Contura C i4 Operating instructions

Category
Stoves
Type
Operating instructions

This manual is also suitable for

Installation
Instructions
Ci4
For use in GB and IE only
contura.eu
GB
102
Declaration of performance according
to Regulation (EU) 305/2011
No. Ci4-CPR-130619-SE-1
DECLARED PERFORMANCE
Essential characteristics Performance Harmonised technical
specification
Reaction to fire NPD
Minimum distance to combustible material Rear: 150 mm
Side: 150 mm
According to the given conditions in the installa-
tion instructions
Risk of falling embers Pass EN 13229:2001 / A2:2004
Emissions from combustion
Wood / (Coal briquettes)
CO 0,10% / (0,21%)
Surface temperatures Pass
Cleaning options Pass
Mechanical durability Pass
Emissions of hazardous substances Pass
Nominal output 4 kW / (4 kW)
Efficiency 78% / (76%)
Flue gas temperature in connector at nominal
output
310°C / (270°C)
PRODUCT
Product type Insert lit with solid biofuels
Type designation Contura i4
Manufacturing number See rating plate on the insert
Intended area of use Heating of rooms in residential buildings
Fuel Wood / (Coal briquettes)
MANUFACTURER
Name NIBE AB / Contura
Address Box 134, Skulptörvägen 10
SE-285 23 Markaryd, Sweden
CHECKS
According to AVCP System 3
European standard EN 13229:2001 / A2:2004
Test institute Rein-Ruhr Feuerstätten Prüfstelle, NB 1625,
has checked declared performance and issued test report no. RRF-29 11 2751
The undersigned is responsible for the manufacture and conformity with the declared performance.
Niklas Gunnarsson,
Business area manager NIBE STOVES
Markaryd, 1st July 2013
CERTIFICATE
GB
103
Table of contents
Technical data 104
Dimensions 105
Recessing the insert 106
Recess example 107
Installation in Builders opening 108
Supply of combustion air 108
Prior to installation 109
Installing and connecting the convection box 110
Smoke control area 113
Installing stove body into the convection box 114
Installing fire box insulation panels 116
A warm welcome to Contura.
A warm welcome to the Contura family. We hope
you will get a great deal of pleasure from your new
stove. As a new owner of a Contura stove you have
secured a product with timeless design and long
service life. Contura also has combustion that is both
environmentally friendly and efficient for the best heat
production.
Read through these installation instructions carefully
before installation. Read how to best light your stove in
the lighting instructions.
NOTE!
Report the installation of a stove to
your local authority.
The owner of the house is personally responsible
for ensuring compliance with the mandatory safety
requirements and must have the installation approved by
a qualified inspector. Your local chimney sweep must also
be informed about the installation as this will affect the
routines for regular chimney-sweeping services.
WARNING!
The stove becomes very hot.
During operation, certain surfaces of the stove become
very hot and can cause burn injury if touched. Be aware
of the strong heat radiated through the hatch glass.
Placing flammable material closer than the safe distance
indicated may cause a fire. Smouldering can cause quick
gas ignition with the risk of damage to property and
personal injury.
CONTENTS
GB
104
Handle
(removable on modern)
FACTS
Building application
Before installing a stove or erecting a
chimney it is necessary for you to apply
for planning permission from your local
authority. Ask your local authority for
advice regarding building regulations and
the application.
Technical data
Output 3-5 kW
Nominal output 4 kW
Efficiency level Up to 78%
Model Classic
Weight (kg) 77
Width (mm) 490
Depth (mm) 420
Height (mm) 600
Model Modern-3-sided frame
Weight (kg) 71
Width (mm) 490
Depth (mm) 380
Height (mm) 590
Model Modern-4-sided frame
Weight (kg) 72
Width (mm) 490
Depth (mm) 380
Height (mm) 635
The connector’s inner diameter is Ø126 mm
Type approved in accordance with:
European standard EN-13 229
(DE/A) DINplus, Art. 15a B-VG
RRF-29 11 2751
DEFRA exempted
The stove can be used in Smoke Control
Areas.
Fire-box insulation panels
Convection box
Grate
Ash-pan
Log guard
Type plate
Primary air
inlet control
Secondary air
inlet control
WOOD
COAL
Chimney
Note! The stove installation and connection
to a chimney must be accomplished with
the current edition of Building Regulations.
We recommend that you consult a local
chimney sweep before the installation
to make sure that the chimney is in good
condition.
The stove is type approved and must be
connected to a chimney dimensioned
for at least 350°C. The connector on
the appliance is suitable for pipes with
diameter of 125 mm.
A flexible flue liner or steel flue
certified for use with solid fuel is highly
recommended. The stove requires a
draught in the chimney of at least –12
Pa. The draught is affected both by the
length and area of the chimney, and by how
well sealed it is. Minimum recommended
chimney length is 3.5 m and a suitable
cross section area is 120-175 cm² (125-
150 mm in diameter). Carefully check that
the chimney is sealed and that there is
no leakage around soot hatches and flue
connections.
Note that a flue with sharp bends and
horizontal routing reduces the draught in
the chimney. Maximum horizontal flue is 1
m, on the condition that the vertical flue
length is at least 5 m. It must be possible
to sweep the full length of the flue and the
soot hatches must be easily accessible.
General
In this manual you will find instructions
about how your Contura i4 shall be
installed. Before you start the installation
it is important that you read this
instruction carefully and fully understand
the requirements. All European, national
and local standards and regulations needs
to be fulfilled when the appliance are
installed.
To guarantee the function and safety of
the stove we recommend that it is installed
by a professional. Our Contura agents can
recommend a suitable installer.
The room or space containing a stove shall
have a permanent air supply sufficent to
ensure proper combustion, to determine
correct amount of air supply use current
edition of Building Regulations.
Remember to use only for the appliance
recommended fuel as wood logs
or smokeless fuel as anthracite or
manufactured smokeless fuel briquettes.
Do not ever burn bituminous coal, “petro-
coke” or other petroleum based fuels!
GB
105
Dimensions
DIMENSIONS
Ci4
580
530
300
45°
40
390
350
420
490
600
550
300
255
60
40
50
490
590
580
530
300
45°
40
550
300
255
60
40
45
390
350
380
415
390
350
380
415
490
635
580
530
300
45°
40
550
300
255
60
40
45
45
Ci4 Classic
Ci4 Modern 3 - sided frame
Ci4 Modern 4 - sided frame
Flue outlet 45° backwards
Flue outlet 45° backwards
Flue outlet 45° backwards
GB
106
When recessing the insert, adjacent walls that are not classed as fire walls or are considered unsuitable for heat loads must be protected
by non-combustible material according to the specification below.
All joints on the non-combustible material must be sealed using the manufacture’s recommended method. The area between the insert
and the recess must be ventilated according to the specification/dimension.
When top connecting a steel flue please refer to the relevant manufacturers installation instructions. Observe the safety distances to
combustible material that steel flues require. Heat radiation from the hatch is strong and is why combustible material must not be placed
closer than 1 m in front of the hatch. When recessing, building material must not be in direct contact with the insert due to the thermal
expansion of the insert.
Material requirements
The building material must not be combustible.
The thermal conductivity coefficient
λ may be a maximum of 0.14 W/mK.
The thickness of the building material must always be at least 100 mm.
In cases where the building material’s insulation properties are given as a U-Value, this must be a maximum of 1.4 W/ m²K.
List of suitable materials:
Aerated concrete:
λ =0.12-0.14
Vermiculite:
λ =0.12-0.14
Calcium silicate: λ =0,09
Recessing the insert
Heat shield
If the recess is to extend to the ceiling, a heat shield must be made above the convection exhaust. This is to prevent hot air collecting in
the recess closest to the ceiling. The seal must a maximum of 100 mm above the convection exhaust’s upper edge and must be made up
of 20 mm thick building boards made of calcium silicate or a panel with at least a 50 mm thickness of rock wool on top.
Convection air
The convection air ventilates the surround, cools the insert and transports the hot air out into the room. The total sum of the effective
cross section area up and down must not be less than the stated values. The air intake must be positioned somewhere between the floor
and the bottom of the insert, up to or on the sides of the recess. The vent must be positioned above the insert’s highest point up to or to
the sides of the recess.
Observe the minimum distance up to the ceiling.
Convection air in: 200 cm²
Convection air out: 200 cm²
Note that building regulations apply regarding the area below and in front of the insert, see section ”Hearth plate” below.
Load bearing base
Ensure that the bottom of the convection box is installed on a loadbearing with the strength to support the weight of the insert and the
chimney. The insert can be loaded maximum 100 kg of chimney. The load bearing must not prevent the convection air ventilate the area
between the insert and recsess.
Hearth plate
Due to the risk of falling embers, a flammable floor must be protected by a hearth plate. It must extend 300 mm in front of the stove
and 100 mm on each side of the stove, or have a 200 mm extension on each side of the opening. The hearth plate can consist of natural
stone, concrete, metal plate or glass, consult the Building regulations.
RECESSING THE INSERT
GB
107
RECESS EXAMPLE
Ci4
Recess example
50
800
100
50
100
300
50
100
50
100
50
50
100
300
500
20
max 100
50
100
100
800
300
20
Area out min. 200 cm
2
Heat shield
Area in min. 200 cm
2
Load bearing base
50
100
Ci4 Classic and Modern
20
100
100
500
Wall of combustible material
600
20
100
100
100
Wall of non-combustible material, made
of 100 mm aerated concrete in the recess
example.
20
100
100
500
Wall of non-combustible material that is
not in contact with combustible material
and therefore has no minimum thickness
requirement.
The dimensions are the
minimum dimensions,
unless otherwise stated.
!
GB
108
Hearth dimensions
The appliance must stand on a constructional hearth which meet
the building regulations and has minimum dimension as shown in
the diagram beside. Always check that the building has enough
bearing capacity for the heart, stove and chimney. The stove can
be loaded with maximum 100 kg of chimney.
790 mm
150 mm
125 mm
150 mm
450 mm
Installation in Builders opening
Supply of combustion air
When a stove is installed in a room, the demand for air supply to
the room increases. Air can be provided indirectly via a vent in the
outer wall or via a duct from the outside that is connected to the
stove. The amount of air needed for combustion is approximatly
20m³/h.
If the insert will be used with supply air connector (accessory)
and outside air-supply kit (accessory) then prepare the convection
box by open the lid where the air supply hose will enter, from side
or back. Make the supply air connector installation as the flue pipe
is connected to the convection box.
Outside air-supply kit (accessory)Supply air connector (accessory)
INSTALLATION / COMBUSTION AIR
GB
109
Prior to installation
Remove loose components as stove base plate and ash tray. Take
out the stove body from the convection box by first unscrew the
four side bolts and the four bolts for the collar. At last release the
convection box from the pallet.
x4
x4
1
3
2
4
LEK
10
10
VANADIUM
No. 7
CHROME
!
PREINSTALLATION
GB
110
Flue collar 90° straight upwards or 45° backwards
Straight upwards 45° backwards
Installing and connecting the convection box
1a 1b
If the builders opening is too tight above when the flue collar adapter
plate is turned for installation 45° backwards, then remove and fasten
the flue collar adapter on the flue. Install the convection box and finally
fasten the flue adapter on the convection box, see “Flue collar 45°
backwards and tight builders opening” on side 112.
180°
INSTALLING AND CONNECTING
2a
2b
GB
111
5 6
13
13
VANADI UM
No. 7
CHROME
LEK
Ø 6 mm
3
4
INSTALLING AND CONNECTING
GB
112
Flue collar 45° backwards and tight builders opening
4
1
65
2
3
LEK
Ø 5 mm
INSTALLING AND CONNECTING
GB
113
1
2
In smoke control areas it is mandatory to stop the damper from
closing completely. In other areas it´s optional.
Smoke control area
SMOKE CONTROL AREA
GB
114
x4
x4
3 4
Installing stove body into the convection box
x4
1 2
Classic - fasten the screws properly after the
stovebody is fitted to the backpanel
Modern - fasten the screws only a few turns,
they shall be fasten properly first when
the cast iron frame are assembled and fitted,
see side 115.
LEK
10
10
VANADIUM
No. 7
CHROME
!!
INSTALLING STOVE BODY
GB
115
Modern frame
3 4
1 2
13
13
VANADI UM
No. 7
CHROME
13
13
VANADI UM
No. 7
CHROME
INSTALLING STOVE BODY
Make sure that the stovebody
and frame are parallel before
fasten the screws
!
GB
116
Installing fire box insulation panels
1
2
INSTALLING FIRE PANELS
The Thermotte insulation panels are fragile, handle them with care and
be careful when placing them into the stovebody.
GB
117
Final inspection of the installation
It is very important that the installation is inspected by an authorised chimney sweep before the
stove is used. Also read the ”Operating instructions”, before lighting for the first time.
3 4
5
INSTALLING FIRE PANELS
!
811163 IAV Ci4 SE_EX-7
2
018-07-05
NIBE AB · Box 134 · 285 23 Markaryd · Sweden
www.contura.eu
Contura reserves the right to change dimensions and
procedures described in these instructions at any
time without special notice. The current edition can be
downloaded from www.contura.eu
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Contura C i4 Operating instructions

Category
Stoves
Type
Operating instructions
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI