.
SPDT microswitch.
Conformity with CEI EN 60947-5-1
Pipeline
diameter
Minimum Calibration
value (dm³/sec) with
Max Calibration
value (dm³/sec)
Brass
threaded
connection
Max.
working
pressure
Protection
degree
Unit
weight
increasing
flow
decreasing
flow
increasing
flow
decreasing
flow
FF84
FF81
G 1 0,26 0,16 0,58 0,53
G1” 10 bar
IP54
0,39
G 2 0,8 0,6 1,6 1,7 IP54
G 3 1,7 1,2 3,2 3 IP54
G 4 2,2 1,7 5,1 4,8 IP54
G 6 4,7 3,4 9 8,5
G1” 10 bar
IP54
0,67G 8 12,9 10,7 26 25,2 IP54
G 10 26,5 22 43,5 41 IP54
We reserve the right to make any necessary technical modifications without advanced notice 2014/10 GB79080C
english
AB
28G1
C
5638
D
L1...L10
L6
L4
L3
L2
L1
L8
L10
Dimensions (mm)
Nominal insulation tension Ui 380V~
Continuous duty nominal current Ith 10A
Operating nominal current Ie: 220V- 250V~
Resistive load AC-12 - 10A
Inductive load AC-15 - 3A
Direct current DC-13 0,2A -
Flow directions
Earth screw
Cable gland G 3/8
Adjusting screw
Level for manual control
FF81 FF84
A 105 98
B 62 54
C 80 72
D 204 354
L1 28
L2 53
L3 78
L4 103
L6 153
L8 203
L10 253
Flow increases open C-NC close C-NO
Flow decreases close C-NC opene C-NO
AB
28G1
C
5638
D
L1...L10
L6
L4
L3
L2
L1
L8
L10
/