Omega EIS-2 and EIS-2-RJ Owner's manual

Category
Networking
Type
Owner's manual
USA
MADE IN
Industrial
MMiiccrrooSSeerrvveerr
EIS-2B
Operators Manual
Users Guide
www.omega.com
iSeries info:
www.omega.com/specs/iseries
®
®
Shop on line at
TM
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply.
OMEGA is constantly pursuing certification of its products to the European New Approach Directives. OMEGA will add the CE mark
to every appropriate device upon certification.
The information contained in this document is believed to be correct, but OMEGA Engineering, Inc. accepts no liability for any
errors it contains, and reserves the right to alter specifications without notice.
WARNING: These products are not designed for use in, and should not be used for, patient-connected applications.
!
This device is marked with the international caution symbol. It is important to read the Setup Guide before installing or
commissioning this device as the guide contains important information relating to safety and EMC.
Servicing North America:
USA: One Omega Drive, P.O. Box 4047
ISO 9001 Certified Stamford CT 06907-0047
TEL: (203) 359-1660 FAX: (203) 359-7700
Canada: 976 Bergar
Laval (Quebec) H7L 5A1
TEL: (514) 856-6928 FAX: (514) 856-6886
For immediate technical or application assistance:
USA and Canada: Sales Service: 1-800-826-6342 / 1-800-TC-OMEGA
®
Customer Service: 1-800-622-2378 / 1-800-622-BEST
®
Engineering Service: 1-800-872-9436 / 1-800-USA-WHEN
®
Mexico and TEL: (001)800-TC-OMEGA
®
FAX: (001) 203-359-7807
Latin America: En Español: (001) 203-359-7803
Servicing Europe:
Benelux: Postbus 8034, 1180 LA Amstelveen, The Netherlands
TEL: +31 20 3472121 FAX: +31 20 6434643
Toll Free in Benelux: 0800 0993344
Czech Republic: Frystatska 184, 733 01 Karviná
TEL: +420 59 6311899 FAX: +420 59 6311114
France: 11, rue Jacques Cartier, 78280 Guyancourt
TEL: +33 1 61 37 29 00 FAX: +33 1 30 57 54 27
Toll Free in France: 0800 466 342
Germany/Austria: Daimlerstrasse 26, D-75392 Deckenpfronn, Germany
TEL: +49 7056 9398-0 FAX: +49 7056 9398-29
Toll Free in Germany: 0800 639 7678
United Kingdom: One Omega Drive
ISO 9002 Certified River Bend Technology Centre
Northbank, Irlam Manchester M44 5BD United Kingdom
TEL: +44 161 777 6611 FAX: +44 161 777 6622
Toll Free in England: 0800 488 488
OMEGAnet
®
On-Line Service
www.omega.com
Internet e-mail
®
®
TABLE OF CONTENTS
Part 1: Introduction ..................................................................................................................2
1.1 Safety and EMC Considerations...........................................................................2
1.2 Before You Begin ...................................................................................................2
1.3 Description .............................................................................................................3
Part 2: Hardware ..................................................................................................................4
2.1a Mounting on a DIN Rail..........................................................................................4
2.1b Removal from a DIN Rail .......................................................................................4
2.2 DIP Switches...........................................................................................................5
2.3 Parts of iServer Unit ..............................................................................................5
2.4 Serial Communication Interfaces ........................................................................6
2.4.1 Wiring RS232 Interface ..........................................................................7
2.4.2 Wiring RS485 Interface ..........................................................................8
2.5 Network Communication Interfaces ....................................................................8
2.5.1 10Base-T RJ-45 Pinout ...........................................................................8
2.5.2 10Base-T Crossover Wiring ...................................................................8
Part 3: Network Configuration............................................................................................................7
3.1 Network Protocols ................................................................................................9
3.2 Ethernet (MAC) Address .......................................................................................9
3.3 DHCP ...............................................................................................................10
3.4 DNS ...............................................................................................................10
3.5 IP Address ............................................................................................................11
3.5.1 Default IP Address.................................................................................11
3.6 Port Number..........................................................................................................11
Part 4: Operations ................................................................................................................12
4.1 iCONNECT Software ...........................................................................................13
4.2 Setup and Operation using the iServer Web Page ..........................................14
4.2.1 Read Devices ........................................................................................15
4.2.2 Send Raw Command.............................................................................15
4.2.3 Modify Device List Entry.......................................................................16
4.2.4 Configuration.........................................................................................17
4.2.5 Configure Access Control ...................................................................19
4.2.6 Change ID...............................................................................................20
4.3 Setting a New IP Address using the Serial Port ...............................................21
4.4 Setting a New IP Address over the Network .....................................................23
4.5 Terminal Server Function ...................................................................................24
4.6 Telnet Setup .........................................................................................................25
4.7 HTTPGET Program...............................................................................................27
4.8 ARP Protocol ........................................................................................................28
4.9 Remote Access (Tunneling) ................................................................................29
4.9.1 Remote iServer ......................................................................................30
4.9.2 Local iServer .........................................................................................31
4.9.2 Tunneling Troubleshooting .................................................................32
4.10 iPORT, COM Port Redirector ...............................................................................32
4.10.1 Overview ................................................................................................32
4.10.2 Configurations.......................................................................................33
4.11 Mail Notifier Software ..........................................................................................35
4.11.1 Installation .............................................................................................35
4.11.2 Program Options Setup and Configuration .......................................36
4.11.3 Device Setting Setup and Configuration.............................................37
Part 5: Specifications ...................................................................................................................... 38
Part 6: Factory Preset Values ..........................................................................................................39
Appendix A Glossary................................................................................................................40
Appendix B IP Address ...........................................................................................................41
Appendix C IP Netmask............................................................................................................42
Appendix D ASCII Chart ..........................................................................................................43
ASCII Chart Control Codes ................................................................................44
Part 7: Approvals Information
7.1 Electromagnetic Compatibility (EMC) ...............................................................45
7.2 FCC ................................................................................................................45
i
LIST OF FIGURES:
Figure 1.1 Accessing devices over the Ethernet ...............................................................3
Figure 2.1a Mounting .............................................................................................................4
Figure 2.1b Removal ..............................................................................................................4
Figure 2.2 DIP Switches........................................................................................................5
Figure 2.3 Parts of iServer Unit............................................................................................5
Figure 2.4 DB9 Connector ....................................................................................................6
Figure 2.5 Multi-point, Half-Duplex RS485 Wiring..............................................................7
Figure 2.6 RJ45 Pinout ........................................................................................................8
Figure 2.7 10Base-T Crossover Cable Wiring ...................................................................8
Figure 3.1 Labeling ..............................................................................................................9
Figure 3.2 DIP Switch on Bottom Side of Case ................................................................10
Figure 4.1 Pinging eis03ec MS-DOS Prompt ...................................................................12
Figure 4.2 Assigning an IP Address using iCONNECT ...................................................13
Figure 4.3 Accessing the iServer for Configuration ........................................................13
Figure 4.4 Device Type Menu ............................................................................................14
Figure 4.5 iServer Home Page Menu ................................................................................14
Figure 4.6 Read Devices Menu .........................................................................................15
Figure 4.7 Login Password ...............................................................................................15
Figure 4.8 Serial Device Query Menu ...............................................................................15
Figure 4.9 Device Setup Menu ..........................................................................................16
Figure 4.10 Modify Device List Menu .................................................................................16
Figure 4.11 Configuration Menu .........................................................................................17
Figure 4.12 Access Control Menu ......................................................................................19
Figure 4.13 Change ID Menu ...............................................................................................21
Figure 4.14 DIP Switch #1 shown in “ON” Position...........................................................21
Figure 4.15 Setting the IP address via the Serial Port .......................................................21
Figure 4.16 Pinging 128.100.101.70 from the MS-DOS Prompt ........................................22
Figure 4.17 Access Control Menu ......................................................................................23
Figure 4.18 Terminal Server Configuration ........................................................................24
Figure 4.19 Tera Term Telnet Connection Screen .............................................................25
Figure 4.20 Telnet Setup Menu - iServer Configuration Page ..........................................25
Figure 4.21 Telnet Setup Menu - iServer Help Page ..........................................................26
Figure 4.22 ARP Commands and Responses ...................................................................28
Figure 4.23 Serial Tunneling ................................................................................................29
Figure 4.24 Device-to-Device Communication ...................................................................29
Figure 4.25 Configuration Menu - Remote iServer.............................................................30
Figure 4.26 Configuration Menu - Local iServer ................................................................31
Figure 4.27 iPORT Main Window .........................................................................................32
Figure 4.28 Redirect Serial Connection ..............................................................................32
Figure 4.29 iPORT Main Window .........................................................................................34
Figure 4.30 COM Port Window.............................................................................................34
Figure 4.31 iServer Mail Notifier Main Window ..................................................................35
Figure 4.32 iServer Mail Notifier Profile Setup ...................................................................36
Figure 4.33 iServer Mail Notifier Device Setting ................................................................37
LIST OF TABLES:
Table 2.1 Parts of iServer Unit ...........................................................................................5
Table 2.2 Communication Interfaces - RS232 and RS485 ..............................................6
Table 2.3 Signals and Directions of DB9 ..........................................................................6
Table 2.4 RS485 Half-Duplex Hookup ...............................................................................7
ii
NOTES, WARNINGS and CAUTIONS
Information that is especially important to note is identified by following labels:
• NOTE
• WARNING or CAUTION
• IMPORTANT
• TIP
NOTE: Provides you with information that is important to successfully
setup and use the iServer.
CAUTION or WARNING: Tells you about the risk of electrical shock.
CAUTION, WARNING or IMPORTANT: Tells you of circumstances or
practices that can effect the instrument’s functionality and must refer
to accompanying documents.
TIP: Provides you helpful hints.
1
PART 1
INTRODUCTION
1.1 Safety and EMC Considerations
Refer to the CE Aprrovals Section.
EMC Considerations
Whenever EMC is an issue, always use shielded cables.
Never run signal and power wires in the same conduit.
Use signal wire connections with twisted-pair cables.
Install Ferrite Bead(s) on signal wires close to the instrument if EMC problems persist.
Failure to follow all instructions and warnings may result in injury!
1.2 Before You Begin
Inspecting Your Shipment:
Remove the packing slip and verify that you have received everything listed. Inspect the
container and equipment for signs of damage as soon as you receive the shipment. Note
any evidence of rough handling in transit. Immediately report any damage to the shipping
agent. The carrier will not honor damage claims unless all shipping material is saved for
inspection. After examining and removing the contents, save the packing material and
carton in the event reshipment is necessary.
Customer Service:
If you need assistance, please contact the Customer Service Department nearest you.
Manuals, Software:
The latest operator’s manual as well as free iServer configuration software (iCONNECT)
and iServer Mail Notifier software are available at the WEB site listed on the cover
page of this manual. They may also be on the CD-ROM enclosed with your
shipment.
2
1.3 Description
The iServer is a stand alone Ethernet Server designed to connect devices with serial
interfaces to the Ethernet network using the TCP/IP protocol. It contains Ethernet and
RS-232/485/422 interfaces.
The standard features include:
Use standard Web Browser , TCP connection, HTTPGET DOS program or Telnet
Simulation, for network connectivity.
Install via RS-232/485/422 serial port connection.
Transfer data from RS-232/485/422 serial interface to TCP/IP using built-in socket server.
Use a standard home page or customize Web page for OEM applications.
This device can be purchased as a stand alone DIN Rail mounted unit, or
as a bench/wall mount unit.
The following example illustrates how you can hookup the devices with serial interface
on the network using the iServer:
Figure 1.1 Accessing devices over the Ethernet
COMMUNICATIONS
ETHERNET
DC POWER IN
RX TX ON COL
RESET
+ - N/C
COMPUTER
(COM Port
Redirector)
COMPUTER
(Telnet or
IP-enabled
Programs)
COMPUTER
(Standard
Web Browser)
3
4
PART 2
HARDWARE
2.1a Mounting on a DIN Rail
To install unit onto DIN Rail:
a) Tilt unit, position mounting slot onto DIN Rail, as shown.
b) Push unit towards DIN Rail and it will snap into place.
Figure 2.1a Mounting
2.1b Removal from a DIN Rail
a) Insert flat screw-driver into tab and push downwards.
b) Unit will detach from DIN Rail.
Figure 2.1b Removal
5
2.2 DIP Switches
1 To change the IP address, gateway address, and subnet mask from the serial port
2 To change to default factory settings
3 To enable/disable DHCP
4 To enable/disable Terminal Server function
To set the iServer to factory default
settings, slide DIP switch #2 to ON position. Power the
iServer on and wait about 10 seconds until the iServer fully
boots up. Set the DIP switch #2 back to OFF position (it
does not matter if the iServer is powered ON or OFF, just
make sure that the DIP switch is set
to OFF, otherwise, every time the
unit is power-cycled the factory
settings will take over. See Section
4.6 for setting the iServer to factory
default using the firmware (over the
LAN).
To enable the DHCP, besides using
DIP switch #3, set the iServer’s IP
address to 0.0.0.0. An iServer with
IP address of 0.0.0.0 will request an
IP address, gateway address, and
subnet mask from the DHCP server
over the Ethernet.
The iServer is shipped with all
DIP switches in "OFF" position
2.3 Parts of the iServer Unit
Table 2.1 Parts of iServer Unit
SERIAL Screw Terminal Block for RS-232 / RS-485 /
COMMUNICATIONS
RS-422 connections.
ETHERNET RJ45 interface for 10BASE-T connection.
RESET Button: Used for power reseting the iServer.
ACT LED (Red) Blinking: Indicates network activities
(receiving or sending packets).
LINK LED (Green) Solid: Indicates good network link.
TX LED (Yellow) Blinking: Indicates transmitting data
to the serial port.
RX LED (Green) Blinking: Indicates receiving data on
the serial port.
DC Power Supply Section:
+ Plus power supply wire connection
- Minus power supply wire connection
COMMUNICATIONS
ETHERNET
DC POWER IN
RX TX LINK ACT
RESET
+ - N/C
CH1 CH2
Figure 2.3 Parts of
the iServer Unit
OFF
ON
4
3
2
1
OFF
ON
4
3
2
1
Figure 2.2 DIP Switches
6
2.4 Serial Communication Interfaces
Two communication interfaces are supported in the iServer: RS232 and RS-485. These
standards define the electrical characteristics of a communication network. The RS485
port of the iServer is fully compatible to use with RS-485 and RS-422 instruments. The
RS485 is an extended version of the RS422 communication standard which increases
the allowable number of devices from 10 to 32 by improving the electrical
characteristics.
The RS232 standard (point-to-point) allows a single device to be connected to an
iServer. The iServer operates with full-duplex RS232 using seven wires: Rx-receive,
Tx-transmit, DTR, DCD, CTS, RTS and common ground wires. RS232 cable
length is limited to 50 feet.
The RS485 standard (multi-point) allows one or more devices (multi-dropped) to be
connected to the iServer using a two-wire connection (half-duplex) +Rx/+Tx and
–Rx/-Tx. Use of RS485 communications allows up to 31 devices to connect to the
iServer with cable length up to 4000 feet long.
Although the RS485 is commonly referred to as a "two wire" connection, the
iServer also provides a ground/return shield connection to use as a common
connection for EMI noise protection.
Table 2.2 shows the differences between RS232 and RS485 communication interfaces.
Table 2.2
Data Transmission Characteristics RS232 RS485
Transmission Mode Single ended Differential
Electrical connections 7 wire 2 wire
Drivers per line 1 driver 32 drivers
Receivers per line 1 receiver 32 receiver
Maximum cable length 50 ft (15 meters) 4000 ft (1200 meters)
Changing between RS232 and RS485 interfaces, as well as modifying the other
parameters is possible through the iServer firmware using its home Web page
or Telnet connection (see Part 4 for details).
2.4.1 Wiring RS232 Interface
Table 2.3 shows the signals and the direction of signals on the Screw Terminal Block
connector.
Figure 2.4 Serial Connector
Pin # Signal Direction
1 N/C --
2 GND --
3Rx IN
4 Tx OUT
*5 DCD IN
*6 RTS OUT
*7 DTR OUT
*8 CTS IN
COMMUNICATIONS
CH1 CH2
* These 4 pins can also be used as digital
input/output signals (firmware selection).
Table 2.3
7
2.4.2 Wiring RS485 Interface
RS485 interface uses a two-wire communication system (one for transmitting and one for
receiving) plus a common wire to connect to the shield of the cable. It is recommended
to use a shielded cable with one twisted pair.
Use of twisted pair and shield will significantly improve noise immunity.
Figure 2.5 shows multi-point, half-duplex RS485 interface connections for the iServer.
Figure 2.5 Multi-point, Half-Duplex RS485 Wiring
Value of the termination resistor is not critical and depends on the cable impedance.
Table 2.4 shows RS485 half-duplex hookup between the iServer serial port and
device with RS485 communication interface.
Table 2.4
Pin# iServer DEVICE WITH RS485
3
+Tx/+Rx (+Transmit/+Receive) +Tx/+Rx (+Transmit/+Receive)
4 -Tx/-Rx (-Transmit/-Receive) -Tx/-Rx (-Transmit/-Receive)
2
RTN (Common GND) GND (Common GND)
DEVICE #1
DEVICE #29
DEVICE #31
DEVICE #30
DEVICE #2
iServer
120 Ohm
Termination resistor
120 Ohm
Termination resistor
GND
-Tx/-Rx
+Tx/+Rx
+Tx/+Rx
-Tx/-Rx
Twisted shielded pair
-Tx/-Rx
-Tx/-Rx-Tx/-Rx
-Tx/-Rx
+Tx/+Rx
+Tx/+Rx
GND
GND
GND
GND
+Tx/+Rx
+Tx/+Rx
.........................
.........................
...............................
...............................
COMMUNICATIONS
ETHERNET
DC POWER IN
RX TX LINK ACT
RESET
+ - N/C
8
2.5 Network Communication Interfaces
2.5.1 10Base-T RJ-45 Pinout
The 10BASE-T Ethernet network (RJ-45) system is used in the iServer for network
connectivity. The 10 Mbps twisted-pair Ethernet system operates over two pairs of wires.
One pair is used for receiving data signals and the other pair is used for transmitting data
signals. This means that four pins of the eight-pin connector are used.
Figure 2.6 RJ45 Pinout
2.5.2 10Base-T Crossover Wiring
When connecting the iServer directly to the computer, the transmit data pins of the
computer should be wired to the receive data pins of the iServer, and vice versa. The
10Base-T crossover cable with pin connection assignments are shown on Figure 2.7.
Figure 2.7 10Base-T Crossover Cable Wiring
Use straight through cable for connecting the iServer to an Ethernet hub.
The ports on the hub are already crossed.
Pin Name Description
1 +Tx + Transmit Data
2 -Tx - Transmit Data
3 +RX + Receive Data
4 N/C Not Connected
5 N/C Not Connected
6 -Rx - Receive Data
7 N/C Not Connected
8 N/C Not Connected
9
PART 3
NETWORK CONFIGURATION
3.1 Network Protocols
The iServer can be connected to the network using standard TCP/IP protocols.
It also supports ARP, HTTP (WEB server), DHCP, DNS and Telnet protocols.
3.2 Ethernet (MAC) Address
MAC (Media Access Control) address is your computer's unique hardware number.
When you're connected to the LAN from your computer, a correspondence table relates
your IP address to your computer's physical (MAC) address. The MAC address can be
found on the label of your device and contains 6 bytes (12 characters) of hexadecimal
numbers XX:XX:XX:XX:XX:XX hex
For example: 0A:0C:3D:0B:0A:0B
There is room on the label to put your IP address. See Figure 3.1
Figure 3.1 Labeling
3.3 DHCP
DHCP, Dynamic Host Configuration Protocol enables individual computers or devices to
extract their IP configurations from a server (DHCP server). If the DHCP is enabled on
your iServer, as soon as the iServer is connected to the network, there is an exchange of
information between DHCP server and the iServer. During this process the IP address,
the Gateway address, and the Subnet Mask will be assigned to the iServer by the DHCP
server. Note that the DHCP server must be correctly configured to make such assignment.
The DHCP can also be enabled if the iServer’s IP address is set to 0.0.0.0.
If fixed or static IP address is desired, the DHCP must be disabled. The iServer is
shipped with DHCP disabled (factory default). The DHCP can be enabled by setting the
DIP switch # 3 to the “ON” position (refer to Figure 3.2).
Figure 3.2 DIP Switch on the Bottom Side of iServer
3.4 DNS
DNS, Domain Name System enables individual computers and devices to be recognized
over a network based on a specific name instead of an IP address. For example, instead
of having to use http://128.100.101.254 (IP address), you would use only http://eis03ec
or any eight character name stored as Host Name under Access Control menu in the
iServer Home Page. The default DNS name for an iServer is "eis" followed by the last
four digits of the MAC address of that particular iServer.
1. It is very important to communicate with the network administrator in order to
understand the DHCP and its existing configurations on the host server,
before enabling the DHCP on the iServer.
2. The iServers are shipped with a default static IP address of
128.100.101.254 and Subnet Mask of 255.255.0.0.
3. On Novell networks or Windows 2000 where the DCHP is an updated
function of DNS this feature may be beneficial since a particular name can be
assigned eliminating the need for the IP address, as described in Section 3.4.
OFF
ON
4
3
2
1
OFF
ON
4
3
2
1
10
10
DIP switch # 3 shown
in “ON” position
3.5 IP Address
Every active device connected to the TCP/IP network must have a unique IP address.
This IP address is used to build a connection to the iServer’s serial port. Every computer
using TCP/IP should have a unique 32-bit address. It is divided into two portions, the
network ID and the host ID. For instance, every computer on the same network uses the
same network ID. At the same time, all of them have a different host ID. For more details
about the IP address see Appendix B.
3.5.1 Default IP Address
The iServer is shipped with a default IP address set to 128.100.101.254 and Subnet
Mask of 255.255.0.0. If you are going to use a Web browser or Telnet program to access
the iServer using its default IP address, make sure that the PC from which you’re
establishing the connection has an IP address that is in the same range as the iServer’s
IP address (128.100.x.x, where x can be any number from 1 to 254. Note that your PC’s
IP address cannot be the same as the iServer’s IP address). You also need to make
sure that your PC’s Subnet Mask is 255.255.0.0. This is a good way to access the
iServer over the network and make any configuration changes needed. If the factory
default address is already in use on your network, use an Ethernet crossover cable
between your computer and the iServer and modify the IP address or any other settings
within the iServer.
3.6 Port Number
All TCP connections are defined by the IP address and a port number. A port number is
an internal address that provides an interface between an application running on your
computer and the network through the TCP/IP protocol.
There are three default TCP port (socket) numbers assigned to the iServer:
1. Port (socket) number 1000 when using HTTPGET program.
2. Port (socket) number 2000 when trying to access your serial device connected to
the serial port of the iServer.
3. Port (socket) number 2002 when trying to access the iServer itself for reading or
changing the settings. This can be done using Telnet application.
Example: C:\>Telnet 128.100.101.254 2002
11
PART 4
OPERATIONS
This iServer can be used and configured in several ways, depending on user’s
preference and network setup. It can be used in Telnet simulation mode where it
emmulates serial communication operation over a network cable or directly from a Web
browser, like Netscape or Internet Explorer.
If DHCP and DNS servers are used, the connection is very simple, you do not need to
worry about IP address, MAC address, or network conflicts, all of these issues are
resolved for you by your network DHCP and DNS server. All that is left for you to do, is to
use a straight/normal network cable to connect the device to a hub and power it up. Then
you can go to your computer that is connected over the same network and from the MS-
DOS Prompt window type "ping eisxxxx" followed by the last four digits from the MAC
address located on the side or back of the device.
Figure 4.1 Pinging eis03ec MS-DOS Prompt
This proves that the connection is proper and you can get into configuration or run mode
using the Telnet or Web browser.
12
13
4.1 iCONNECT Software
The iServer may also be assigned an IP Address by using the iCONNECT software.
a) Download the iCONNECT software from the website listed in this manual.
b) Install iCONNECT software on a networked PC. This software is compatible with
Windows 95, 98, NT, 2000, and XP.
c) Use iCONNECT to assign an IP address to the iServer and access its web pages
for configuration. You can also use any standard web browser to access the
iServer’s web pages. Consult with your IT department for obtaining an IP address.
Figure 4.2 Assigning an IP Address using iCONNECT
To access the iServer for Configuration.
a) By clicking on the “View Webpage” button, you will access the iServer’s main web page.
b) Click on the “Update” button to enter the main menu.
c) For information configuring the iServer, refer to Sections 4.2.4 and 4.2.5.
Figure 4.3 Accessing the iServer for Configuration
Place the IP address in this box
Take the MAC address from the
label attached to the bottom of
the iServer and place it in this
box
Click here to send the above IP
address to the iServer
After the IP address is assigned
to the iServer, click here to
access it’s web pages
4.2 Setup and Operation Using the iServer Web Page
Besides the iCONNECT software, you can use any standard web browser to access the
iServer’s web pages.
a) Start your web browser.
b) From the browser you type http://eisxxxx using the last four-digits from the MAC
address label located on the device if DHCP and DNS are used. If a static IP address
is used, then simly type http://x.x.x.x, where x.x.x.x is the iServer’s IP address.
c) The Home Page, shown below, will be displayed.
Figure 4.4 Device Type Menu
d) From the drop-down window you can select the type of device connected (i-Server,
iDRN, iDRX, i-Series, INFB, iR2, or iLD) then press Update to get to the Home Page.
Figure 4.5 iServer Home Page Menu
In order to access certain menu items of the Home Page, users may be
prompted with passwords. More details given in later sections.
14
15
4.2.1 Read Devices
Read variables from up to eight different devices.
Figure 4.6 Read Devices Menu
Read up to eight variables from the same device.
Manually or automatically update readings from your devices. Set time interval for
Auto Update.
Read and write the setpoint values to the device.
Changing Device Setup helps you to see eight different variables or devices by
“Check” box.
If access to the menu item is restricted, the user will be prompted for a
password. In order to proceed to the "Device Setpoints" submenu, the user
should enter the correct password for access Login (default password is
12345678) or access Admin (default password is 00000000).
Figure 4.7 Login Password
4.2.2 Send Raw Command
Send single command and receive response.
Figure 4.8 Serial Device Query Menu
16
4.2.3 Modify Device List Entry
Up to four different devices or parameters can be modified.
Device Address or ID is in Hex format. See Appendix D for conversion.
Figure 4.9 Device Setup Menu
Modify device list or parameters.
Figure 4.10 Modify Device List Menu
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51

Omega EIS-2 and EIS-2-RJ Owner's manual

Category
Networking
Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI