Pulsar PSUPS10A12 Operating instructions

Type
Operating instructions

Pulsar PSUPS10A12 is a 13.8V/12V/10A/40Ah buffer power supply unit designed for uninterrupted power supply of CCTV cameras. It features 8 dedicated outputs for supplying CCTV 12V DC (8x0.5A) and 1 dedicated 12V/5A output for supplying a recorder.

Pulsar PSUPS10A12 is a 13.8V/12V/10A/40Ah buffer power supply unit designed for uninterrupted power supply of CCTV cameras. It features 8 dedicated outputs for supplying CCTV 12V DC (8x0.5A) and 1 dedicated 12V/5A output for supplying a recorder.

PSUPS 10A12
v.1.1
PSUPS 13,8V/12V/10A/40Ah Buffer power supply unit
EN
Edition: 2’st from 03.02.2012
Supercedes edition: 1’st from 20.09.2011
www.pulsar.pl PSUPS10A12
2
Features of the power supply unit
:
12 VDC uninterruptible power supply
Dedicated 8 outputs for supplying CCTV
12V DC (8x0,5A)
Dedicated 1 output 12V/5A(1x5A) for supplying
recorder
Controlling of battery charging and maintaining
Protecting of battery against excessive
discharging (UVP)
Securing the BAT outlet against short-circuit and
reverse connection
Possibility of select battery charging current 0,7A;
2,1A; 3,6A; 4,8A.
START function of manual battery actuation
LED optical signalisation: AC and DC
BS outlet for the signalling of the 230V network
AW output of power supply unit failure, tripped by:
outlet short-circuit (SCP)
outlet overload (OLP)
battery disconnection < 10V (UVP)
failure of DC/DC voltage converter
Safety equipment:
SCP short-circuit protection
OLP overload protection
OHP overheat protection
OVP overvoltage protection
Overvoltage
Against sabotag
CONTENTS:
1. Technical description
1.1. General description
1.2. Block diagram
1.3. Description of elements and power supply connectors
1.4. Technical parameters
2. Installation.
2.1. Requirements
2.2. Installation procedure
3. The power supply operation indication
3.1. Optical indication
3.2. Technical output
4. Service and operation
4.1. Overload or short circuit
4.2. Overload or short-circuit in the output of recorder module or CCTV cameras module
4.3. Battery assisted operation
4.4. Maintenance
1. Technical description
1.1. General description
The buffer power supply is used for uninterrupted supply of CCTV cameras requiring stabilized voltage of
12V DC (+/-15%). The power supply is equipped with 2 circuits: first 12V DC 5A for supplying the register, second
8 x 0,5A/12VDC for CCTV cameras. Battery charging current – set on 0,7A. In case of power voltage decay,
prompt switching to battery supply occurs.
During the normal operation, the sum of currents collected by receivers shall not exceed I=10A
(P=138W max.), including the maximum battery charging current Ibat.
1. Output current 9.3A + 0,7A battery charging
2. Output current 7,9A + 2,1A battery charging
3. Output current 6,4A + 3,6A battery charging
4. Output current 5,2A + 4,8A battery charging
The power supply has got a metal casing (RAL 9003 colour) with a space for 40Ah/12V battery. The casing
features a micro-switch indicating door (front) opening and separating from the wall.
www.pulsar.pl PSUPS10A12
3
1.2. Block diagram (fig.1).
Fig.1. Block diagram of the power supply unit.
www.pulsar.pl PSUPS10A12
4
1.3. Description of elements and connection links of the power-supply unit (tab.1, tab.2, fig.2, fig.3).
Table 1.
Element no.
[Fig. 2]
Description
[1] F1 fuse in the battery circuit
[2] START pushbutton (power-supply activation from the battery)
[3]
J, jumper - configuration of UVP battery protection function
J = protection function (disconnection) of the battery off
J = protection function (disconnection) of the battery on
Legend:
jumper installed, jumper removed
[4] P1 potentiometer, DC voltage adjustment
[5]
+AUX-
+AUX1-
+AUX2-
+AUX3- Outputs for DC power supply (+AUX= +U, -AUX=GND)
[6] O1, O2, O3, AUX - optical signalisation of power supply operation
[7] AC - LED diode that indicates the presence of AC voltage
[8] LB - LED diode that indicates battery charging
[9] OVP - LED diode that indicates the activation of the OVP overvoltage protection
[10]
J1, J2, jumpers battery charging current configuration
J1= J2= Ibat =0.7A
J1= J2= Ibat =2.1A
J1= J2= Ibat =3.6A
J1= J2= Ibat =4.8A
Factory setting 0,7A
Legend:
jumper installed jumper removed
[11]
+BAT - DC power supply output of the battery
(+BAT = red, -BAT = black)
[12]
BS - technical output of AC shortage OC type
hi-Z level = status: AC power supply
L level = status: AC power supply failure
[13]
AW - failure technical output – OC type
Activation: SCP, OLP, UVP, converter failure
L level = status: correct operation
hi-Z level = status: failure, overload
[14] LED signalisation connection
Tab.1. Elements of the PCB board of the power-supply unit (refer to fig.2).
www.pulsar.pl PSUPS10A12
5
Fig.2. View of the PCB board of the power-supply unit.
Table 2.
Element no.
[Fig. 3]
Description of outputs of the power-supply unit
[1] Separation transformer
[2] Power-supply unit board (tab. 1)
[3] TAMPER micro-switch (contacts) of the anti-sabotage protection (NC)
[4] F2 fuse in the power supply circuit (230VAC)
[5]
L-N 230VAC power supply connection, PE protection connection
[6] Battery connectors +BAT = red, - BAT = black
[7] Fuse block of recorder – 1 x 12V/ 5A output
[8] Recorder voltage regulation (11-13,8V DC), factory setting: 12V/ DC
[9] Fuse block of CCV cameras – 8x12V/ 0,5A outputs
[10] CCTV cameras voltage regulation (11-13,8V DC), factory setting: 12V /DC
Tab.2.
Elements of the power-supply unit (refer to fig. 3).
www.pulsar.pl PSUPS10A12
6
Fig.3 View of the power-supply unit.
www.pulsar.pl PSUPS10A12
7
1.4. Technical parameters:
- electrical parameters (tab.3)
- mechanical parameters (tab.4)
- operation safety (tab.5)
- operation parameters (tab.6)
Electrical parameters (tab. 3).
Supply voltage 230V AC (-15%/+10%)
Supply frequency 50Hz
PSU power P 138W
Current consumption 1.1A
Output voltage 11.0V ÷ 12V DC – buffer operation
10.0V ÷ 12V DC – battery operation
Output voltage setting, escalation and keeping
time
20ms / 30ms / 50ms
Pulsating voltage 50mV p-p max.
Output current 8x0,5A + 1x5A provided that:
9.3A + 0,7A battery charging
7,9A + 2,1A battery charging
6,4A + 3,6A battery charging
5,2A + 4,8A battery charging
Power consumption of the power-supply unit
systems during battery operation
20mA max.
Battery charging current 0.7A / 2.1A / 3.6A / 4.8A (factory setting 0,7A)
SCP short-circuit protection
200% ÷ 250% of power supply,
hiccup mode – 13A/200ms and/or
fuse failure in the battery circuit (fuse-element
replacement required)
OLP overload protection
110% ÷ 150% of power supply electronic.
Disconnection of power supply outputs automatic re-
connection after the disconnecting of the DC output
circuit
SCP protection of the battery circuit and reverse
polarity protection
10A - current limitation, F1 fuse (failure requires
replace of the fuse-element)
UVP excessive discharge protection U < 10.0 V 5%)
Technical outputs:
- BS output indicating failure of AC power supply
- AW output indicating failure (activation of SCP,
OLP, UVP, converter failure)
- TAMPER output indicating the opening of the
power supply casing
- OC type, 50mA max, normal status: hi-Z level, failure:
level L (0V), 30s time lag.
- OC type, 50mA max, normal status: L(0V) level,
failure: hi-Z level, (automatic return after correct
operation is returned)
- micro-switch x2, NC contacts (closed casing,
mounted on foundation), 0.5A@50V DC (max)
Fuse in the power supply circuit 230V
Fuse in battery circuit on PCB of the power
supply
Fuse block of recorder fig.3[7]
Fuse block of CCV cameras fig.3[9]
T 6,3A / 250V
T 10A / 250V
F 5A/250V
F0,5A/250V
Mechanical parameters (tab 4).
Casing dimensions
400 x 440 x 170+8
(WxHxD) [mm] (+/- 2), with cover: 405 x 445 x 178
Fixation
371 x 410 x Φ 6
x4pcs (WxH)
Battery space 40Ah/12V (SLA) max.
Net/gross weight 11,75 / 12,60 kg
Casing colour RAL 9003
Closing Cheese screw x 2 (at the front), lock assembly possible
Connectors Power-supply: Φ0.41-2.5
Outputs: Ф0.41÷2.5
BAT battery outputs: connectors Φ6 (M6-0-2.5)
TAMPER output: wires, 300 mm
www.pulsar.pl PSUPS10A12
8
Notes The casing is distant from the assembly surface so that cables can be installed
and has convection cooling
Operation safety (tab.5).
Protection class PN-EN 60950-1:2007 I (first)
Protection grade PN-EN 60529: 2002 (U) IP20
Electrical strength of insulation:
- between input (network) circuit and output circuits of power-supply (I/P-
O/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit (O/P-FG)
3000V AC min.
1500V AC min.
500V AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100MΩ, 500V DC
Operation parameters (tab.6).
Operation temperature -10ºC...+40ºC
Storage temperature +25ºC...+60ºC
Relative humidity 30%...90%, without condensation
Vibrations during operation
Unacceptable
Impulse waves during operation
Unacceptable
Direct isolation
Unacceptable
Vibrations and impulse waves during transport According to PN-83/T-42106
2. Installation
2.1 Requirements
The buffer power-supply shall be mounted by the qualified installer having appropriate (required and
necessary for a given country) permissions and qualifications for connecting (operating) 230V AC installations and
low-voltage installations. The device shall be mounted in closed rooms, according to the environment class II, of
the normal air humidity (RH=90% max. without condensation) and the temperature within the range from -10°C to
+40°C. The power-supply shall operate in a vertical position so that free and convectional air flow through
ventilating holes of the casing is guaranteed.
Before installation is started, the balance of the power-supply load shall be performed. During the
normal operation, the sum of currents collected by receivers shall not exceed I=10A (P=138W max.),
including the maximum battery charging current Ibat.
1. Output current 9.3A + 0,7A battery charging
2. Output current 7,9A + 2,1A battery charging
3. Output current 6,4A + 3,6A battery charging
4. Output current 5,2A + 4,8A battery charging
As the power-supply is designed for a continuous operation and is not equipped with a power-switch,
therefore an appropriate overload protection in the power supply circuit shall be guaranteed. Moreover, the user
shall be informed about the method of isolation of the power supply from the power voltage (usually through
assignment and marking of an appropriate fuse in the fuse-box). The electrical system shall be made in
accordance with valid standards and regulations.
2.2 Installation procedure
1. Before installation is started, the voltage in the 230V power-supply circuit shall be isolated.
2. The power-supply shall be mounted in a selected location and connection cords shall be lead.
3. The power cables (230 VAC) shall be connected to L-N terminals of the power supply. The earth conductor shall
be connected to the terminal marked by the earth symbol . The connection shall be made by means of a three-
core cable (with a yellow and green PE protection wire). The power cables shall be lead to appropriate terminals of
the connection board through bushing.
4. Connect receiver cables to the connectors of recorder module and CCTV cameras module.
5. If necessary, connect the conductors from the equipment to the technical outputs:
- BS AC status indication (alarm panel, controller, signalling unit, LED diode, etc.)
- AW technical output of failure
- TAMPER signalization of power-supply unit opening or separating from foundation
www.pulsar.pl PSUPS10A12
9
RED DIODE:
lights – the power-supply unit supplied with 230VAC
does not light – no 230VAC supply
GREEN DIODE
lights – DC voltage at the AUX output of the power-supply unit
does not light – no DC voltage at the AUX output of the
power-supply unit
The circuit of the shock protection shall be performed with a particular care, i.e. the yellow and
green protection wire of the power cable shall be connected from one side to the terminal
marked by the symbol of in the casing of the power-supply. Operation of the power-supply
without the properly made and fully operational circuit of the shock protection is
UNACCEPTABLE! It can result in failure of devices and electric shock.
6. Using the jumper ‘J1, J2 determine maximal battery charging current, take into consideration battery
parameters (refer to tab.1 page 4).
7. Using the jumper J’ determine whether the function of disconnecting the discharged battery U<10V (+/-5%) is to
be on or off. The battery protection is on if the jumper ‘J’ is removed.
8. Activate the 230V AC supply (the AC diode should be permanently illuminated, and AUX O1, O2, O3 diode
should be permanently illuminated).
9. Check the output voltage (the power-supply unit voltage without load should be anywhere between
13.6V÷13.9V, and during battery charging 11V÷13.8V). If the value of the voltage requires adjustment, the setting
should be made by means of the potentiometer P1, monitoring the voltage at the AUX output of the PSU.
10. Connect the battery in accordance with the indications: +BAT red to plus’ , -BAT black to ‘minus’, (the LB red
diode should go on and the lighting intensity should reduce with the charging time elapsed increasing).
11. Once the tests and control operation have been completed, lock the enclosure, cabinet, etc.
3. The power supply operation indication
3.1 Optical indication
The PSU is equipped with two diodes on the front panel:
Moreover, the PSU is equipped with three diodes indicating operation status: AC, LB, AUX, O1, O2, O3,
and UVP, placed on the PCB of the power-supply unit module:
AC - red diode: under normal status (AC supply) the diode is permanently illuminated. The absence of AC
supply is indicated by the AC diode going off.
LB - red diode: indicates the battery charging process; the intensity of illumination is dependent on the
charging current.
AUX - green diode: indicates the DC supply status at the output of the PSU. Under normal status, the
diode is permanently illuminated and in the case of short-circuits or overload, the diode goes off.
O1, O2, O3 - green diodes: indicate the status of DC power supply at AUX1, AUX2, AUX3 outputs, which
are independently protected with 2.5A polymer safety equipment. In normal state, the diode emits
continuous lightin the case of short-circuit or overload, the diode goes off.
UVP (fig.2) – red diode: signals the activation of the UVP overvoltage protection. In normal state, the
diode is off in the case of short-circuit or overload, the diode emits continuous light.
3.2 Technical outputs
The PSU is equipped with indication outputs:
BS - absence of AC supply output: - OC output type indicates the loss of AC supply in a normal status,
with the supply equal to 230V, the output is deactivated and in case of power supply loss the PSU
activates the output after 30s.
AW - technical output of failure: OC output type indicates failure the occurrence of at least one of the
following failures: SCP, OLP, UVP, voltage converter failure.
In normal state (correct operation), the output has the L status "ground" (0V) – in the case of failure, the
output is open (hi-Z high impedance).
www.pulsar.pl PSUPS10A12
10
TAMPER - output indicates opening the power-supply unit: output as volt-free contacts which indicate
power-supply unit door status and fastening to the ground: NC unit opened and/or wrongly fastened (e.g.
unit unconnected with the ground): NO.
4. Service and operation
4.1 Overload of short-circuit to the power-supply output
The output circuit has an electronic current protection. If permissible value of the I
max
output current is
exceeded, the power-supply unit output voltage is disconnected and this is indicated by the O1, O2, O3 and AUX
diodes going off. The voltage is restored automatically, when the receivers are disconnected from the output.
Additionally, the AUX1, AUX2, AUX3 outputs of the power-supply unit are independently protected, using
the PTC polymer fuses. If the output is loaded with the current that exceeds 2.5A, the output voltage is
automatically disconnected, which is indicated by the O1, O2 or O3 green diode going off. The restoration of the
voltage at the output requires the disconnecting output load for the period of at least one minute.
In the case of the short-circuit to the AUX, BAT output, (load 200% ÷ 250% of the PSU power) or incorrect
connection of the battery, the fuse F1 in the battery circuit becomes permanently damaged. The restoration of the
voltage at the BAT output requires the replacement of the fuse.
4.2. Overload or short-circuit in the output of recorder module or CCTV cameras module
Outputs of recorder module and CCTV cameras module are secured against short-circuit with fuses (fuse-
elements). In case of damage it is required to replace the fuse with suitable new one (same as original or according
to applicable standards and power balance)
4.3 Battery assisted operation
In the case of power failure, in the unit will instantly switch to the battery assisted operation.
In order to activate the operation of the PSU from the battery itself, connect the BAT connectors in accordance with
the indications: +BAT red to plus’ and, -BAT black to 'minus of the battery and press and keep depressed for five
seconds the START pushbutton on the equipment board.
The PSU is equipped with the discharged battery disconnection system (UPV); the configuration of
functions through the jumper ‘J. The battery protection is on if the jumper ‘J’ is removed.
4.4 Maintenance
Any and all maintenance operations may be performed following the disconnection of the PSU from the
power supply network. The PSU does not require performing any specific maintenance measures, however, in the
case of significant dust rate, its interior is recommended to be cleaned with compressed air. In the case of fuse
replacement, only the substitutes in conformity to the original ones are allowed.
www.pulsar.pl PSUPS10A12
11
www.pulsar.pl PSUPS10A12
12
WEEE MARK
The waste electric and electronic products do not mix with general household waste.
There are separate collection system for used electric and electronic products in
accordance with legislation under the WEEE Directive and is effective only with EU.
Notice: The power supply unit is adapted for cooperation with the sealed lead-acid battery (SLA). After the
operation period it must not be thrown but recycled according to the applicable law.
Pulsar K.Bogusz Sp.j.
Siedlec 150, 32-744 Łapczyca, Poland
Tel. (+48) 14-610-19-40, Fax. (+48) 14-610-19-50
e-mail:
biuro@pulsar.pl, sales@pulsar.pl
http:// www.pulsar.pl www.zasilacze.pl
GENERAL WARRANTY CONDITIONS
1. Pulsar K. Bogusz Sp.j. (manufacturer) grants a two-year quality warranty for the equipment, starting from the date of purchase
placed on the purchase order.
2. Should such purchase order be missing when the claim is submitted, the three-year guarantee period is counted from the date
of the manufacturing of the device.
3. The warranty includes free-of-charge repairing or replacing with a functional equivalent (the selection is made by the
manufacturer) of the malfunctioning device, due to reasons attributable to the manufacturer, including manufacturing and
material defects, unless such defects have been reported beyond the warranty period (item 1 and 2).
4. The equipment subject to warranty is to be brought to the place where it was purchased, or directly to the main office of the
manufacturer.
5. The warranty applies to complete equipment, including the type of defect specified in writing, using a properly filled warranty
claim.
6. Should the claim be accepted, the manufacturer is obliged to render warranty repairs, as soon as possible, however not later
that within 14 days from the delivering of the equipment to the service centre of the manufacturer.
7. The repair period mentioned in item 6 may be prolonged, if there is no technical capability to carry out the repairs, and in the
case that the equipment has been accepted conditionally, due to the failing of the warranty terms by the claimant.
8. All the services rendered by force of the warranty are carried out at the service centre of the manufacturer, exclusively.
9. The warranty does not cover the defects of the equipment, resulting from:
- reasons beyond the manufacturer's control,
- mechanical damage,
- improper storage and transport,
- use that violates the operation manual or equipment application,
- random events, including lightning discharges, failures of power networks, fire, flooding, high temperatures and chemical
agents,
- improper installation and configuration (at variance with the rules set forth in the manual),
10. Each confirmation of structural modifications or repairs, carried out beyond the service centre of the manufacturer, or any
modification of serial numbers or warranty labels, results in the loss of the rights resulting from the warranty.
11. The liability of the manufacturer towards the buyer is limited to the value of the equipment, determined according to the
wholesale prices suggested by the manufacturer on the day of purchase.
12. The manufacturer shall not be responsible for the defects that resulted from the damaging, malfunctioning or inability to
operate the equipment, particularly, if such defects are the result of failing to abide by the recommendations and requirements
contained in the manual, or the use of the equipment.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12