P6
Usually "B" hole is used in the installation
when the outside temperature is very low,
and in this way we prevent no ice in the
discharge water pipe . This solution is used
also to be more easy for the installer to
connect the internal drainage pipe when he
don't want to see the pipe from outside.
P20
- After drilling the holes, the plastic sheet supplied
with the air conditioner need to be fitted through
them.
- Measure the depth of the wall and cut supplied
plastic sheet.
- Roll the sheet and insert it into the hole, paying
attention to the joint line, which must be always
upper position. Remember that the sheet must
have the same inclination of the holes(min 3°).
- Insert the rings into the holes.
150mm ring
160mm ring