3906120683_NF_THYRITOP100_07_2019_FRA
SINGLE PHASE SOLID
STATE RELAYS 15 TO 90 A
THYRITOP
SERIE 101
GB - Installation and operation manual
2
906120683_NF_THYRITOP101_04_2022_FRA
GENERAL DESCRIPTION
Single phase solid state relay with input control by 3 - 32 Vdc or universal 20 - 260 Vac/dc signal. Switching
at zero crossing of the mains voltage.
Model available with MOV protection (varistor).
MOUNTING RECOMMENDATIONS
-Single-phase solid state relays are designed to provide a switching function that does not include
protection of the load line or the devices connected to it. The customer must provide all necessary
safety and protective devices in accordance with applicable electrical standards.
-Protect the safety relay against overheating by using a suitable heat sink (accessory). The heat sink
must be sized according to the ambient temperature and the load current.
Calculation of the power dissipation of the solid state relay :
Single-phase solid-state relay THYRITOP 101 15/25 A = 1.45 x IRMS[W]
Single-phase solid-state relay THYRITOP 101 50/90 A = 1.35 X IRMS[W]
IRMS = single-phase load current
Calculation of the thermal resistance of the heat sink Rth = (90 °C - T.amb. max.) / Pd with Pd = power dissipation
T.amb.max = maximum air temperature in the control cabinet.
Use a heat sink with a lower heat resistance than the calculated element (Rth).
Maximum ambient temperature 40°C usable with pollution degree 2 or higher.
- Mounting procedure on the heatsink: The contact surface between the heatsink and the module must have a
maximum flatness error of 0.05 mm and a maximum roughness of 0.02 mm. The fixing holes of the heat sink must be
threaded and countersunk.
ATTENTION
Spread 1 gram of heat conductive silicone paste (Thermo silicone paste ref. P01660013 recommended) on
the dissi-pated metal surface of the module. The surfaces must be clean and there must be no impurities in
the heat conducting paste.
Tighten the two fastening screws alternately to a torque of 0.4...0.6 Nm. Wait 5 minutes so that the excess
paste can drain off.
Tighten the two fixing screws alternately until a tightening torque of 1.2...1.4 Nm is reached.
WARNINGS
During its continuous operation, the heatsink
can reach very high temperatures, which may
persist even after the device is switched off,
due to its high thermal inertia.
Do not work on the
power section without
first disconnecting the
supply voltage to the
panel.
Follow the instructions
in the technical manual.
3906120683_NF_THYRITOP101_4_2022_FRA
THYRITOP 101
TH101-15 ATH101-25 ATH101-50 ATH101-70/90 A
THYRITOP 101
TH101-15 AP01660015 P01660025
Porte-fusibles Fusibles
P01660026
P01660029
P01660031
P01660015
P01660017
P01660017
TH101-25 A
TH101-50 A
TH101-90 A
THYRITOP 101THYRITOP 101
(*)
(*) avec l’option borne de signal de commande = 4
27.5
44.5
P01660030
P01660017
TH101-75 A
3906120683_NF_THYRITOP101_07_2019_FRA
The devices are produced in accordance with the Community Directives:
2011/65/EU (RoHS), 2014/30/EU (EMC), 2014/35/EU (LVD)
and in accordance with
following standards:
EN 50581:2012,
EN 60947-4-3:2000/A2:2011
The product has been designed for Type 1 environments.
Use of the product in type B environments may cause interference
electromagnetic interference; in this case, the user must adopt adequate solutions
improvement.
In Conformity with UL508 - File :E522688- NRNT, NRNT7, NRNT2, NRNT8
FRANCE
Pyrocontrole
6 bis, av. du Docteur Schweitzer
69881 MEYZIEU Cedex
Tél : +33 4 72 14 15 40
Fax : +33 4 72 14 15 41
www.pyrocontrole.com
INTERNATIONAL
Pyrocontrole
Tél : +33 4 72 14 15 55
Fax : +33 4 72 14 15 41
Our international contacts
http://www.pyrocontrole.com/fr/contact-us/international
Conformity TC N° RUД-IT.AЛ32.b.01762
FM approvals project NO: 0003054712
Conformity C/UL/US File no. TBA
Compatibilité électromagnétique EMC: Respect de la Directive 2014/30/EU avec référence à la norme EN 61326-1
Émission en milieu industriel classe A - Sécurité LVD: Respect de la Directive 2014/35/EU avec référence à la norme EN 61010-1
906120686_NF_THYRITOP 500_05-2019_FRA
906121683_NF_THYRITOP101_04-2022_GB
FRANCE
Pyrocontrole
6 bis, av. du Docteur Schweitzer
69881 MEYZIEU Cedex
Tél : +33 4 72 14 15 40
Fax : +33 4 72 14 15 41
www.pyrocontrole.com
INTERNATIONAL
Pyrocontrole
Tél : +33 4 72 14 15 55
Fax : +33 4 72 14 15 41
Our international contacts
http://www.pyrocontrole.com/fr/contact-us/international
Conformity TC N° RUД-IT.AЛ32.b.01762
FM approvals project NO: 0003054712
Conformity C/UL/US File no. TBA
Compatibilité électromagnétique EMC: Respect de la Directive 2014/30/EU avec référence à la norme EN 61326-1
Émission en milieu industriel classe A - Sécurité LVD: Respect de la Directive 2014/35/EU avec référence à la norme EN 61010-1
906120686_NF_THYRITOP 500_05-2019_FRA
15
12.5
10
7.5
5
0
20 30 40 50 60 70
Température ambiante °C
Courant de charge Arms
THYRITOP 101 - 15 A
Dissipateur thermique °C/W
3.40
4.00
4.60
5.70
7.50
25
20
15
10
5
0
20 30 40 50 60 70
Température ambiante °C
Courant de charge Arms
THYRITOP 101 - 25 A
1.60
1.90
2.20
2.80
4.60
50
40
30
20
10
0
20 30 40 50 60 70
Température ambiante °C
Courant de charge Arms
THYRITOP 101 - 50 A
0.52
0.66
0.83
1.50
2.50
50
40
30
20
10
0
20 30 40 50 60 70
Température ambiante °C
0.40
0.50
0.60
1.50
2.00
THYRITOP 101 - 75 A
0.83
1.20
Courant de charge Arms
Dissipateur thermique °C/W
Dissipateur thermique °C/W Dissipateur thermique °C/W
DERATING CURVES
Connector Référence
2-pole spring connector TH101 P01660000
2-pole spring connector (x2) TH101 P01660001
2-pole spring connectorTH101 P01660002
ACCESSORIES
Sinker Référence
Heat sink Rth 0,83°/W P01660006
Heat sink Rth 0,56°/W P01660008
DIN adapter Référence
DIN rail adapter P01660009
Thermo silicone paste Référence
Thermo silicone paste(100g) P01660013
50
40
30
20
10
0
20 30 40 50 60 70
Température ambiante °C
0.40
0.50
0.60
1.50
2.00
THYRITOP 101 - 90 A
0.83
1.20
Courant de charge Arms
Dissipateur thermique °C/W
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

CHAUVIN ARNOUX Thyritop 101 Series User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI