4 DKRCI.PI.HT0.E2.02 / 520H2195 © Danfoss A/S (AC-AKC/frz), 11-2007
Installation
Mechanical installation
General procedure for installation of heat cartridge kit ICAD 600 / ICAD 900 for all sizes of ICM valves.
Please observe that heat cartridge kit ICAD 600 / ICAD 900 must be installed before ICAD 600/900
are mounted on the ICM valves
• Check that the three socket set screws on ICAD are fully unscrewed counter clockwise and removed
with a 2.5 mm Hexagon key. See Fig.2
• Check that the two socket set screws on heat cartridge holder are fully unscrewed counter
clockwise with a 2.5 mm Hexagon key. See Fig.1
• Apply heat conductive compound to
• the heat cartridge (marked 1A on g. 1)
• into the both ends of the holes for heat cartridge,
on the heat cartridge holder. (marked 1B on g. 1)
• on the inner surface of the heat cartridge holder (marked 1C on g. 1)
• Insert the heat cartridge into the hole of the the heat cartridge holder.
Please observe to install it in to the rigth end ,as shown in g. 1
• Fasten the heat cartridge with the socket set screw using a 2.5 mm Hexagon key.
• Insert the ICAD into the hole the heat cartridge holder. (g. 2)
• Install the heat cartridge holder on the ICAD. Position the heat cartridge holder in a center position
as shown on g. 3
• Fasten the heat cartridge holder the socket set screw using a 2.5 mm Hexagon key.
• Reinstall the three socket set screws on ICAD.
• Please ICAD instruction PIHV0A352 on how to mount ICAD on ICM
Electrical installation
Please observe
. Never connect supply voltage before the heat cartridge is insertted into the hole of
the the heat cartridge holder.
Connect 24 V d.c/a.c