DL300 Series Universal Low-Power Inverter
Chapter 3 Inverter Wiring
3.1 Wiring precautions
(1) Make sure intermediate circuit breaker is connected between
the frequency inverter and power supply to avoid expanded
accident when the frequency inverter is faulty.
(2) In order to reduce electromagnetic interference, please
connect surge sorber on the coil of electromagnetic contactor,
relay and etc. in the surrounding circuit of the frequency
inverter.
(3) Please use shielded wire of above 0.3mm² for the wiring of
such analog signals as frequency setting terminal AI and
instrument loop (AO), etc. The shielding layer shall be
connected on the grounding terminal E of the frequency
inverter with wiring length less than 30m.
(4) The stranded wire or shielded wire of above 0.75mm² shall
be selected for the wiring of input and output loop (X1-X4) of
relay; and the shielded layer shall be connected to the
common port CM of control terminals, with wiring length
less than 50 m.
(5) The control wire shall be separated from the power line of
major loop;it shall be at a distance of above 10cm for parallel
wiring and vertical for cross wiring.
(6) The connecting wire between the inverter and the motor shall be
less than 30m; and when it is longer than 30m, the carrier
frequency of the inverter shall be appropriately reduced.
(7) All leading wires shall be fully fastened with terminals to ensure
good contact.
(8) The pressurization of all the leading wires shall be in
compliance with the voltage class of the frequency inverter.
Absorption capacitor or other RC absorbers shall not be
installed at U, V and W output end of the frequency
inverter, as shown in figure 3-1.