ADC PowerWorx Select Series User manual

Type
User manual
ADCP-80-531 • Issue 4 • July 2004
1262204 Rev B Page 1
© 2006, ADC Telecommunications, Inc.
PowerWorx
®
Power Distribution Products
Select Series Circuit Breaker
Power Distribution Panel User Manual
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Important Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Standard Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Revision History. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Trademark Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Admonishments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
General Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1 GENERAL CHARACTERISTICS AND FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1 Power Buses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.2 Input Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.3 Input Connectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.4 Output Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.5 Output Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.6 Chassis Ground Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.7 Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
1.8 Power-On Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
1.9 Circuit Breaker Alarm Indicator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
1.10 Alarm Relay Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
(continued)
Content Page
16755-B
ADCP-80-531 • Issue 4 • July 2004
Page 2
© 2006, ADC Telecommunications, Inc.
1.11 Alarm Contact Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.12 Circuit Breaker Designation Card and Holder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.13 Voltage Designation Label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.14 Material and Finish . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.15 Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1.16 Protective Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1.17 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1.18 Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1.19 Color. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1.20 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1.21 Environmental Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2 ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3 UNPACKING AND INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.1 Recommended Installation Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.2 Use of Screws in Accessories Package. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.3 Protective Cover Installation/Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.4 Cable Management Bar (Optional Accessory for Circuit Breaker Panels). . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.5 Rack Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.6 General Wiring Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.7 Chassis Ground Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
4.8 External Alarm Contact Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.9 Output Power Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.10 Input Power Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.11 Circuit Breaker Designation Card Holder and Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.12 Voltage Designation Label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
5 TESTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
5.1 Resistance Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.2 Wiring Connection Torque Measurements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.3 Connection Polarity Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.4 Alarm Contact Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.5 Circuit Breaker Alarm Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
6 OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
7 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
7.1 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
7.2 Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
7.3 Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
7.4 Power-On LED Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
7.5 Circuit Breaker Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
8 CUSTOMER INFORMATION AND ASSISTANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
_________________________________________________________________________________________________________
Content Page
ADCP-80-531 • Issue 4 •July 2004
Page 3
© 2006, ADC Telecommunications, Inc.
INTRODUCTION
This manual describes the PowerWorx
®
Select Series Circuit Breaker Power Distribution Panel,
hereinafter called “circuit breaker panel” or “panel.” A complete description of the circuit
breaker panel and its available options and accessories is provided plus the information required
to install, test, and operate the circuit breaker panel.
Application: The circuit breaker panel is a high current (100 Amps per bus) circuit breaker type
power distribution platform. The circuit breaker panel may be used to supply protected dc
power to the type of telecommunications products typically installed in central offices,
multimedia headends, remote sites, and other locations.
Input Power: The circuit breaker panel contains two buses (feeds) that accept either –24 Vdc or
–48 Vdc input power (both buses must have the same voltage) of up to 100 Amps per bus for a
total of 200 Amps per panel.
Output Power: The circuit breaker panel provides circuit breaker protected output power with
up to 8 circuit breaker positions per bus. The current rating for each circuit breaker may be 1, 3,
5, 10, 15, or 20 Amps (see Subsection 1.7, Circuit Breakers).
Standards
The circuit breaker panel meets UL, Telcordia (formerly Bellcore), NEC 1999, CSA, NEBS
Level 3, IEC, and CE standards.
Important Features
The circuit breaker panel incorporates the following important features:
Self-configuring voltage (–24 Vdc or –48 Vdc) capability and up to 100 Amps per bus to
simplify installation and allow one panel to fit most dc voltage applications
ON/OFF lettering on each circuit breaker for quick identification of tripped circuit
breakers as well as ampere ratings
Eight circuit breaker positions per bus (field-replaceable)
Alarm contact connections built into the circuit breaker panel for external connection to
visual, audio, and remote alarms
Two field-replaceable high-brilliance Power-On green LED indicators and two Alarm red
LED indicators (not field-replaceable)
Easily-removable (turn four screws) plastic protective cover over connectors to enhance
safety and panel accessibility
Two-post grounding to ensure robust and reliable ground connectivity
Standard Configuration
The standard configuration circuit breaker panel has two power buses (feeds), with each power
bus having multiple circuit breaker positions. The two buses are duplicates of each other in the
number and type of circuit breakers. The capacity of each bus is one to eight circuit breakers.
Each bus has Power-On and Alarm indicators on the front of the chassis and input, output,
ground, and alarm contact connections on the rear of the chassis.
ADCP-80-531 • Issue 4 • July 2004
Page 4
© 2006, ADC Telecommunications, Inc.
The current capacity of each bus is 100 Amps maximum. The total current of the circuit breaker
panel (both buses) is 200 Amps maximum.
The power dissipation of the circuit breaker panel is 100 watts maximum at 200 Amps.
The dimensions of the circuit breaker panel are 1.75 inches (4.45 centimeters) high, 17.13 inches
(43.5 centimeters) wide, and 10 inches (25.41 centimeters) deep. This does not include depth of
protective cover and connectors, circuit breakers, and visual indicators that extend beyond the
chassis.
The circuit breaker panel can be mounted in 19- or 23-inch racks (48.26 or 58.42 cm) with
WECO or EIA hole spacing using the mounting brackets provided.
Options
The circuit breaker panel is available with the following options:
One to eight replaceable circuit breakers can be installed for each bus
Selection of circuit breaker values (1, 3, 5, 10, 15, or 20 Amps).
Panel can be equipped with any combination of circuit breakers (with specified values) as
long as total current draw on each bus does not exceed 100 Amps
Selection of circuit breakers that trip instantly or trip after a short delay
Two types of alarm contact connectors, either a screw-down terminal strip connector or a
wire wrap pin block connector
Color of the circuit breaker panel is putty white.
Accessories
Several accessories for the circuit breaker panels are available (see Section 2, Accessories):
Circuit breakers with capacity values of 1, 3, 5, 10, 15, and 20 Amperes
Cable management bar kit
Compression lugs for connection to the input connectors
Lug terminals to connect #10 AWG wire to earth ground
Spare circuit breaker designation card kit
Revision History
ISSUE DATE REASON FOR CHANGE
Issue 1 09/2001 Original
Issue 2 03/2002 Updated to cover replaceable circuit breaker feature
Issue 3 07/2004 Updated to add warning saying use of one bus only on dual bus panel will result in false alarms
ADCP-80-531 • Issue 4 •July 2004
Page 5
© 2006, ADC Telecommunications, Inc.
Trademark Information
ADC and PowerWorx are registered trademarks of ADC Telecommunications, Inc.
Admonishments
Important safety admonishments are used throughout this manual to warn of possible hazards to
persons or equipment. An admonishment identifies a possible hazard and then explains what
may happen if the hazard is not avoided. The admonishments — in the form of Dangers,
Warnings, and Cautions — must be followed at all times. These warnings are flagged by use of
the triangular alert icon (seen below), and are listed in descending order of severity of injury or
damage and likelihood of occurrence.
General Safety Precautions
-
1 GENERAL CHARACTERISTICS AND FEATURES
This section defines the general characteristics and features of the Select Series Circuit Breaker
Panel. A typical circuit breaker panel with protective covers in place is shown in Figure 1. A
typical circuit breaker panel with the protective cover removed is shown in Figure 2.
Configurations and features other than those described may be available by special order. The
accessories available for the circuit breaker panel are listed in Section 2, Accessories.
Danger: Danger is used to indicate the presence of a hazard that will cause severe personal
injury, death, or substantial property damage if the hazard is not avoided.
Warning: Warning is used to indicate the presence of a hazard that can cause severe personal
injury, death, or substantial property damage if the hazard is not avoided.
Caution: Caution is used to indicate the presence of a hazard that will or can cause minor
personal injury or property damage if the hazard is not avoided.
Caution: The circuit breaker panel uses electrical voltage and amperage levels which, per
GR-1089, may be considered an electrical hazard. Care should be exercised to assure that only
qualified personnel are allowed to install, operate, maintain, or otherwise come in contact with
this equipment when the panel is energized. Only insulated tools should be used on energized
elements of the panel.
Caution: All circuit breaker panel wiring and cabling should be connected with the system
office battery input off or disconnected at the office distribution panel.
Caution: A replacement circuit breaker must have exactly the same current rating as the circuit
breaker being replaced.
ADCP-80-531 • Issue 4 • July 2004
Page 6
© 2006, ADC Telecommunications, Inc.
Figure 1. Front and Rear View of ADC PowerWorx Select Series Circuit Breaker Panel
with Protective Cover Attached (8/8-Position Panel Shown)
16756-B
UL/CSA/CE
LABEL
VENTS
PROTECTIVE COVER
PLACED OVER INPUT
AND OUTPUT POWER,
GROUND, AND ALARM
CONNECTIONS
MOUNTING
BRACKETS
FOR 23-IN. (58.42 CM)
RACK MOUNTING
BUS A
POWER-ON
INDICATOR
(GREEN LED)
BUS B
POWER-ON
INDICATOR
(GREEN LED)
BUS A
CIRCUIT BREAKER
INDICATOR (RED LED)
BUS B
CIRCUIT BREAKER
INDICATOR (RED LED)
1 TO 8 CIRCUIT BREAKERS
(BLANK PANEL IF NO
CIRCUIT BREAKER)
1 TO 8 CIRCUIT BREAKERS
(BLANK PANEL IF NO
CIRCUIT BREAKER)
FRONT VIEW
REAR VIEW
ADCP-80-531 • Issue 4 •July 2004
Page 7
© 2006, ADC Telecommunications, Inc.
Figure 2. Rear View of Select Series Circuit Breaker Panel with Protective Cover Removed
to Show Connections (Panel with Wire Wrap Alarm Connection Shown)
1.1 Power Buses
Each circuit breaker panel has two isolated power buses. Each bus distributes the input power to
the output power circuits. In each bus circuit, current flows from the input power bus, through
the circuit breaker, to the output power circuit. The current capacity of each bus is 100 Amps
maximum. A typical circuit breaker panel block diagram is shown in Figure 3.
Each of the power buses supports eight circuit breaker positions. Any combination of circuit
breakers up to 100 Amps total capacity may be installed in the circuit breaker mounting
positions for each power bus. Other circuit breaker capacity configurations may be available by
special order.
When a circuit breaker trips, the input power bus is disconnected from the corresponding output
circuit.
Warning: Use of one bus only on a dual bus panel will result in false alarms for the unused bus.
Power is required on both buses on a dual bus panel for normal operation.
16757-B
BUS B INPUT
CONNECTORS
(TWO-HOLE
COMPRESSION
LUG-STUD TYPE)
BUS A INPUT
CONNECTORS
(TWO-HOLE
COMPRESSION
LUG-STUD TYPE)
TO
BATTERY
B
TO
RETURN
B
TO
BATTERY
A
TO
RETURN
A
BUS B OUTPUT
CONNECTORS
(SCREW-DOWN
BARRIER TERMINAL
STRIPS)
BUS A AND BUS B
ALARM CONTACT
CONNECTOR (WIRE-
WRAP PIN BLOCK
TYPE SHOWN)
CHASSIS
GROUND
TERMINALS
BUS A OUTPUT
CONNECTORS
(SCREW-DOWN
BARRIER TERMINAL
STRIPS)
ADCP-80-531 • Issue 4 • July 2004
Page 8
© 2006, ADC Telecommunications, Inc.
Figure 3. PowerWorx Circuit Breaker Panel Block Diagram (8/8-Position Panel Shown)
1.2 Input Voltage
The dual bus circuit breaker panel can accommodate either –24 Vdc on both buses or –48 Vdc on
both buses.
The voltage level is sensed by the circuit breaker panel circuitry. The input voltages used with
the circuit breaker panel can fall within the following ranges:
–24 Vdc nominal, within range of –21 Vdc to –30 Vdc
–48 Vdc nominal, within range of –42 Vdc to –56 Vdc
1
2
3
4
5
6
7
8
BATTERY RETURN
BATTERY A
RETURN A
POWER A LED
BREAKER
ALARM A LED
1
2
3
4
5
6
7
8
BATTERY RETURN
BATTERY B
RETURN B
BUS A
RETURN A
POWER B LED
BREAKER
ALARM B LED
BUS B
RETURN B
–24V/–48V
–24V/–48V
C
NO
NC
C
NO
NC
SYSTEM ALARM
CONNECTIONS
16758-B
FA
FB
ADCP-80-531 • Issue 4 •July 2004
Page 9
© 2006, ADC Telecommunications, Inc.
1.3 Input Connectors
Each power bus has two input connectors on the rear of the fuse panel through which input power is
provided. The two input power connectors are labeled “BATT” (battery) and “RTN” (return). Each
input connector consists of two pairs of studs (with nuts), each mounted on a plated copper bar. Each
set of studs can accept different size 2-hole compression lugs which can be used with a range of wire
sizes up to #2 AWG copper wire. Two 2-hole lugs per bus and one spare lug for use with #2 AWG
wire (five total) are provided with the circuit breaker panel. Additional lugs are available as
accessory items (see Section 2, Accessories).
1.4 Output Voltage
The output voltage will be the same voltage as the applied input voltage.
1.5 Output Connectors
Each output circuit has two connectors through which the output power is provided for
connection to telecommunications equipment. Each output connector consists of two screw-
down barrier terminal strips. Eight terminals with 6-32 screws are mounted in each terminal
block. Two terminal blocks are provided per bus (one block for output and one block for return).
The terminals are on 0.375 inch (9.525 mm) centers with a distance between barriers of 0.325
inch (8.26 mm). The terminals can accept #12 to #22 AWG copper wire with crimp-on spade
lug or ring connectors, or wires with the insulation stripped back. The connectors or wires are
inserted under the screws in the terminal strip, and the screws are tightened down.
1.6 Chassis Ground Connection
Two #10 studs (with nuts) are provided for grounding the circuit breaker panel chassis. The
studs are mounted on 0.625 inch (15.875 mm) centers. The ground connection can be used to
attach a separate grounding conductor when mounting the circuit breaker panel in non-
grounded or non-conducting material or when required by local practice. The studs can
accommodate 2-hole lugs and up to #6 AWG wire. Two crimp ring lug terminals for use with
two #10 AWG wires are provided with the circuit breaker panel. The circuit breaker panel can
be properly grounded using only one stud.
ADCP-80-531 • Issue 4 • July 2004
Page 10
© 2006, ADC Telecommunications, Inc.
1.7 Circuit Breakers
The circuit breakers are magnetic actuation, manual reset, single pole, replaceable, 60 Vdc rated
circuit breakers, with finger guard and ampere markings. Circuit breaker values of 1, 3, 5, 10,
15, and 20 Amperes capacity are available. Each circuit breaker can be field-replaced by another
breaker with a different current rating or time delay. A breaker with a higher current rating may
be installed as a replacement as long as the total current draw of the affected bus does not
exceed 100 Amps.
The circuit breaker panel will accommodate from one to eight circuit breakers for each bus (up
to eight circuit breakers installed on each side of the panel). Each circuit breaker position that
does not have a circuit breaker installed will be filled with a black-colored blank plastic plate.
Any circuit breaker mounting positions that are left blank when the panel is ordered cannot be
fitted with field-installed circuit breakers.
Two types of circuit breakers are available. One type trips instantly and one type trips after a
short delay. The trip times as a function of the percent of rated current are shown in Table 1. The
circuit breaker will trip (open) and the switch will move to the “OFF” position (bottom pushed
in) when the circuit current exceeds the capacity of the circuit breaker. To reset the circuit
breaker, push the switch to the “ON” position (top pushed in).
1.8 Power-On Indicator
A green LED power-on indicator for each power bus is mounted on the front panel of the circuit
breaker panel. If the LED indicator is on, power is applied to the bus input connectors. If the
green LED indicator is off, power is not applied to the bus input connectors. The Power-On
LED is field-replaceable (see Subsection 7.4, Power-On LED Replacement).
Table 1. Circuit Breaker Trip Times
PERCENT OF RATED CURRENT
TRIP TIME
in
seconds
DELAY 100% 135% 150% 200% 400% 600% 800% 1000% 1200%
Instant NO
TRIP
MAY
TRIP
.100
MAX
.100
MAX
.100
MAX
.100
MAX
.100
MAX
.100
MAX
.100
MAX
Short NO
TRIP
.300-
7.00
.200-
5.00
.100-
2.00
.030-
.500
.008-
.300
.006-
.150
.005-
.100
.005-
.100
ADCP-80-531 • Issue 4 •July 2004
Page 11
© 2006, ADC Telecommunications, Inc.
1.9 Circuit Breaker Alarm Indicator
For each bus, the circuit breaker panel has one visual circuit breaker alarm indicator (red LED)
mounted on the front of the panel. The circuit breaker alarm indicator lights if any circuit
breaker on the corresponding bus fails. The circuit breaker alarm indicator stays off if all circuit
breakers on the corresponding bus are operational. Loss of power to either bus will cause the
circuit breaker alarm indicator for the corresponding bus to be off.
1.10 Alarm Relay Contacts
Each bus contains circuitry that operates a set of Form C alarm relay contacts when any circuit
breaker on the bus trips or when input power to the bus is lost. The alarm contacts may be used
to open or close a loop connected to an external alarm system.
Alarm connections are provided though a screw-down barrier terminal strip or a wire wrap pin
terminal block located on the rear side of the circuit breaker panel. During normal operation, the
normally open (NO) contacts remain open and the normally closed (NC) contacts remain
closed. When a circuit breaker trips or power is lost, the NO contacts close creating a
connection from NO to common (C), and the NC contacts open creating an open circuit
between the NC and C contacts. The maximum current rating for each set of alarm relay
contacts (three sets are provided) is 1.0 Amp.
1.11 Alarm Contact Connection
The fuse panel is available with either a screw-down terminal block or wire wrap pin terminal
block for the alarm contact connections.
The screw-down terminal block consists of six 3-48 screw terminals mounted in a barrier type
terminal block (see Figure 2). The screw terminals are mounted on 0.250 inch (6.350 mm)
centers with a maximum distance between barriers (maximum connecting terminal width) of
0.200 inch (5.080 mm). Two sets of three terminals (labeled NO, C, and NC) are provided for
connection with external alarm systems. The screw-down terminals will accept #16 to #30
AWG copper wire.
The wire wrap pin terminal block consists of nine wire wrap pins mounted in a terminal block.
Three sets of three wire wrap pins (NO, C, NC) are provided for connection with external alarm
systems. The wire wrap pins will accept #22 to #26 AWG copper wire.
Warning: Use of one bus only on a dual bus panel will result in false alarms for the unused bus.
Power is required on both buses on a dual bus panel for normal operation.
ADCP-80-531 • Issue 4 • July 2004
Page 12
© 2006, ADC Telecommunications, Inc.
1.12 Circuit Breaker Designation Card and Holder
A circuit breaker designation card as shown in Figure 4 and a card holder are provided with the
circuit breaker panel. The card holder is intended to be attached to the underside of the panel,
one of the panel mounting brackets, to a part of the rack in which the panel is installed, or at a
location close to the panel, as desired. The card should be filled out with circuit information for
each of the circuit breakers installed in the panel and inserted in the card holder. The card holder
has a pressure sensitive adhesive backing for attachment.
Figure 4. Circuit Breaker Designation Card
1.13 Voltage Designation Label
A voltage designation label as shown in Figure 5 is provided with the circuit breaker panel. The
label is intended to be filled out with the actual voltage present on the buses and placed on the
panel. The voltage designation label has a pressure sensitive adhesive backing for attachment.
Figure 5. Voltage Designation Label
1.14 Material and Finish
The circuit breaker panel chassis and brackets are made of 16-gauge cold rolled steel. The panel
and brackets are finished with powder paint.
16753-A
1.60 IN.
(4.06 CM)
2.36 IN.
(5.99 CM)
10 POSITION A AND B CARD
0.38 IN.
(0.96 CM)
1.00 IN.
(2.54 CM)
14228-A
ADCP-80-531 • Issue 4 •July 2004
Page 13
© 2006, ADC Telecommunications, Inc.
1.15 Cooling
The circuit breaker panel is well ventilated to allow efficient convection cooling of all components
without the use of fans or blowers. Holes are provided in the top and bottom of the panel to allow
heated air to escape from the panel and cool air to enter.
1.16 Protective Cover
A thick plastic protective cover is mounted over the input power connectors, the output power
connectors, the chassis ground terminals, and the external alarm contact connections. Access to
these connectors and terminals is obtained by removing the cover. The cover is easily removed
by loosening (but not removing) four screws that attach the cover to the chassis. The holes in the
cover are keyed to allow it to be pulled to the side and then lifted clear of the screws.
1.17 Dimensions
The dimensions of a typical circuit breaker panel are shown in Figure 6.
Figure 6. Dimensions of Circuit Breaker Panel (8/8-Position Panel with
Mounting Brackets Attached for 23-Inch [58.42 cm] Rack Mounting Shown)
22.31 IN.
(56.67 CM)
17.13 IN.
(43.51 CM)
23.00 IN.
(58.42 CM)
1.13 IN.
(2.86 CM)
1.75 IN.
(4.45 CM)
10.00 IN.
(25.41 CM)
10.93 IN.
(27.75 CM)
16762-B
ADCP-80-531 • Issue 4 • July 2004
Page 14
© 2006, ADC Telecommunications, Inc.
1.18 Weight
The weight of the circuit breaker panel is approximately 10 pounds (4.54 kilograms). The actual
weight is dependent upon the configuration of the panel.
1.19 Color
The color of the circuit breaker panel and mounting brackets is putty white.
1.20 Mounting
The circuit breaker panel can be mounted in a 19- or 23-inch rack (48.26 or 58.42 cm) using the
mounting brackets shown in Figure 7. The panel can be flush mounted or recessed 1, 2, 3, or 4
inches (25.4, 50.8, 76.2, or 101.6 mm) from the front of the rack. The mounting holes are slotted
to permit installation in racks with WECO 1.00-inch (2.54 cm) hole spacing or EIA 1.25-inch
(3.18 cm) hole spacing.
The following mounting brackets and screws are enclosed with the circuit breaker panel:
Two brackets for 19-inch rack installations
Two brackets for 23-inch rack installations
Eight 5/16-inch (7.936 mm) long, 8-32 chromate finish, thread-forming, flathead screws
for attaching the brackets to the circuit breaker panel
Four 3/8-inch (9.525 mm) long, 12-24 thread-forming screws and washers for attaching
the brackets to the rack
The slotted mounting hole pattern in the mounting brackets compensates for vertical rack
differences and allows mounting the circuit breaker panel in either 1.75- or 2-inch (4.45 or 5.08 cm)
rack spaces.
Caution: Use only the 5/16-inch (7.936 mm) long, chromate finish, flathead, thread forming
screws for attaching the mounting brackets to the circuit breaker panel. Use of any other
hardware could cause contact with internal parts of the panel. If parts are missing, please
contact ADC.
ADCP-80-531 • Issue 4 •July 2004
Page 15
© 2006, ADC Telecommunications, Inc.
Figure 7. Mounting Brackets for Mounting Circuit Breaker Panel
in 19- and 23-Inch (48.26 or 58.42 cm) Racks
1.21 Environmental Characteristics
Table 2 lists the environmental characteristics of the PowerWorx Select Series circuit
breaker panel.
Table 2. PowerWorx Select Series Circuit Breaker Panel Environmental Characteristics
PARAMETER DESCRIPTION
Operating temperature –5° C to +55° C
Storage temperature –45° C to +85° C
Humidity range 0% to 95% humidity (non-condensing)
Altitude range –197 ft. (0.06 km) to 13,000 ft. (3.96 km) above sea level
Fire rating All components UL94-V1
Earthquake design NEBS Level 3, Zone 4
Acoustic noise 0 dBA above ambient
Heat dissipation (fully loaded) 50 watts @ 100 Amps per bus, 100 watts @ 200 Amps
total circuit breaker panel load
Heat dissipation (no load) 1 watt per bus
19-INCH RACK MOUNTING
BRACKET INSTALLATION
23-INCH RACK MOUNTING
BRACKET INSTALLATION
USE 3/8-INCH (9.525 MM) 12-24
THREAD-FORMING SCREWS AND
WASHERS TO SECURE MOUNTING
BRACKETS TO RACK
USE 5/16-INCH (7.936 MM) 8-32
THREAD-FORMING FLAT-HEAD
SCREWS TO SECURE MOUNTING
BRACKETS TO PANEL
16965-A
ADCP-80-531 • Issue 4 • July 2004
Page 16
© 2006, ADC Telecommunications, Inc.
2 ACCESSORIES
The following accessories for the PowerWorx Select Series circuit breaker panel are available:
Circuit breakers. Current capacity of 1, 3, 5, 10, 15, 20 Amps with choice of two delay
values (instant and short).
Cable management bar with mounting screws. Provides cable tie points. Installed at rear
of circuit breaker panel by fastening ends of bar to both sides of the panel
Three sizes of two-hole compression lugs for #2, #4, and #6 AWG wire for input power
connection
Lug terminals to connect #10 AWG wire to earth ground
Circuit breaker designation card kit
Spare circuit breakers for field-replacement
3 UNPACKING AND INSPECTION
Unpack and inspect the various components as follows:
1. Inspect the exterior of the shipping container for evidence of handling that may have
damaged the components in the container.
2. Unpack each container while carefully checking the contents for damage and verify with
the packing slip.
3. File a claim with the commercial carrier and notify ADC Customer Service if damage is
detected or if parts are missing. Save damaged cartons for inspection by the carrier.
4. Refer to Section 8, Customer Information and Assistance at the back of this manual, for
repair, replacement, and warranty information.
5. Save all shipping containers for use if the equipment requires return shipment at a future date.
4 INSTALLATION
Circuit Breaker panels must be installed in a central office, equipment room, or restricted access
location.
The following guidelines should be used when mounting the circuit breaker panel in a rack.
Mount the circuit breaker panel in the uppermost area of the rack to reduce exposure of the
power wiring.
Provide a minimum of 1.75 inches (4.45 cm) of air space (one rack space) between the top
of the circuit breaker panel and the next item in the rack for cooling.
Adding a circuit breaker panel to a rack may displace a device which may require
relocation.
ADCP-80-531 • Issue 4 •July 2004
Page 17
© 2006, ADC Telecommunications, Inc.
4.1 Recommended Installation Tools
Use common hand tools, such as a Phillips screwdriver, a wire wrap gun and bits, a wire
stripper, and a wire lug crimper to install the circuit breaker panel. In addition to these tools, the
following tools are recommended:
Power screwdriver with bits for Phillips and slotted head screws
Set of sockets and driver
Set of open end or box end wrenches
Caution: This equipment employs electrical voltage and amperage levels which may be
considered an electrical hazard. Care should be exercised to assure that only qualified
personnel are allowed to install, operate, maintain, or otherwise come in contact with this
equipment when the circuit breaker panel is energized. Only insulated tools should be used on
energized elements of the circuit breaker panel.
Warning: Never install power equipment in a wet location or during a lightning storm. When
installing or modifying power lines, disconnect lines at the source before working with
uninsulated lines or terminals to prevent electrical shock.
16776-A
PHILLIPS SCREW
HEAD BIT
12504-A
ADCP-80-531 • Issue 4 • July 2004
Page 18
© 2006, ADC Telecommunications, Inc.
Torque screwdriver calibrated in pound-force inches or Newton meters and equipped with
bits for Phillips and slotted head screws
4.2 Use of Screws in Accessories Package
The circuit breaker panel accessories kit contains three types of screws. The screws used with
the rack-mounting brackets are thread-forming screws which will provide a solid ground path
between the panel chassis and the rack. Use the power screwdriver to install these screws.
4.2.1 Screws to Attach Brackets to Circuit Breaker Panel
To fasten the mounting brackets (ears) to the circuit breaker panel, use the 5/16-inch
(7.936 mm) long, chromate finish 8-32 screws as shown in Figure 8 (4 for each bracket). Eight
screws are in the package.
Figure 8. Screw for Attaching Bracket to Circuit Breaker Panel
4.2.2 Screws to Attach Brackets to Rack
To fasten the brackets to the rack, use the nickel plated 12-24 screws as shown in Figure 9 (2 for
each bracket). Four screws are in the package.
Caution: When installing the circuit breaker panel, use only the hardware supplied with the
panel. Use of any other hardware could cause damage to the panel. If parts are missing, please
contact ADC.
12506-A
5/16-IN.
(7.936 mm)
THREAD FORMING SCREW,
FLAT HEAD UNDERCUT,
PHILLIPS DRIVE
16977-A
8 - 32
THREAD
ADCP-80-531 • Issue 4 •July 2004
Page 19
© 2006, ADC Telecommunications, Inc.
Figure 9. Screw for Attaching Bracket to Rack
4.2.3 Screws to Attach Protective Cover to Circuit Breaker Panel
To fasten the plastic protective cover over the power connections, use the four tin plate finish
screws as shown in Figure 10. Four screws are in the package.
Figure 10. Screw for Attaching Protective Cover to Circuit Breaker Panel
4.3 Protective Cover Installation/Removal
To attach the plastic protective cover over the connectors on the rear of the circuit breaker panel,
insert the four screws (defined in Subsection 4.2.3, Screws to Attach Protective Cover to Circuit
Breaker Panel) into the standoffs located next to each output power screw-down barrier strip.
Rotate each screw several turns to get it threaded. Hold the cover so the lettering is oriented
properly and then place the cover over the screw heads. Slide the cover to the left and then
tighten the screws to 9 pound-force inches (1 Newton meter).
To remove the protective cover, loosen but do not remove the four screws that secure the cover
to the panel. Slide the cover to the right and then pull the cover directly outward and away from
the panel. The screws do not need to be completely removed to remove the protective cover.
3/8-IN.
(9.53 mm)
12 - 24
THREAD
PAINT CUTTING, TAPPING SCREW,
PAN HEAD, COMBINATION DRIVE
16592-A
3/8-IN.
(9.53 mm)
6 - 32
THREAD
MACHINE SCREW, PAN HEAD,
PHILLIPS DRIVE
16593-B
ADCP-80-531 • Issue 4 • July 2004
Page 20
© 2006, ADC Telecommunications, Inc.
4.4 Cable Management Bar (Optional Accessory for Circuit Breaker Panels)
Before installing the circuit breaker panel in the rack, mount the cable management bar (accessory
item, not supplied with panel) on the rear of the panel as shown in Figure 11, using the 0.25-inch
(6.35 mm) long 4-40 screws that are supplied with the cable management bar. The cable
management bar can be recess mounted by using the mounting holes closest to the front of the
panel.
Figure 11. Cable Management Bar Installation
4.5 Rack Mounting
The circuit breaker panel can be mounted in either a 19- or 23-inch (48.26 or 58.42 cm) wide
rack using the 1.75-inch high (4.45 cm), 19- or 23-inch rack mounting brackets. The brackets,
mounting screws, and washers are provided with the panel.
Use the following procedure to install the circuit breaker panel in the rack:
1. Attach the mounting brackets to the sides of the chassis using the eight 5/16-inch (7.94
mm) 8-32 flathead thread-forming screws provided. Tighten screws to 15 pound force-
inches (1.7 Newton meters) of torque to insure grounding.
2. Place the fuse panel in the specified mounting space within the rack as shown in Figure 12.
Caution: When attaching the cable management bar to the circuit breaker panel, use only the
hardware supplied with the cable management bar. Use of any other hardware could cause
contact with internal parts of the circuit breaker panel. If parts are missing, please contact ADC.
Note: A circuit breaker panel with the cable management bar attached may exceed the
12-inch (3.05 mm) overall depth objective described in GR-63 CORE, 02-14.
Caution: When attaching the mounting brackets to the circuit breaker panel, use only the
5/16-inch (7.935 mm) long, chromate finish, flathead, thread forming screws supplied with the
panel. Use of any other hardware could cause contact with internal parts of the circuit breaker
panel. If parts are missing, please contact ADC.
16759-B
CABLE
MANAGEMENT
BAR
ATTACH TO
EITHER SET
OF 3 HOLES
MOUNTING BRACKET
INSTALLED FOR
23-IN. (58.42 CM)
RACK MOUNTING
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32

ADC PowerWorx Select Series User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI