Kidde P3010CU Installation guide

Category
Fire protection
Type
Installation guide

This manual is also suitable for

Combination Smoke and
Carbon Monoxide Alarm
Sealed Lithium Battery Power
Voice Alarm
Announces the hazard type detected.
Test/Hush Button
A single button that tests alarm circuitry and
temporarily silences nuisance alarms.
LED Indicator
A flashing red indicator blinks to correspond
with alarm sound, unit error mode, and standby
condition.
Combined Smoke and Carbon Monoxide Alarm
Unique sensor algorithm detects real fires faster and
reduces nuisance alarms.
Sealed-In Lithium Battery
Unit will continue to operate for 10 years. Alerts
user to replace alarm after 10 years of operation.
Description
The Kidde P3010CU is a 10-year, sealed battery, smoke and
carbon monoxide alarm with a voice warning system that features
photoelectric and electrochemical sensing technology with Smart
Hush feature. This combination alarm combines the detection
capabilities of a photoelectric sensor with that of an electrochemical
sensor, which is used to detect CO. When either sensor notices a
potential hazard, it will communicate with the other. Depending on
what is detected, the alarm will adjust its smoke sensitivity in order
to better discriminate between a real hazard and a false one. This
constant communication enhances the alarm’s overall performance
and significantly reduces the potential for a nuisance alarm.
The voice warning system announces “Fire”, or “Warning, Carbon
Monoxide” to help eliminate any confusion and clearly warn you
and your family of a smoke or carbon monoxide danger.
The sealed in lithium battery will power the unit for the entirety of
its 10 year life, eliminating the need for battery replacement and
worry about unauthorized battery removal. The alarm provides
continuous protection from smoke and carbon monoxide, even
during power outages.
The alarm will automatically activate when it is attached to the
mounting bracket; there are no pull-tabs, no switches, everything
is automatic. At the end of alarm life, the unit will chirp, indicating
the alarm is in need of replacement. The customer can use a simple
tool such as a screwdriver to deactivate the unit, stopping the chirp
and making it safe for disposal.
Leading authorities recommend that both ionization and
photoelectric smoke alarms be installed to help ensure maximum
detection of the various types of fires that can occur within the
home. Ionization sensing alarms may detect invisible fire particles
(associated with fast flaming fires) sooner than photoelectric
alarms. Photoelectric sensing alarms may detect visible fire particles
(associated with slow smoldering fires) sooner than ionization
alarms.
Features and Benefits
Combination Smoke and Carbon Monoxide Alarm – Smoke
and CO sensing technologies work together to detect real fires
faster and reduce nuisance alarms.
Voice Alarm – Announces the hazard type detected thereby
helping to speed up the correct reaction. Alarm announces
“Fire!” when a smoke or fire hazard is detected and announces
“Warning Carbon Monoxide” when a CO hazard is detected.
Sealed-In Lithium Battery – Sealed-in lithium power supply;
no battery replacement required over the 10 year life of the
alarm. Eliminates worry about battery removal or unauthorized
deactivation of alarm.
Photoelectric Sensor – Smoke alarm contains advanced
photoelectric sensor that may detect visible particles (associated
with smoldering fires) sooner than ionization alarms.
Self Activation – Alarm automatically activates when attached
to the mounting bracket.
Test/Hush Button – Tests alarm circuitry and activates Hush
features.
Smart Hush
TM
– Temporarily silences nuisance alarms for
approximately 9 minutes and will not allow hush mode unless
the unit is in alarm mode.
• LED – Red LED will blink in conjunction with the alarm sound.
End of Life Warning – Alarm chirps twice every 30 seconds to
indicate the unit is in need of replacement.
End of Life Hush
®
– End of life indication can be silenced three
days at a time up to 30 days to
allow for alarm replacement at
a more convenient time.
UL217 and UL2034 Listed
10 Year Limited Warranty
10
Model P3010CU
See user guide for additional important information.
Combination Smoke & Carbon Monoxide Alarm
Sealed Lithium Battery Power
Model P3010CU
Architectural and Engineering
Specifications
The combination smoke and carbon monoxide alarm shall be
Kidde model number P3010CU or approved equal. It shall be
powered by a non-replaceable lithium battery with a 10-year life.
The lithium battery shall be sealed in the unit to prevent removal
and/or tampering. The unit shall incorporate a photoelectric
smoke sensor and an electrochemical carbon monoxide sensor.
The CO sensor shall be of a fuel cell design and provide accuracy
of +/- 20% + 15 PPM. The temperature operating range shall be
between 40ºF and 100ºF (4ºC and 38ºC) and the humidity oper-
ating range shall be 10%-95% non-condensing relative humidity.
The alarm can be installed on the surface of any wall or ceiling
following the UL/Manufacturer’s approved placement guidelines.
The alarm shall incorporate an automatic activation feature that
will activate the unit as soon as it is attached to the mounting
bracket, no other steps are involved.
The alarm shall include a test button that will electronically simu-
late the presence of smoke and CO and cause the unit to go into
both modes of alarm. This sequence tests the unit’s electronics to
ensure proper operation.
The CO sensor will not alarm to levels of CO below 30 PPM and
will alarm in the following time range when exposed to the cor-
responding levels of CO.
70 PPM CO Concentration 60 – 240 Minutes
150 PPM CO Concentration 10 – 50 Minutes
400 PPM CO Concentration 4 – 15 Minutes
The alarm shall include a piezoelectric horn that is rated at 85
decibels at 10 feet. For a CO incident, the horn will sound in
the repetitive manner – 4 quick beeps, voice message “Warning!
Carbon Monoxide”, 4 quick beeps. In a smoke incident, the
horn sounds 3 long beeps, voice message “Fire!”, 3 long beeps,
repeating. The red LED will flash in conjunction with the alarm
sound. See User Guide for details regarding voice warning for
low battery condition.
The unit shall indicate a low battery condition with a brief alarm
chirp every 60 seconds and LED flash once every 30 seconds. In
standby condition, the LED will flash every 60 seconds for the
first 10 minutes following power on or test, and once every 10
minutes thereafter. It will also flash every 10 seconds while in
Hush mode.
The smoke alarm shall include an End of Life Alert, where ten
years after initial power-up the unit shall chirp two times every
30 seconds to indicate the alarm needs to be replaced. The
End of Life indication can be silenced for 3 days at a time for
a maximum of 30 days. The unit shall have a deactivation
switch to disable it and make it safe for disposal.
The unit shall at a minimum meet the requirements of
UL217, UL 2034, NFPA 72. The State of California Fire
Marshall, NFPA 101 (One and two family dwellings), Federal
Housing Authority (FHA), Housing and Urban Development
(HUD). It shall also include a 10-year manufacturer’s limited
warranty.
Ordering Information
Technical Specifications
Model: P3010CU
Power Source: Sealed Lithium Battery
Sensor: Smoke: Photoelectric
CO: Electrochemical
Audio Alarm: 85dB at 10ft
Temperature Range: 40˚F (4.4˚C) to 100˚F (37.8˚C)
Humidity Range: 10%-95% non-condensing
relative humidity (RH)
Size: 5.22” in diameter x 1.6” depth
Weight: 1 lb.
Interconnects: No
Warranty: 10 year limited
5.22" 1.6"
1016 Corporate Park Drive
Mebane NC 27302
1-800-880-6788
www.Kidde.com
Distributed by:
P/N: KL-P3010CU sheet rev. 01-2015
Ordering
Number UPC I 2 of 5
Pack
Cong Pack Qty
Dimensions
(w x d x h)
inches Weight
Cartons/
Pallet
21026065 0-47871-26065-2 100-47871-26065-9 Clam 3pk 8 x 9.5 x 11.5 1.35 225
  • Page 1 1
  • Page 2 2

Kidde P3010CU Installation guide

Category
Fire protection
Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI