Danfoss GP coils Installation guide

Type
Installation guide
Installation Guide
Coil for solenoid valves
Type GPU
© Danfoss A/S (AC-MCI/MWA) 2013-07 DKRCC.PI.BS0.A1.02 1
032 R9793
032 R9793
ENGLISH
General instructions
1. Danfoss type GPU coils may only be used with
Danfoss solenoid valves.
2. No tools are needed for installation.
3. Always verify your selection of correct coil
voltage and frequency by comparing label data
for the coil you are replacing with the data
from the label of your new coil.
4. Always disconnect electrical power before
removing a coil from a valve, and never
connect power to a coil until it is installed on a
valve armature. Failure to observe these rules
will cause the coil to burn out and may cause
bodily injury.
5. All wiring must comply with applicable
national and local electrical codes. Note that
many codes require fusing of coils for over-
curent protection.
If fuses are required, they should not exceed
2 amperes for coils rated less than 50 volts, and
should not exceed 1 ampere for coils rated
50 volts or more.
6. Coil installation (see g.1)
7. Coil removal (see g. 2)
•Disconnectlinevoltage
Note 1:
It is recommended to install the delivered o-ring
on armature tube to reduce vibrations from coils.
Note 2:
Press the latch until you hear/feel a click indicting
that the latch is locked onto the armature tube.
1 2
On
Danfoss
32F904.10
On
A
B
Danfoss
32F903.10
Danfoss
32F905.10
A
B
2 DKRCC.PI.BS0.A1.02 © Danfoss A/S (AC-MCI/MWA) 2013-07