Nordic W/WH-Series Dual Circuit Owner's manual

Category
Heat pumps
Type
Owner's manual
Maritime Geothermal Ltd.
P.O. Box 2555, 170 Plantation Road
Petitcodiac, NB E4Z 6H4
(506) 756-8135
Commercial W-Series & WH-Series
Water to Water Heat Pumps
Dual Refrigeration Circuit
Model Sizes 150-1000 (12 to 81 ton)
info@nordicghp.com
www.nordicghp.com
002097MAN-04
ISSUE 03: 18-Oct-2023
Application, Installation, & Service Manual
ISSUE 03: 18-Oct-2023 Page 2 002097MAN-04
go to TABLE OF CONTENTS
Search for any topic:
W - 400 - H - P - 2D - PP - xx
Series:
W = liquid to water
WH = high temperature liquid to water
(sizes 150-800 only)
Nominal Size:
150 = 12 ton
185 = 15 ton
240 = 20 ton
300 = 23 ton
400 = 30 ton
500 = 40 ton
600 = 50 ton
800 = 65 ton
900 = 70 ton
1000 = 81 ton
Functions:
H = Heating
AC = reversing valve (sizes 150-800 only)
W = desuperheater for DHW (sizes 150-400 only)
Refrigerant:
P = R410a (W series)
B = R134a (WH series)
Voltage Code:
1 = 208/230-1-60
2 = 208-3-60
4 = 460-3-60
5 = 575-3-60
6 = 220-1-50
7 = 380-3-50
8 = 400-3-60
Indoor Loop Exchanger:
P = brazed plate
Revision:
01, 02 etc.
Compressor:
D = dual scroll
Outdoor Loop Exchanger:
P = brazed plate
WARNING: Ensure all access panels are in place and properly secured before applying power to the unit.
Failure to do so may cause electrical shock.
WARNING: Before performing service or maintenance on the heat pump system, ensure all power sources
are DISCONNECTED. Electrical shock can cause serious personal injury or death.
WARNING: Heat pump systems contain refrigerant under high pressure and as such can be hazardous to
work on. Only qualified service personnel should install, repair, or service the heat pump.
CAUTION: Safety glasses and work gloves should be worn at all times whenever a heat pump is serviced.
A fire extinguisher and proper ventilation should be present whenever brazing is performed.
CAUTION: Venting refrigerant to atmosphere is illegal. A proper refrigerant recovery system must be
employed whenever repairs require removal of refrigerant from the heat pump.
SAFETY PRECAUTIONS
Model Nomenclature
ISSUE 03: 18-Oct-2023 Page 3 002097MAN-04
go to TABLE OF CONTENTS
Search for any topic:
APPLICATION TABLE - W-SERIES
MODEL FUNCTION REFRIGERANT VOLTAGE COMPR. OUTDOOR COIL INDOOR COIL REVISIONS
W-150 H
HAC P
1
2
4
5
6
7
D P P 05
W-185
H P 2
4
5
7
D P P 03
HAC P D P P 04
W-240
H P 2
4
5
7
D P P 02
HAC P D P P 03
W-300
H P 2
4
5
7
D P P 02
HAC P D P P 03
W-400
H P 2
4
5
7
D P P 02
HAC P D P P 03
W-500
H P 4
5
7
D P P 02
HAC P D P P 03
W-600
H P 4
5
7
D P P 02
HAC P D P P 03
W-800
H P 4
5
7
D P P 02
HAC P D P P 03
W-900 H P
4
5
7
D P P 02
W-1000 H P
4
5
7
D P P 02
Maritime Geothermal Ltd. has a continuous improvement policy and reserves the right to modify specification data at any
time without prior notice .
ISSUE 03: 18-Oct-2023 Page 4 002097MAN-04
go to TABLE OF CONTENTS
Search for any topic:
Maritime Geothermal Ltd. has a continuous improvement policy and reserves the right to modify specification data at any
time without prior notice .
APPLICATION TABLE - FIRMWARE AND PC APP
Firmware Version Associated PC APP Version
MGT GEN2 Bootload Firmware V3.60+ MGT GEN2 PC APP V2.00+
APPLICATION TABLE - WH-SERIES
MODEL FUNCTION REFRIGERANT VOLTAGE COMPR. OUTDOOR COIL INDOOR COIL REVISIONS
WH-150 H
HAC B
1
2
4
5
6
7
D P P 05
WH-185
H B 2
4
5
7
D P P 02
HAC B D P P 03
WH-240
H B 2
4
5
7
D P P 02
HAC B D P P 03
WH-300
H B 2
4
5
7
D P P 02
HAC B D P P 03
WH-400
H B 2
4
5
7
D P P 02
HAC B D P P 03
WH-500
H B 4
5
7
D P P 02
HAC B D P P 03
WH-600
H B 4
5
7
D P P 02
HAC B D P P 03
WH-800
H B 4
5
7
D P P 02
HAC B D P P 03
ISSUE 03: 18-Oct-2023 Page 5 002097MAN-04
go to TABLE OF CONTENTS
Search for any topic:
Tables & Documents 6
System Description 7
General Overview 7
1. Heating Mode 7
2. Cooling Mode 7
Installation Basics 8
Unpacking the unit 8
Unit Placement 8
General Bill of Materials 8
Wiring 9
Power Supply Connections 9
Indoor Loop Circulator Pump Wiring 9
Outdoor Loop Circulator Pump Wiring 9
Outdoor Loop Water Valve Wiring 9
Indoor Loop Water Valve Wiring 10
Control Transformer 10
BACnet Control Connections 10
Setpoint Control Connections 10
Setpoint Control: Aux. Connections 10
Signals/Hardwired Control Connections 11
Disable Switch (field installed) 11
Other Connections 11
002188CDG - Typ. GEN2 Indoor Circ. Connections 12
002067CDG - Typ. Heating Only Zone Wiring (Setpoint) 13
002069CDG - Typ. Heating Only Zone Wiring (Signals) 14
Piping & Loop Information 15
Water Loop Connections 15
Headers for Multiple Units 15
Ground Loop Systems 16
Open Loop Systems (Water Quality Guidelines) 16
Modulating Water Valve 16
002366PDG - Recommended Buffer Tank Piping 17
002367PDG - Auxiliary Boiler Piping 18
002528PDG - Buffer Tank Piping - Multiple Units 19
002240PDG - DHW with Single Wall Condenser 20
002252PDG - Two Tank Piping with a Rev. Heat Pump 21
002527PDG - 2 Tank Piping w/Multiple Rev. Heat Pumps 22
002288PDG - Two Tank Simultaneous Heating/Cooling 23
001680PDG - Two Tank Sim. Heating/Cooling (Diverting) 24
002286PDG - Geothermal Snow Melt w/Reheating 25
000530PDG - Typical Zone Types 26
Operation 27
1. BACnet Control 27
2. Signals / Hardwired Control 27
3. Setpoint Control 27
Setpoint Control Method 1 - Indoor Loop (ICR), One Tank 27
Typical Temperature Setpoints 28
Summer Setback 28
Outdoor Reset 29
Setpoint Control Method 2 - Indoor Loop (ICR), 2 Tanks 30
Setpoint Control Method 3 - External HTS/CTS, One Tank 31
a) Heat Pump Mode 31
b) Chiller Mode 32
Setpoint Control Method 4 - External HTS/CTS, 2 Tanks 33
PC Application (PC APP) 34
PC Application Menus 34
LCD Interface & Menus 47
BACnet Interface 49
Table of Contents
Startup Procedure 53
Pre-start Inspection 53
Unit Startup 54
Startup Record 55
Routine Maintenance 56
Troubleshooting Guide 57
Repair Procedures 66
Pumpdown Procedure 66
General Repair Procedure 66
Vacuuming & Charging Procedure 66
Compressor Replacement Procedure 67
Control Board Replacement Procedure 68
LCD Interface (Display) Board Replacement Procedure 69
Model Specific Information 70
Flow Rates & Volumes 70
Refrigerant Charge 70
Shipping Information 70
Operating Temperature Limits 71
Loop Pressure Drop Data 72
Standard Capacity Ratings - W-Series 74
Performance Tables (Heating/Cooling): W-150 76
Performance Tables (Heating/Cooling): W-185 77
Performance Tables (Heating/Cooling): W-240 78
Performance Tables (Heating/Cooling): W-300 79
Performance Tables (Heating/Cooling): W-400 80
Performance Tables (Heating/Cooling): W-500 81
Performance Tables (Heating/Cooling): W-600 82
Performance Tables (Heating/Cooling): W-800 83
Performance Tables (Heating/Cooling): W-900 84
Performance Tables (Heating/Cooling): W-1000 85
Performance Tables (Ice Making/Arena Application) 86
Performance Tables: WH-150 91
Performance Tables: WH-185 92
Performance Tables: WH-240 93
Performance Tables: WH-300 94
Performance Tables: WH-400 95
Performance Tables: WH-500 96
Performance Tables: WH-600 97
Performance Tables: WH-800 98
Electrical Specifications - W Series 99
Electrical Specifications - WH Series 100
Electrical Diagrams (All Voltages) 101
Refrigeration Circuit Diagrams 106
Dimensions - Without Enclosure (Sizes 150-400) 109
Dimensions - With Enclosure (Sizes 150-400) 110
Dimensions - Without Enclosure (Sizes 500-1000) 111
Dimensions - With Enclosure (Sizes 500-1000) 112
Appendix A: Control Board Description 113
Appendix B: USB Driver Installation 117
Appendix C: PC App Installation (Win11) 118
Appendix D: PC App Installation (Win10) 119
Appendix E: Updating Firmware 120
Warranty 123
ISSUE 03: 18-Oct-2023 Page 6 002097MAN-04
go to TABLE OF CONTENTS
Search for any topic:
Tables & Documents
Table 1 - Power Supply Connections .............................................................................................................. 9
Table 2 - Indoor & Outdoor Circulator Connections ......................................................................................... 9
Table 3 - Water Valve Connections ............................................................................................................... 10
Table 4 - BACnet Connections ...................................................................................................................... 10
Table 5 - Setpoint Control Connections ......................................................................................................... 10
Table 6 - Setpoint Control: Aux. Connections ................................................................................................ 11
Table 7 - Signals Control Connections .......................................................................................................... 11
Table 8a - Typical W-Series Aquastat Settings ............................................................................................. 11
Table 8b - Typical WH-Series Aquastat Settings ........................................................................................... 11
Table 9 - Loop Connection Sizes................................................................................................................... 15
Table 10 - Horizontal Headers Size for Multiple Units ................................................................................... 15
Table 11 - Buffer Tank Size ........................................................................................................................... 15
Table 12 - Water Quality Limits ..................................................................................................................... 16
Table 13a - Typical W-Series Setpoints ........................................................................................................ 28
Table 13b - Typical WH-Series Setpoints ...................................................................................................... 28
Table 14 - Typical Setpoints: HTS/CTS Method, Chiller Mode ...................................................................... 32
Table 15 - BACnet Objects - Control Signals (Read/Write) ........................................................................... 49
Table 16 - BACnet Objects - Operation Mode Description (Read Only) ........................................................ 49
Table 17 - BACnet Objects - Limits Description (Read Only) ........................................................................ 49
Table 18 - BACnet Objects - Data (Read Only) ............................................................................................. 50
Table 19 - BACnet Objects - Alarm Descriptions (Read Only) ...................................................................... 51
Table 20 - BACnet Objects - Fault Descriptions (Read Only) ........................................................................ 52
Table 21 - Flow Rates & Volumes ................................................................................................................. 70
Table 22 - Refrigerant Charge (Per Circuit) ................................................................................................... 70
Table 23 - Shipping Information .................................................................................................................... 70
Table 24a - W-Series Operating Temperature Limits .................................................................................... 71
Table 24b - WH-Series Operating Temperature Limits .................................................................................. 71
Table 25 - Loop Pressure Drop Data ............................................................................................................. 72
Table 26 - W-Series Standard Capacity Ratings ........................................................................................... 74
Table 27 - W-Series Electrical Specifications ................................................................................................ 99
Table 28 - WH-Series Electrical Specifications ........................................................................................... 100
Table A1 - Control Board Connector Descriptions (Top) ............................................................................ 114
Table A2 - Control Board Connector Descriptions (Left Side) .................................................................... 114
Table A3 - Control Board Connector Descriptions (Bottom) ....................................................................... 115
Table A4 - Control Board Connector Descriptions (Right Side) .................................................................. 116
002188CDG – Commercial W Typical ICR Connections for GEN2 Setpoint Control .................................... 12
002067CDG - Typical Zone and Auxiliary Wiring with GEN2 Setpoint Control (Heating Only) ...................... 13
002069CDG - Typical Zone and Auxiliary Wiring with GEN2 Hardwired Option (Heating Only) ................... 14
002366PDG - Recommended Hydronic Buffer Tank Piping ......................................................................... 17
002367PDG - Auxiliary Boiler Piping ............................................................................................................ 18
002528PDG - Buffer Tank Piping - Multiple Units ......................................................................................... 19
002240PDG - High Temperature Single Wall Unit Connection to DHW Tank ............................................... 20
002252PDG - Two Tank System Piping with a Reversing Heat Pump ......................................................... 21
002527PDG - Two Tank Piping with Multiple Reversing Heat Pumps ........................................................... 22
002288PDG - Two Tank Simultaneous Heating / Cooling ............................................................................ 23
001680PDG - Two Tank Simultaneous Heating / Cooling (Diverting Arrangement) ...................................... 24
002286PDG - Geothermal Snow Melt System with Warm-Weather Ground Loop Reheating ...................... 25
000530PDG - Typical Zone Types for Hydronic Applications ........................................................................ 26
001717SCH - W-150 to 1000-H***-*-*D-PP High Voltage Schematic Diagram ........................................... 101
002414SCH - W-150 to 1000-H***-*-*D-PP w/Disconnect High Voltage Schematic Diagram ..................... 102
001718SCH - W-150 to 1000-H***-*-*D-PP Schematic Diagram................................................................. 103
001719ELB - W-150 to 1000-H***-*-*D-PP Electrical Box Diagram ............................................................ 104
002415ELB - W-150 to 1000-H***-*-*D-PP w/Disconnect Electrical Box Diagram ...................................... 105
001720RCD - W-150 to W-1000-H(W) Refrigeration Circuit Diagram - Heating Mode................................ 106
001721RCD - W-Series HAC(W) (150-800) Dual Circuit Refrigeration Circuit Diagram—Heating Mode .... 107
001722RCD - W-Series HAC(W) (150-800) Dual Circuit Refrigeration Circuit Diagram—Cooling Mode .... 108
Tables
Documents
ISSUE 03: 18-Oct-2023 Page 7 002097MAN-04
go to TABLE OF CONTENTS
Search for any topic:
System Description
General Overview
These units are 2-compressor dual refrigeration circuit
water-to-water heat pumps. They have a vertical chillerstyle
design with external loop headers, for ease of passage through
doors and convenience for multiple-unit installations. They are
available in any world electrical service.
The W-series uses R410a refrigerant to achieve a stand-
ard geothermal temperature range: the outdoor loop can oper-
ate at as low a temperature as 0°F (-17°C) for ice production,
and the indoor loop can reach 130°F (54°C) leaving water tem-
perature under standard ground loop conditions.
The WH-series uses R134a refrigerant to achieve an
upward shift in temperature range: the outdoor loop requires a
minimum incoming water temperature of 45°F (7°C), so is suita-
ble for use on many open loop or heat recovery applications, or
closed ground loops in warm climates. The indoor loop can
reach 160°F (71°C) leaving water temperature.
The units are built on industrial-strength steel frames, with
removable enclosure insulated with 1” insulation. The indoor
and outdoor loop hydronic heat exchangers are both true dual
circuit stainless steel brazed plates with copper brazing. Two
single-stage scroll compressors are standard, as are two Elec-
tronic Expansion Valves (EEVs). The electronic control board
has full local unit hydronic temperature control, laptop connec-
tivity via USB with free PC App, LCD interface, electronic
readout of all pressures and temperatures, data logging & gra-
phing, and BACnet.
1. Heating Mode
In heating mode, the heat pump heats water in an indoor
loop or buffer tank, while extracting heat from an outdoor loop.
For commercial environments, heat pumps are normally
sized and the system laid out by a mechanical consulting engi-
neer. It is good practice to design the system with non-
reversing heat pumps that always use heating mode’: heating
with the hot indoor loop, and cooling with the chilled outdoor
loop. (See simultaneous heating-cooling diagrams in the Pip-
ing chapter.) Multiple units are easily installed side by side with
zero clearance using horizontal headers, to provide redundancy
as well as the ability to meet large loads. Control is normally
done using the building control system via BACnet, and includes
lead/lag stage rotation to evenly distribute the run hours be-
tween compressors. Loop circulation pumps are also centrally
controlled via BACnet.
It is also possible to use the heat pump in standalone op-
eration or in small numbers of units. In this case, hydronic tem-
perature control functionality built into the heat pump may be
used, and circulation pumps and/or water valves (either on/off or
modulating) can be powered and controlled by the heat pump.
A third control option is through dry contacts by an external ther-
mostat or controller.
Hydronic heating systems are easily zoned, and zones
may be in-floor heating, hydronic air handlers, or other hydronic
devices suitable for the water temperature. When a zone re-
quires heat, its zone thermostat calls for a zone circulator pump
or zone valve to activate, so that hot water from the buffer tank
is sent to the zone requiring heat. Note that there is no direct
connection between the zone thermostat and the heat pump,
the functions of each being separated by the buffer tank.
2. Cooling Mode (HAC models only)
Reversing valves to swap the hot and cold loops are avail-
able on model sizes up to 400 (see Application Table on page
3). When reversing valve is activated, the indoor loop or buffer
tank is chilled, and heat is rejected to the outdoor loop.
Hydronic cooling is usually done through hydronic air han-
dlers, which have condensate drains to remove water that is
removed while dehumidifying the air. In less humid climates, in-
floor or radiant cooling is sometimes performed; such systems
cant remove humidity from the air. In this case, care must be
taken to ensure the cooling surface does not fall below the dew
point temperature in order to prevent condensation on floor sur-
faces.
Four W-1000 heat
pumps with enclosures
installed, and 8”
external horizontal loop
headers
ISSUE 03: 18-Oct-2023 Page 8 002097MAN-04
go to TABLE OF CONTENTS
Search for any topic:
Installation Basics
Unpacking the Unit
When the heat pumps reach the site, they should be
unpacked to determine if any damage has occurred during
shipment. Any visible damage should be noted on the carrier's
freight bill and a claim filed.
Unit Placement
Locate the unit as per the system design drawings. The
access panels on the ends of the units should remain clear of
obstruction for a distance of 3 ft (1 m) to facilitate installation
and servicing.
Note that for multiple unit installations, horizontal headers
will connect the units on the piping end. Extra space must be
allotted for the headers, which can be of substantial size
(up to 12” in diameter). Space for external accessories must
also be planned for, e.g. strainers and valves (manual, electron-
ic, balancing, or modulating). Headers and accessories are not
included with the heat pump, and must be ordered or sourced
separately.
Since all serving can be done from the ends, no access is
required to the long side panels, which are fully removable
from the ends. This means that multiple units can be installed
side by side with minimal clearance, although if large headers
obstruct access to the piping-end panels, side clearance may be
provided to ease access to the components located there.
The heat pumps are provided with rubber mounting feet
(shipped inside electrical box), which must be installed on site.
These will preserve the frame finish and dampen vibrations
when used on solid concrete floors. Optional spring feet should
be ordered when heat pump is installed on floors with flex, e.g.
mezzanines.
General Bill of Materials
This is not an exhaustive list, but is an example of the ma-
terials that may be required for a commercial installation.
FROM MARITIME GEOTHERMAL
W/WH SERIES HEAT PUMP(S)
INSULATED ENCLOSURE(S) [STANDARD]
OPTIONAL FROM MARITIME GEOTHERMAL
SPRING FEET FOR MEZZANINE INSTALLATION
OUTDOOR TEMPERATURE SENSOR FOR OUTDOOR
RESET WHEN USING ONBOARD SETPOINT CONTROL
HOT/COLD TANK TEMPERATURE SENSORS
0-10V MODULATING WATER VALVE(S)
LOOPS (AS SPECIFIED BY SYSTEM DESIGNER)
FABRICATED HORIZONTAL HEADERS
GROOVED (VICTAULIC) FLEXIBLE COUPLINGS
STRAINERS - 16 MESH / 1 MM
ON/OFF WATER VALVES
BUTTERFLY (HAND) VALVES
BALANCING VALVES
CIRC. PUMPS, SIZED FOR REQUIRED FLOW & dP
PIPE & FITTINGS
ANTIFREEZE: METHANOL OR PROP. GLYCOL
BUFFER TANK, OPT. W/ELEMENTS __kW
SECONDARY WATER TO WATER HEAT EXCHANGERS
ZONES
ZONES CIRCULATOR(S)
ZONE TRANSFORMER & CIRC CONTACTOR
ZONE VALVES (IF NOT INDIVIDUAL PUMPS)
IN-FLOOR PIPING
OTHER AIR HANDLERS, DUCTING
ZONE THERMOSTATS
RELAYS OR ZONE CONTR. (REVERSING SYSTEMS)
ZONE SUPPLY & RETURN HEADERS
PIPE & FITTINGS TO ZONES
EXPANSION TANK
ELECTRICAL
HEAT PUMP SERVICE WIRE
BUFFER TANK ELEMENT SERVICE WIRE
HEAT PUMP BREAKER
BUFFER TANK ELEMENT BREAKER
CONTACTOR & ELEC. BOX (IF NOT WITH TANK)
THERMOSTAT WIRE 18-4
THERMOSTAT WIRE 18-2
FORK TERMINALS FOR TSTAT WIRE (6)
ISSUE 03: 18-Oct-2023 Page 9 002097MAN-04
go to TABLE OF CONTENTS
Search for any topic:
Wiring
Power Supply Connections
The heat pump electrical box and also the enclosure (if
used) have several knockouts of various sizes for the electrical
connections.
A schematic diagram (SCH) and electrical box layout
diagram (ELB) can be found on the electrical box cover of the
unit as well as in the Model Specific Information chapter of
this manual.
The Electrical Specifications in the Model Specific Infor-
mation chapter contain information about the size of wire for the
connections, as well as the recommended breaker size. These
should be checked by referencing MCA and FLA by a qualified
professional to ensure conformance to local codes. Power sup-
ply connections to the unit are made directly to the power block
inside the electrical box and are as per TABLE 1. Ground is to
be connected to the GND lug inside the electrical box.
IMPORTANT NOTE: A properly qualified
electrician should be retained for all
connections to the heat pump and associat-
ed controls. The connections to the heat
pump MUST CONFORM TO LOCAL CODES.
Outdoor Loop Circulator Pump Wiring
The outdoor loop circulator provides flow between the heat
pump and the outdoor loop. In most multiple-unit commercial
installations, the circulators (and the heat pump) will be con-
trolled by the building automation system, since one circulator
may serve several heat pumps. Connect circulator pumps as
per site drawings.
If the heat pump is to control the outdoor circulator, there
are dry contacts provided to control the circulator pump so that it
will be turned on whenever the compressor operates. Wire to
CP1 and CP2 on the terminal strip at the lower right side of elec-
trical box, as shown on the following diagram 002188CDG and
the wiring diagram (SCH) in the Model Specific Information
chapter of this manual. Ensure that the total current draw does
not exceed the value indicated on the diagram.
There is also provision for directly connecting an outdoor
circulator contactor with 24VAC coil, without external 24VAC
transformer. See Outdoor Water Valve Wiring - ON/OFF”, be-
low.
IMPORTANT: If the outdoor circulator is connected via CP1 and
CP2, it may be unnecessarily activated at times when the com-
pressor is not running, if using the Setpoint Control option
(refer to Setpoint Control chapter of this manual). Under Set-
point Control, the heat pump will start and stop indoor circulators
connected via CP1 and CP2 to sample the water temperature
when the heat pump is not operating. Therefore, if using Set-
point Control, outdoor circulators should be connected as per
Outdoor Water Valve Wiring - ON/OFF”, below.
TABLE 2 - Indoor & Outdoor Circulator Connections
Terminal Description
CP1 Dry contacts for circulator control
CP2
Use a 2-conductor 18ga cable.
TABLE 1 - Power Supply Connections
Line Description Voltages
L1 Line 1 All
L2 Line 2 All
L3 Line 3 All 3-phase (208-3-60, 460-3-60,
575-3-60, 380-3-50)
N Neutral No Connection
Indoor Loop Circulator Pump Wiring
The indoor loop circulator provides flow between the heat
pump and the buffer tank. In most multiple-unit commercial
installations, the circulators (and the heat pump) will be con-
trolled by the building automation system, since one circulator
may serve several heat pumps. Connect circulator pumps as
per site drawings.
If the heat pump is to control the indoor circulator, there
are dry contacts provided to control the circulator pump so that it
will be turned on whenever the compressor operates. Wire to
CP1 and CP2 on the terminal strip at the lower right side of
electrical box, as shown on the following diagram 002188CDG
and the wiring diagram (SCH) in the Model Specific Infor-
mation chapter of this manual. Ensure that the total current
draw does not exceed the value indicated on the diagram.
There is also provision for directly connecting an indoor
circulator contactor with 24VAC coil, without an external 24VAC
source. See Indoor Water Valve Wiring - ON/OFF”, below.
The indoor circulator only will be activated at times when
the compressor is not running, when using Setpoint Control
(refer to Operation chapter of the manual). The heat pump will
start and stop indoor circulators to sample the water tempera-
ture.
Outdoor Loop Water Valve Wiring
ON/OFF: Connect a 24VAC outdoor loop water valve between
OV1 and GND (terminals DO_0 and LC on control board), as
shown on the wiring diagram (SCH) in the Model Specific In-
formation chapter. Ensure that the total current draw of all wa-
ter valves does not exceed the value indicated on the diagram.
The outdoor circulator contactor may be connected in the
same way, to avoid need for an external 24VAC transformer or
to avoid activation during sampling when using Setpoint Control.
MODULATING: Connect a 0-10VDC or PWM water valve be-
tween OV2 and GND (terminals PWM3 and GND on control
board), as shown on the wiring diagram (SCH) in the Model
Specific Information chapter. An outdoor modulating water
valve will give the control board the means to restrict the out-
door loop water flow in cooling mode on reversing units, in case
a low outdoor loop temperature causes a dip in the head pres-
sure and therefore suction pressure. This will prevent nuisance
low pressure control trips, for example when using cold open
loop well water in cooling mode. It will be closed when unit is
off, and may act to limit suction pressure due to high outdoor
loop temperature in heating mode depending on firmware revi-
sion.
The head pressure below which the modulating water
valve will start restricting water flow can be adjusted via the
Configuration page in the PC App. Default is 350 psi.
IMPORTANT NOTE FOR 3-PHASE UNITS: If
on startup compressor is noisy and not
pumping, reverse L1 and L2 supply wires.
ISSUE 03: 18-Oct-2023 Page 10 002097MAN-04
go to TABLE OF CONTENTS
Search for any topic:
Control Transformer
The low voltage controls for 208/230-1-60 and 208-3-60
models are powered by a class II transformer with resettable
breaker on the secondary side for circuit protection. Should the
breaker trip, locate and correct the problem and then reset the
breaker by pressing in on it.
All other voltage models have a transformer with primary
and secondary fuses for circuit protection.
IMPORTANT NOTE: For 208/230VAC-1-60
units, if connecting to 208VAC power supply
move the red wire connected to the 240 ter-
minal of the transformer to the 208 terminal
of the transformer.
Setpoint Control Connections
If not using a building automation system for control, the
heat pumps built in aquastat functionality (with optional outdoor
reset) known as Setpoint Controlmay be used. Refer to the
Operation chapter of this manual for more information. If this
control method is used, it eliminates the need for an external
aquastat, and the ICR option also eliminates temperature probe
in the tank(s). It provides a three stage system along with delay
timer for the hydronic auxiliary heat.
No external control signals are required for non-reversing
H models. For reversing HAC models, a dry contact between
RA and the O signal is required to switch to cooling mode.
Drawing 002067CDG shows a typical wiring setup for zones,
zone circulator and hydronic auxiliary.
Note that for reversing models in cooling mode, it is im-
portant to choose zone thermostats or other control devices that
continuously return an Osignal, even when there is no cooling
demand. This is to avoid repeated heating and cooling of the
buffer tank on demand cycling, causing temperature lags and
high electricity consumption.
Setpoint Control does not currently incorporate any lead/
lag or other coordination between multiple units; that is, each
heat pump operates independently. A small number of units
connected to the same buffer tank may operate under Setpoint
Control by using different setpoint temperatures for each stage
of each heat pump.
TABLE 5 - Setpoint Control Connections
Signal Description
C or CA 24VAC common (ground)
R or RA 24VAC hot
O Reversing valve (HAC models only)
Use a 3-conductor 18ga cable.
An external temperature probe may be used with the on-
board Setpoint Control routine, or two probes (one for hot tank
and one for cold tank) may be used. This is HTS/CTS Setpoint
Control; see Piping and Operation chapters for details.
Setpoint Control: Aux. Connections
When using Setpoint Control, hydronic auxiliary heat is
activated with a 24VAC signal from DO_2 (HYD_AUX) on the
left side of control board.
BACnet Control Connections
In most multiple-unit commercial installations, the heat
pump will be controlled by the building automation system. If
using BACnet MS/TP for external control of heating/cooling de-
mand and/or monitoring of status, use a shielded twisted pair to
the connector at the bottom left of control board. There is an
optional termination jumper located above the connector.
See the BACnet Interface chapter for wiring tips and ob-
ject names.
TABLE 4 - BACnet Connections
Line Description
A Communication +
B Communication -
GND Ground
Use a shielded twisted pair cable.
Indoor Loop Water Valve Wiring
ON/OFF: Connect a 24VAC indoor loop water valve between
IV1 and GND (terminals DO_1 and LC on control board), as
shown on the wiring diagram (SCH) in the Model Specific In-
formation chapter. Ensure that the total current draw of all
water valves does not exceed the value indicated on the dia-
gram.
The indoor circulator contactor may be connected in the
same way, to avoid the need for external 24VAC transformer.
MODULATING: Connect a 0-10VDC or PWM water valve be-
tween IV2 and GND (terminals PWM4 and GND on control
board), as shown on the wiring diagram (SCH) in the Model
Specific Information chapter of this manual. An indoor modu-
lating water valve will give the control board the means to re-
strict the indoor loop water flow in heating mode, in case a low
indoor loop temperature causes a dip in the head pressure and
therefore suction pressure. This will prevent nuisance low pres-
sure control trips, for example in case a large zone containing
cool water opens, or in case of generally low indoor loop tem-
perature. It will be closed when unit is off (and not sampling for
Setpoint Control). On reversing HAC units in cooling mode,
valve may act to limit suction pressure due to high indoor loop
temperature depending on firmware revision.
The head pressure below which the modulating water valve
will start restricting water flow can be adjusted via the Configu-
TABLE 3 - Water Valve Connections
Control
Board
Label
Signal
Name Description
PWM4 IV2 0-10VDC control signal for indoor modu-
lating water valve
PWM3 OV2 0-10VDC control signal for outdoor mod-
ulating water valve
GND - Common/ground for IV2, OV2
DO_1 IV1 24VAC output to actuate indoor water
valve or circulation pump contactor coil
DO_0 OV1 24VAC output to actuate outdoor water
valve or circulation pump contactor coil
LC - Common/ground for IV1, OV1
Use 18ga cable.
ISSUE 03: 18-Oct-2023 Page 11 002097MAN-04
go to TABLE OF CONTENTS
Search for any topic:
The following tables show typical settings for the aq-
uastats. With these settings, stage 1 will activate when the tank
temperature reaches the activation point. If the load is too great,
the tank temperature will continue to drop when heating until
stage 2 is activated. As the tank temperature stops dropping
and begins to increase when heating, stage 2 will turn off before
stage 1, rather than at the same time as stage 1. There are
three main advantages to this:
Less aquastat probe lag leading to reduced overshoot as the
tank temperature rate of change is reduced when only stage
1 is active.
Prolonged stage 1 runtime leads to increased efficiency.
Reduced number of compressor starts.
The settings may be changed as desired; however stage 1
setpoint for heating should not exceed 130°F (54°C) for W-
series and 160°F (71°C) for WH-series; stage 1 cooling setpoint
should not be set below 43°F (6°C) for W-series and 45°F (7°C)
for WH-series. Exceeding these setpoint limits will cause the
heat pump operating pressures to approach the safety control
settings, possibly causing nuisance shutdowns.
If only floor zones are being heated, it is highly recom-
mended to drop each of the heating setpoints by 15°F (8°C)
for increased efficiency.
A buffer tank with electric elements can be used to provide
Signals/Hardwired Control Connections
Most installations will use BACnet or the Setpoint Con-
trol routine to control buffer tank temperature, in which case no
aquastat is required. However, an aquastat or aquastats can be
used if required, for example if heating two loops with different
setpoint temperatures, or using a time-of-day or other third-party
programmable controller. This is Signals or Hardwired Con-
trol.
The CA, RA, Y1A , Y2A, and O connections are located
on the right side towards the top of the control board, as shown
on the wiring diagram in the Model Specific Information chap-
ter. The external device needs to send the 24VAC signal from
RA back to the Y1A terminal to call for compressor 1, to the
Y2A terminal to call for compressor 2, and to O to select cooling
mode (reversing HAC models only). CA is the common or
TABLE 7 - Signals Control Connections
Signal Description
CA 24VAC common (ground)
RA 24VAC hot
O* Cooling mode (reversing valve both stages)*
Y1A Compressor #1 (bottom)
Y2A Compressor #2 (top)
* HAC models only
TABLE 6 - Setpoint Control: Aux. Connections
Signal Description
LC 24VAC common (ground)
DO_2 Hydronic Auxiliary (hot)
Use a 2-conductor 18ga cable.
Disable Switch (field installed)
A switch or dry contact to disable demand from the con-
trol system may be installed. On control board, jumper COM_IN
to GND, and toggle 12VDC to IN_SPARE to disable. See wiring
diagrams in the Model Specific Information chapter.
Other Connections
An accessory outdoor temperature sensor is available, to
enable Setpoint Controls Outdoor Reset functionality.
Dry contacts to separately indicate stage 1 and stage 2
alarms are available, as is an L24VAC trouble indicator signal.
See wiring diagram in the Model Specific Information
chapter for details.
This powers the coil of an external contactor to operate
hydronic auxiliary heat. This signal can provide a maximum
of 500mA at 24VAC. If using an auxiliary heating device with
its own controller and transformer that requires dry contacts to
activate, a relay with 24VAC coil must. be added.
TABLE 8a - Typical W-Series Aquastat Settings
HEATING
Stage 1
(aquastat)
Stage 2
(aquastat)
Stage 3
(tank controller)
°F °C °F °C °F °C
Setpoint 108 42 105 41 100 38
Delta 8 4 8 4 8 4
Activation * 100 38 97 37 92 34
Delay 10 minutes
COOLING Stage 1 Stage 2
*Activation is
determined by
the Setpoint and
Delta values
°F °C °F °C
Setpoint 45 7 48 9
Delta 8 4 8 4
Activation * 53 11 56 13
auxiliary heat. When using Hardwired Control, a mechanical
tank element thermostat can be set to maximum, allowing the
electric elements to be controlled by an external contactor
placed in the power supply connections; the contactor can be
connected to stage 2 of the heating aquastat via an optional 0-
2hour timer. Or if the tank has an electronic controller, it can be
set to run according to its own setpint, which should be set lower
than that of the heat pump. Diagram 002069CDG show a typi-
cal wiring setup for zones, zone circulator, and hydronic auxiliary
for a heating only system.
Note that for reversing models in cooling mode, it is im-
portant to choose zone thermostats or other control devices that
continuously send an Osignal, even when there is no cooling
demand. This is to avoid repeated heating and cooling of the
buffer tank on demand cycling, causing temperature lags and
high electricity consumption.
TABLE 8b - Typical WH-Series Aquastat Settings
HEATING
Stage 1
(aquastat)
Stage 2
(aquastat)
Stage 3
(tank controller)
°F °C °F °C °F °C
Setpoint 150 66 147 64 130 54
Delta 8 4 8 4 20 10
Activation * 142 62 139 60 110 44
Delay 10 minutes
COOLING Stage 1 Stage 2
*Activation is
determined by
the Setpoint and
Delta values
°F °C °F °C
Setpoint 45 7 48 9
Delta 8 4 8 4
Activation * 53 11 56 13
ISSUE 03: 18-Oct-2023 Page 12 002097MAN-04
go to TABLE OF CONTENTS
Search for any topic:
ISSUE 03: 18-Oct-2023 Page 13 002097MAN-04
go to TABLE OF CONTENTS
Search for any topic:
ISSUE 03: 18-Oct-2023 Page 14 002097MAN-04
go to TABLE OF CONTENTS
Search for any topic:
ISSUE 03: 18-Oct-2023 Page 15 002097MAN-04
go to TABLE OF CONTENTS
Search for any topic:
TABLE 11 - Buffer Tank Size
Heat Pump
Size
Minimum Size
gal (L)
Recommended Size
gal (L)
150 100 (380) 120 (450)
185 130 (500) 180 (680)
240 160 (600) 200 (750)
300 200 (750) 250 (950)
400 250 (950) 300 (1100)
500 320 (1200) 400 (1500)
600 400 (1500) 500 (1900)
800 520 (2000) 600 (2300)
900 560 (2100) 600 (2300)
1000 648 (2450) 800 (3000)
TABLE 9 - Loop Connection Sizes
Model Size Connection Size (SS grooved/Victaulic)
150
2” (51 mm)
185
240
300
400
500
3” (76 mm)
600
800
900
1000
Piping & Loop Information
Water Loop Connections
The Outdoor Loop (Supply) and Indoor Loop (Hot) con-
nections are stainless steel pipe designed for Victaulic connect-
ors. The connection sizes are shown in the following table.
Piping should be done as per the system piping diagram as well
as local codes. It is recommended that all piping be insulated to
prevent condensation. All piping connected to the unit must be
sufficiently externally supported so as not to strain the heat ex-
changer connections.
To avoid fouling of the brazed plate heat exchangers, a
strainer is required on each loop IN connection. The strainer
should be specified to stop particles larger than 1 mm, and cor-
responds to a mesh size of 16-20 depending on wire diameter.
For closed loops, the strainer may be able to be removed after
startup and commissioning is complete and a cleaned filter
shows no removed particles after 1 week of operation.
Each port has a temperature sensor. The output is shown
on the LCD Interface on the unit and may also be viewed via the
PC APP. There is also a P/T port installed in each line, for
measuring pressure drop for flow rate estimation. Both of the
OUTports have a flow switch on reversing models; only on the
outdoor loop for non-reversing models.
Buffer tank sizing should be as per the engineering specifi-
cations for the jobsite. However, the minimum buffer tank
size should follow the rule of 8 US gallons per ton of heat
pump capacity to avoid problems with short-cycling the
heat pump(s). The table shows the minimum buffer tank size
for each heat pump along with the recommended size. The
recommended size will provide longer runtimes and fewer starts
for improved efficiency.
IMPORTANT NOTE: Units are shipped configured for water
for both the indoor and the outdoor loop. This prevents the
heat exchangers from freezing when a low pressure alarm
occurs regardless of the fluid type and mixture in the sys-
tem loops. During startup the fluid type and mixture for
both the indoor and outdoor loop must be configured via
the PC APP using the Tools - Configuration menu. (There is
no need for antifreeze with WH-series due to source tem-
perature limitation of 45°F / 7°C.)
WARNING: ENSURE FLUID TYPE SETTING ARE
ACCURATE. FAILURE TO DO SO COULD
CAUSE THE HEAT EXCHANGER TO FREEZE
AND RUPTURE, DESTROYING THE HEAT PUMP
AND VOIDING THE WARRANTY.
WARNING: REPEATED RESETS OF A LOW
PRESSURE LOCKOUT COULD CAUSE THE
HEAT EXCHANGER TO FREEZE AND RUP-
TURE, DESTROYING THE HEAT PUMP AND
VOIDING THE WARRANTY.
TABLE 10 - Horizontal Header Size for Multiple Units
Number of
Heat Pumps
Heat Pump Con-
nection Size
Min. Nominal SCH40
Pipe Size for Header
2 2” (51 mm) 3”
3” (76 mm) 5”
3 2” (51 mm) 4”
3” (76 mm) 6”
4 2” (51 mm) 5”
3” (76 mm) 8”
5 2” (51 mm) 5”
3” (76 mm) 8”
6 2” (51 mm) 6”
3” (76 mm) 8”
7 2” (51 mm) 6”
3” (76 mm) 10”
2” (51 mm) 6”
8 3” (76 mm) 10”
Headers for Multiple Units
Horizontal headers with equally spaced side connections
for multiple units may be fabricated by the mechanical contrac-
tor (the usual practice), or ordered with the heat pumps. In ei-
ther case, detailed plans and a list of required accessories
(strainers, valves) must be provided.
The header pipe must have at least the capacity of all the
heat pump connections combined. See the following table for
minimum header sizes.
ISSUE 03: 18-Oct-2023 Page 16 002097MAN-04
go to TABLE OF CONTENTS
Search for any topic:
Modulating Water Valve
A 0-10VDC modulating motorized water valve controlled
by the Gen2 control board in the heat pump may be required on
the indoor or outdoor loops depending on transient or steady
state loop operating temperatures. See Wiring chapter, and the
Operating Temperature Limits table in the Model Specific
Information chapter.
The modulating water valve is available as an accessory
from Maritime Geothermal Ltd., and can be installed on either
the loops IN or OUT connections at the heat pump. Depending
on size, valve connections may be threaded or flanged, and
two grooved (Victaulic) adapters should be used per valve.
Note that where installed, the modulating water valve will
act as the water shutoff valve, and no additional solenoid valve
is required.
CAUTION: if a modulating water valve is not
installed where its use is indicated, nuisance
low pressure control trips may occur.
Ground Loop Systems
Note that in northern climates, only the W-series is suita-
ble for use with a closed ground loop (WH is generally not suita-
ble due to its minimum required source temperature of 45°F/7°
C).
Commercial ground loop design is beyond the scope of
this manual, and is normally performed by mechanical consult-
ing engineering firms. For concept stage planning, it may be
considered that approximately one vertical loop of 150 ft depth
per nominal ton of heat pump capacity will be required; or there
can be a smaller number of deeper wells. Note that a different
borehole length per ton may be required if ground conductivity
or load balance vary from the average, and that due to the cost
of a commercial installation, a test well to measure ground con-
ductivity is often drilled before ground loop design is finalized.
Loops must be placed far enough apart to avoid excessive ther-
mal interference, e.g. 20 ft / 6 m apart. Loops are normally
headered together underground, with care taken to size the
headers properly so that purging of air is possible with reasona-
bly sized pumping equipment.
Note that adequate freeze protection for the loop fluid is
required. The proper type and quantity of antifreeze must be
added to the ground loop as per the system design.
WARNING: It is recommended that enough
antifreeze be added to allow for a temperature
20°F (11°C) lower than the expected lowest
loop fluid temperature entering the heat pump.
It is important to size ground loop circulation pumps to
deliver the required flow as listed in the table in the Model Spe-
cific Information chapter, considering the expected pressure
drop of the antifreeze mixture used through the heat pumps and
ground loop and all accessories. Low flow rate due to under-
sized circulation pumps causing low heat pump performance or
safety control trips is a common problem when commercial pro-
jects are commissioned.
Once the antifreeze solution has been added to the ground
loop and all air has been purged from the system, the entire
ground loop can be pressurized to the appropriate value as per
the system design requirements. If possible, the ground loop
circulators should be tested prior to starting the heat pump to
ensure that the loop is functioning properly.
Open Loop Systems
The temperature of the well water for open loop installa-
tions should be a minimum of 42°F (6°C) for the W-series and
45°F (7°C) for the WH-series. Refer to the Model Specific
Information chapter for a complete table of temperature opera-
tion limits.
Discharge water from the heat pump should be disposed
of as per the system piping diagram and local codes. Most
commonly, a return well will be required.
Open loop systems will require an ON/OFF or modulating
water valve to shut off the water flow when heat pump is not
running.
Water Quality Guidelines
The well water should be tested to be sure it meets mini-
mum standards. Poor water quality can lead to rapid heat ex-
changer failure or frequent servicing.
The well should not produce any sand. Sand will physically
erode heat exchanger surfaces, and quickly clog return
(injection) wells. Solids or TDS should be less than 1 ppm (1
mg/L) if a return well is used.
To avoid scale formation on the inside of the heat pumps
outdoor loop coil, total hardness should be less than 350 ppm /
350 mg/L. In practice, scaling is very rarely a problem at north-
ern groundwater temperatures of 50°F or less because scale
does not generally form at low well water temperatures (unlike,
for example, in a domestic hot water tank). In more southern
climates, the hardness guideline will be a more important con-
sideration. Should scale form, heat pump performance will
gradually deteriorate, and will require periodic flushing with a
calcium/lime removing solution (see Routine Maintenance).
Corrosive (salty) water is a concern, since although the
brazed plates are made of corrosion-resistant 316SS, the cop-
per brazing is susceptible to attack by chlorides. The water
should be tested and fall within the limits in the following table.
If it doesnt, the use of an open loop system should be reconsid-
ered.
TABLE 12 - Water Quality Limits
Water Property Should be
Chlorides < 300 ppm
pH > 7.5
Ammonia (NH3) < 2 ppm
Hydrogen Sulfide (H2S) < 0.05 ppm
Sulfate (SO42-) < 70 ppm
Solids (TDS) < 1 ppm
Hardness < 350 ppm
Note that mg/L = ppm, and see notes above table.
ISSUE 03: 18-Oct-2023 Page 17 002097MAN-04
go to TABLE OF CONTENTS
Search for any topic:
ISSUE 03: 18-Oct-2023 Page 18 002097MAN-04
go to TABLE OF CONTENTS
Search for any topic:
ISSUE 03: 18-Oct-2023 Page 19 002097MAN-04
go to TABLE OF CONTENTS
Search for any topic:
ISSUE 03: 18-Oct-2023 Page 20 002097MAN-04
go to TABLE OF CONTENTS
Search for any topic:
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123

Nordic W/WH-Series Dual Circuit Owner's manual

Category
Heat pumps
Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI