ISSUE 03: 18-Oct-2023 Page 9 002097MAN-04
go to TABLE OF CONTENTS
Search for any topic:
Wiring
Power Supply Connections
The heat pump electrical box and also the enclosure (if
used) have several knockouts of various sizes for the electrical
connections.
A schematic diagram (SCH) and electrical box layout
diagram (ELB) can be found on the electrical box cover of the
unit as well as in the Model Specific Information chapter of
this manual.
The Electrical Specifications in the Model Specific Infor-
mation chapter contain information about the size of wire for the
connections, as well as the recommended breaker size. These
should be checked by referencing MCA and FLA by a qualified
professional to ensure conformance to local codes. Power sup-
ply connections to the unit are made directly to the power block
inside the electrical box and are as per TABLE 1. Ground is to
be connected to the GND lug inside the electrical box.
IMPORTANT NOTE: A properly qualified
electrician should be retained for all
connections to the heat pump and associat-
ed controls. The connections to the heat
pump MUST CONFORM TO LOCAL CODES.
Outdoor Loop Circulator Pump Wiring
The outdoor loop circulator provides flow between the heat
pump and the outdoor loop. In most multiple-unit commercial
installations, the circulators (and the heat pump) will be con-
trolled by the building automation system, since one circulator
may serve several heat pumps. Connect circulator pumps as
per site drawings.
If the heat pump is to control the outdoor circulator, there
are dry contacts provided to control the circulator pump so that it
will be turned on whenever the compressor operates. Wire to
CP1 and CP2 on the terminal strip at the lower right side of elec-
trical box, as shown on the following diagram 002188CDG and
the wiring diagram (SCH) in the Model Specific Information
chapter of this manual. Ensure that the total current draw does
not exceed the value indicated on the diagram.
There is also provision for directly connecting an outdoor
circulator contactor with 24VAC coil, without external 24VAC
transformer. See “Outdoor Water Valve Wiring - ON/OFF”, be-
low.
IMPORTANT: If the outdoor circulator is connected via CP1 and
CP2, it may be unnecessarily activated at times when the com-
pressor is not running, if using the Setpoint Control option
(refer to Setpoint Control chapter of this manual). Under Set-
point Control, the heat pump will start and stop indoor circulators
connected via CP1 and CP2 to sample the water temperature
when the heat pump is not operating. Therefore, if using Set-
point Control, outdoor circulators should be connected as per
“Outdoor Water Valve Wiring - ON/OFF”, below.
TABLE 2 - Indoor & Outdoor Circulator Connections
Terminal Description
CP1 Dry contacts for circulator control
CP2
Use a 2-conductor 18ga cable.
TABLE 1 - Power Supply Connections
Line Description Voltages
L1 Line 1 All
L2 Line 2 All
L3 Line 3 All 3-phase (208-3-60, 460-3-60,
575-3-60, 380-3-50)
N Neutral No Connection
Indoor Loop Circulator Pump Wiring
The indoor loop circulator provides flow between the heat
pump and the buffer tank. In most multiple-unit commercial
installations, the circulators (and the heat pump) will be con-
trolled by the building automation system, since one circulator
may serve several heat pumps. Connect circulator pumps as
per site drawings.
If the heat pump is to control the indoor circulator, there
are dry contacts provided to control the circulator pump so that it
will be turned on whenever the compressor operates. Wire to
CP1 and CP2 on the terminal strip at the lower right side of
electrical box, as shown on the following diagram 002188CDG
and the wiring diagram (SCH) in the Model Specific Infor-
mation chapter of this manual. Ensure that the total current
draw does not exceed the value indicated on the diagram.
There is also provision for directly connecting an indoor
circulator contactor with 24VAC coil, without an external 24VAC
source. See “Indoor Water Valve Wiring - ON/OFF”, below.
The indoor circulator only will be activated at times when
the compressor is not running, when using Setpoint Control
(refer to Operation chapter of the manual). The heat pump will
start and stop indoor circulators to sample the water tempera-
ture.
Outdoor Loop Water Valve Wiring
ON/OFF: Connect a 24VAC outdoor loop water valve between
OV1 and GND (terminals DO_0 and LC on control board), as
shown on the wiring diagram (SCH) in the Model Specific In-
formation chapter. Ensure that the total current draw of all wa-
ter valves does not exceed the value indicated on the diagram.
The outdoor circulator contactor may be connected in the
same way, to avoid need for an external 24VAC transformer or
to avoid activation during sampling when using Setpoint Control.
MODULATING: Connect a 0-10VDC or PWM water valve be-
tween OV2 and GND (terminals PWM3 and GND on control
board), as shown on the wiring diagram (SCH) in the Model
Specific Information chapter. An outdoor modulating water
valve will give the control board the means to restrict the out-
door loop water flow in cooling mode on reversing units, in case
a low outdoor loop temperature causes a dip in the head pres-
sure and therefore suction pressure. This will prevent nuisance
low pressure control trips, for example when using cold open
loop well water in cooling mode. It will be closed when unit is
off, and may act to limit suction pressure due to high outdoor
loop temperature in heating mode depending on firmware revi-
sion.
The head pressure below which the modulating water
valve will start restricting water flow can be adjusted via the
Configuration page in the PC App. Default is 350 psi.
IMPORTANT NOTE FOR 3-PHASE UNITS: If
on startup compressor is noisy and not
pumping, reverse L1 and L2 supply wires.