9 Combustion Air and Ventilation Openings
Provisions must be made for combustion air and
ventilation air in accordance with section 5.3 Air for
Combustion and Ventilation, of the National Fuel Gas
Code, ANSI Z 223.1, or applicable provisions of the local
building code.
Canadian installations must comply with CSA/CGA-
B149.1 and .2 Installation Codes.
CAUTION!
BOILER DAMAGE AND OPERATIONAL
FAILURES !
Due to insufficient or lacking openings for
combustion air and/or ventilation of the
boiler room.
Provisions for combustion air and
ventilation are always required, regardless
whether the combustion air is taken from
the outside (sealed combustion) or inside
(room air for combustion).
Insufficient ventilation of the boiler room
can lead to high air temperatures. This
can result in boiler damage.
z Make sure that intake and exhaust
openings are sufficiently sized and no
reduction or closure of openings takes
place.
z When the problem is not resolved, do
not operate the boiler.
z Please note these restrictions and its
dangers to the operator of the boiler.
CAUTION!
BOILER DAMAGE !
due to contaminated air.
z Boiler must be clear and free from
combustible materials, gasoline and
other flammable vapors and liquids,
and corrosive liquids and vapors.
Never use chlorine and hydrocarbon
containing chemicals (such as spray
chemicals, solution and cleaning
agents, paints, glues etc) in the vicinity
of the boiler.
z Do not store and use these chemicals
in the boiler room.
z Avoid excessive dust formation and
build-up.
NOTICE !
When one expects contaminated
combustion air (near swimming pools,
chemical cleaning operations and hair
salons), sealed combustion operation is
recommended.
DANGER!
FIRE DANGER !
due to flammable materials or liquids.
z Do not store flammable materials and
liquids in the immediate vicinity of the
boiler.