Sentera Controls MDACM1 Mounting Instruction

Type
Mounting Instruction

Sentera Controls MDACM1 is a digital-to-analog converter that's designed for converting a Modbus RTU (RS485) signal into an analog/modulating output signal (0—10 VDC / 0—20 mA / PWM). It's a Power over Modbus supplied device and all its parameters are accessible via Modbus RTU.

Here are some of the key features and possible use cases of the MDACM1:

  • Intended for BMS (Building Management Systems) and controlled ventilation systems.
  • Supports Modbus signal conversion.
  • Selectable analog/modulating output types, including 0—10 VDC, 0—20 mA, and PWM.
  • Easy configuration and monitoring via Modbus RTU using Sentera's 3SModbus software or Sensistant tool.

Sentera Controls MDACM1 is a digital-to-analog converter that's designed for converting a Modbus RTU (RS485) signal into an analog/modulating output signal (0—10 VDC / 0—20 mA / PWM). It's a Power over Modbus supplied device and all its parameters are accessible via Modbus RTU.

Here are some of the key features and possible use cases of the MDACM1:

  • Intended for BMS (Building Management Systems) and controlled ventilation systems.
  • Supports Modbus signal conversion.
  • Selectable analog/modulating output types, including 0—10 VDC, 0—20 mA, and PWM.
  • Easy configuration and monitoring via Modbus RTU using Sentera's 3SModbus software or Sensistant tool.
MDACM1 DIGITAL TO ANALOGUE
CONVERTER
Mounting and operating instructions
www.sentera.eu
MIW-MDACM1-EN-000 - 30 / 03 / 2022 2 - 80
back to the table of contents
MDACM1 DIGITAL TO ANALOGUE
CONVERTER
Table of contents
SAFETY AND PRECAUTIONS 3
PRODUCT DESCRIPTION 4
INTENDED AREA OF USE 4
TECHNICAL DATA 4
STANDARDS 4
OPERATIONAL DIAGRAM 5
WIRING AND CONNECTIONS 5
MOUNTING INSTRUCTIONS IN STEPS 5
VERIFICATION OF INSTALLATION INSTRUCTIONS 7
OPERATING INSTRUCTIONS 7
TRANSPORT AND STORAGE 8
WARRANTY AND RESTRICTIONS 8
MAINTENANCE 8
www.sentera.eu
MIW-MDACM1-EN-000 - 30 / 03 / 2022 3 - 80
back to the table of contents
MDACM1 DIGITAL TO ANALOGUE
CONVERTER
SAFETY AND PRECAUTIONS
Read all the information, the datasheet, Modbus map, mounting and operating
instructions and study the wiring and connection diagram before working with the
product. For personal and equipment safety, and for optimum product performance,
make sure you entirely understand the contents before installing, using, or maintaining
this product.
For safety and licensing (CE) reasons, unauthorised conversion and/ or modifications
of the product are inadmissible.
e product should not be exposed to abnormal conditions, such as extreme
temperatures, direct sunlight or vibrations. Long-term exposure to chemical
vapours in high concentration can affect the product performance. Make sure the
work environment is as dry as possible; avoid condensation.
All installations shall comply with local health and safety regulations and local
electrical standards and approved codes. is product can only be installed by
an engineer or a technician who has expert knowledge of the product and safety
precautions.
Avoid contacts with energised electrical parts. Always disconnect the power
supply before connecting, servicing or repairing the product.
Always verify that you apply appropriate power supply to the product and use
appropriate wire size and characteristics. Make sure that all the screws and nuts
are well tightened and fuses (if any) are fitted well.
Recycling of equipment and packaging should be taken into consideration and these
should be disposed of in accordance with local and national legislation/regulations.
In case there are any questions that are not answered, please contact your
technical support or consult a professional.
www.sentera.eu
MIW-MDACM1-EN-000 - 30 / 03 / 2022 4 - 80
back to the table of contents
MDACM1 DIGITAL TO ANALOGUE
CONVERTER
PRODUCT DESCRIPTION
e MDACM1 is intended for converting a Modbus RTU (RS485) signal into an
analogue / modulating output signal (010 VDC / 0—20 mA / PWM). It is Power
over Modbus supplied and all parameters are accessible via Modbus RTU. It needs a
master unit, such as the Sentera RDPU or any BMS or master module that is able to
write a value in Modbus Holding registers.
INTENDED AREA OF USE
BMS and controlled ventilation systems
Modbus signal conversion
TECHNICAL DATA
Power supply: 24 VDC, Power over Modbus
Selectable analogue / modulating output types:
010 VDC mode: min. load 50 kΩ (RL ≥ 50 kΩ)
020 mA mode: max. load 500 Ω (RL ≤ 500 Ω)
PWM mode: PWM Frequency: 1 kHz, min. load 50 kΩ (RL ≥ 50 kΩ)
Maximum power consumption: 0,72 W
Nominal power consumption in normal operation: 0,54 W
Imax: 30 mA
Protection class: IP65
Operating ambient conditions:
Temperature: -10—60 °C
Rel. humidity: 5—85 % rH (non-condensing)
Storage temperature: -20—70 °C
STANDARDS
EMC Directive 2014/30/EC:
EN 61000-6-1:2007 Electromagnetic compatibility (EMC) - Part 6-1: Generic
standards - Immunity for residential, commercial and light-industrial
environments
EN 61000-6-3:2007 Electromagnetic compatibility (EMC) - Part 6-3: Generic
standards - Emission standard for residential, commercial and light-industrial
environments Amendments A1:2011 and AC:2012 to EN 61000-6-3
WEEE Directive 2012/19/EC
RoHs Directive 2011/65/EC
www.sentera.eu
MIW-MDACM1-EN-000 - 30 / 03 / 2022 5 - 80
back to the table of contents
MDACM1 DIGITAL TO ANALOGUE
CONVERTER
OPERATIONAL DIAGRAM
Holding register 12
AO1 (%),
0—10 VDC
0—20 mA
PWM
0
10
0
1000
WIRING AND CONNECTIONS
RJ45 connection
24 VDC Supply voltage 24 VDC
GND Ground
A Modbus RTU communication, signal A
/B Modbus RTU communication, signal /B
/B
A
GND
24 VD
C
8 mm
8 mm
8 mm
8 mm
RJ45
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
3
4
5
6
3
4
Terminal block connection
VIN Supply voltage 24 VDC
GND Ground, supply voltage
AO1 Analogue / modulating output (010 VDC / 0—20 mA / PWM)
GND Ground, AO1
Output
connection Spring contact terminal blocks, cable cross section: 1,5 mm2
ATTENTION MDACM1 needs to be supplied either via the RJ45 connector or via the connection
terminals. Do not supply the device via the RJ45 connector and the connection
terminals simultaneously!
MOUNTING INSTRUCTIONS IN STEPS
Before you start mounting the MDACM1, read carefully Safety and Precautions.
Choose a smooth surface for installation (awall, panel, etc.) and follow these steps:
1. Unscrew the front cover of the enclosure and remove it.
2. Fix the enclosure onto the surface by means of suitable fasteners while adhering
to the mounting dimensions shown in Fig. 1 Mounting dimensions and the correct
mounting position shown in Fig. 2 Mounting position.
www.sentera.eu
MIW-MDACM1-EN-000 - 30 / 03 / 2022 6 - 80
back to the table of contents
MDACM1 DIGITAL TO ANALOGUE
CONVERTER
Fig. 1 Mounting dimensions Fig. 2 Mounting position
2x Ø 3,
4
49
52
Correct Incorrect
MDAC
65
M12
MDAC
80
65
85
M12
MDAC
65
M12
3. Insert the cables though the cable glands.
4. Crimp the RJ45 cable and plug it into the socket, then connect the output wires
as shown in Fig.3. Connections adhering to the information in section “Wiring
and connections”.
Fig. 3 Connections
1
2
/B
A
GND
24 VDC
8 mm
8 mm
8 mm
8 mm
RJ45
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
3
4
5
6
3
4
A01
GND
5. Put back the front cover and secure it with the screws. Tighten the cable glands.
6. Switch on the power supply.
PWM mode (open collector connection):
When PWM mode is selected and the PWM output is set to “open collector, an
external pull-up resistor needs to be used. See Fig. 4 below.
www.sentera.eu
MIW-MDACM1-EN-000 - 30 / 03 / 2022 7 - 80
back to the table of contents
MDACM1 DIGITAL TO ANALOGUE
CONVERTER
Fig. 4 PWM (Open collector) connection
External pull-up
resistor
(10—100 kΩ)
PWM
Voltage source
(3,3—30 VDC) GND
Optional settings
To assure correct communication, the NBT needs to be activated in only two devices
on the Modbus RTU network. If necessary, enable the NBT resistor via 3SModbus or
Sensistant (Holding register 9).
Example 1 Example 2
RX
ТX
NBT
NBT
Slave 2
Master
Slave n
Slave 1
Slave 2
Slave 1
RX
ТX
NBT
NBT
Master
Slave n
On a Modbus RTU network, two bus terminators (NBTs) need to be activated.
NOTE
VERIFICATION OF INSTALLATION INSTRUCTIONS
Continuous green LED indication means the unit is supplied. If the LED is not on,
check the connections again.
Blinking green LED indicates active Modbus communication. If the LED does not
blink, check the connections again.
OPERATING INSTRUCTIONS
e MDACM1 is operated via Modbus RTU. To monitor and configure its settings,
you can either download the free 3SModbus software from Sentera’s website or use
the Sensistant tool. Refer to the Modbus Register Map.
NOTE For the complete Modbus register data, refer to the product Modbus Register
Map, which is a separate document attached to the article code on the website
and contains the registers list. Products with earlier firmware versions may not be
compatible with this list.
www.sentera.eu
MIW-MDACM1-EN-000 - 30 / 03 / 2022 8 - 80
back to the table of contents
MDACM1 DIGITAL TO ANALOGUE
CONVERTER
Bootloader
anks to the bootloader functionality, the unit firmware can be updated via Modbus
RTU communication. With 3SM boot Application (part of 3SM center software
suite), ‘boot mode’ is automatically activated and the firmware can be updated.
NOTE Make sure the power supply does not get interrupted during “bootload” procedure,
otherwise you risk losing unsaved data.
TRANSPORT AND STORAGE
Avoid shocks and extreme conditions; stock in original packing.
WARRANTY AND RESTRICTIONS
Two years from the delivery date against defects in manufacturing. Any modifications
or alterations to the product after the date of publication relieve the manufacturer
of any responsibilities. e manufacturer bears no responsibility for any misprints or
mistakes in this data.
MAINTENANCE
In normal conditions this product is maintenance-free. If soiled, clean with a dry or
damp cloth. In case of heavy pollution, clean with a non-aggressive product. In these
circumstances the unit should be disconnected from the supply. Pay attention that
no fluids enter the unit. Only reconnect it to the supply when it is completelydry.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Sentera Controls MDACM1 Mounting Instruction

Type
Mounting Instruction

Sentera Controls MDACM1 is a digital-to-analog converter that's designed for converting a Modbus RTU (RS485) signal into an analog/modulating output signal (0—10 VDC / 0—20 mA / PWM). It's a Power over Modbus supplied device and all its parameters are accessible via Modbus RTU.

Here are some of the key features and possible use cases of the MDACM1:

  • Intended for BMS (Building Management Systems) and controlled ventilation systems.
  • Supports Modbus signal conversion.
  • Selectable analog/modulating output types, including 0—10 VDC, 0—20 mA, and PWM.
  • Easy configuration and monitoring via Modbus RTU using Sentera's 3SModbus software or Sensistant tool.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI