Akse Electrex FEMTO D4 70A PFA6431-02 Installation guide

  • Hello! I am an AI chatbot trained to assist you with the Akse Electrex FEMTO D4 70A PFA6431-02 Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
akse srl Via Aldo Moro, 39 42100 Reggio Emilia Italy
Tel. +39 0522 924 244 Fax +39 0522 924 245 [email protected] www.akse.it
VAT IT 01544980350 R.E.A. 194296 Cap. Soc. Euro 85.800,00 i.v.
COPYRIGHT
Akse S.r.l. Electrex is a trademark of Akse S.r.l. All rights reserved.
It is forbidden to duplicate, adapt, transcript this document without Akse written
authorization, except when regulated accordingly by the Copyright Laws.
WARRANTY
This product is covered by a warranty against material and manufacturing defects
for a period of 24 months period from the manufacturing date.
The warranty does not cover the defects that are due to:
• Negligent and improper use
• Failures caused by atmospheric hazards
Acts of vandalism
• Wear out of materials
• Firmware upgrades
Akse reserves the right, at its discretion, to repair or substitute the faulty products
The warranty is not applicable to the products that will result defective in consequence
of a negligent and improper use or an operating procedure not contemplated in this
manual.
RETURN AND REPAIR FORMALITIES
Akse accepts the return of instruments for repair only when authorized in advance.
The transport costs are at customer charge.
RE-SHIPPING OF REPAIRED PRODUCT
The terms for re-shipment of repaired products are ex-works, i.e. the transport costs
are at customer charge.
Products returned as detective but found to be perfectly working by our laboratories,
will be charged a at fee to account for checking and testing time irrespective of the
warranty terms.
SAFETY
This instrument was manufactured and tested in compliance with IEC 61010 class 2
standards for operating voltages up to 250 VAC rms phase to neutral.
In order to maintain this condition and to ensure safe operation, the user must
comply with the indications and markings contained in the following instructions:
• When the instrument is received, before starting its installation, check that
it is intact and no damage occurred during transport.
• Before mounting, ensure that the instrument operating voltages and the
mains voltage are compatible then proceed with the installation.
• The instrument power supply needs no earth connection.
• The instrument is not equipped with a power supply fuse; a suitable external
protection fuse must be foreseen by the contractor.
• Maintenance and/or repair must be carried out only by quali ed, authorized
personnel
• If there is ever the suspicion that safe operation is no longer possible, the
instrument must be taken out of service and precautions taken againstits
accidental use.
• Operation is no longer safe when:
1) There is clearly visible damage.
2) The instrument no longer functions.
3) After lengthy storage in unfavorable conditions.
4) After serious damage occurred during transport
The instruments must be installed in respect of all the local regulations.
OPERATOR SAFETY
Warning: Failure to observe the following instructions may lead to a serious danger
of death.
• During normal operation dangerous voltages can occur on instrument terminals
and on voltage and current transformers. Energized voltage and current
transformers may generate lethal voltages. Follow carefully the standard safety
precautions while carrying out any installation or service operation.
• The terminals of the instrument must not be accessible by the user after the
installation. The user should only be allowed to access the instrument front
panel where the display is located.
• Do not use the digital outputs for protection functions nor for power limitation
functions. The instrument is suitable only for secondary protection functions.
• The instrument must be protected by a breaking device capable of interrupting
both the power supply and the measurement terminals. It must be easily
reachable by the operator and well identi ed as instrument cut-off device.
• The instrument and its connections must be carefully protected against short-
circuit.
Precautions: Failure to respect the following instructions may irreversibly damage
to the instrument.
• The instrument is equipped with PTC current limiting device but a suitable
external protection fuse should be foreseen by the contractor.
• The outputs and the options operate at low voltage level; they cannot be
powered by any unspeci ed external voltage.
• The application of currents not compatible with the current inputs levels will
damage to the instrument. supply with extended operating range. The power
supply terminals are numbered (10) and (11). Use cables with max cross-
section of 4 mm2.
VIEWS
TABLE LIST MEASURES MAIN SCREEN
(The measures available vary according to con guration)
EA ER ES V V I P Q S PF
Ea Imp Er Ind
Imp
Es Imp L-N L-N
f
IPQSPF
Press to measure change
Ea Exp Er Cap
Imp
Es Exp L-L L-L
f
In P Avg
Imp
Q Avg
Imp
S Avg
Imp
Ea x
Fase
Er Ind
Exp
THD
L-N
THD L-N
f
THD P Avg
Exp
Q Avg
Exp
S Avg
Exp
Er Cap
Exp
THD
L-L
THD L-L
f
I Max P MD
Imp
Q MD
Imp
S MD
Imp
Er Ind x
Fase
Min L-N Min L-N
f
I Avg P MD
Exp
Q MD
Exp
S MD
Exp
Min L-L Max L-N
f
I MD
Max
L-N
Min L-N
f
Max
L-L
Max L-L
f
TABLE BELOW LISTS MEASURES WALLPAPERS
(The measures available vary according to con guration)
Press to measure change
Hold for 2 seconds
Ea + Er L + Er C + Es +
Ea - Er L - Er C - Es -
Ea P+ Er L P+ Er C P+ Es P+
Ea P- Er L P- Er C P- Es P-
CNT1 CNT2 CNT3 CNT4
CNT1 P CNT2 P CNT3 P CNT4 P
TIME TIME P
TEMP °C TEMP °F
LEGEND MEASURES
L-N Reference Phase Neutral V Voltage
L-L Reference Phase Phase I Current
THD Total Harmonic Distortion In Current neutral
Avg Average value P Active Power
MD Peak Value Q Reactive Power
Imp (+) Value imported S Apparent Power
Exp (-) Export Value PF Power Factor
IND Inductive Ea Enable Energy
CAP Capacitive Er Reactive Energy
Min Minimum Values (Time base 10 Cycles) Es Apparent Energy
Max Maximum values (Time base 10 Cycles) f Frequency
TIME Life Time (total) TEMP °C Temperature in Celsius (*)
TIME P Life Time (partial) TEMP °F Temperature in Fahrenheit (*)
CNT Counting pulses (total)
CNT P Counting pulses (partial)
* Temperature inside the microprocessor
Further documentation may be downloaded from our web site www.electrex.it.
This document is owned by the company AKSE that it reserves all rights.
DECLARATION OF CONFORMITY
Akse hereby declares that its range of products complies with the following directives
EMC 89/336/EEC 73/23CE 93/68 CE and complies with the following product’s
standard CEI EN 61326 – IEC 61326 CEI EN 61010 – IEC 1010.
The product has been tested in the typical wiring con guration and with peripherals
conforming to the EMC directive and the LV directive.
Subject to modi cation without notice. Edition 9 November 2007.
!
FEMTO D4 70A
INSTALLATION MANUAL
MECHANICAL CHARACTERISTICS
Enclosure Self-extinguishing plastic material class V0
Protection degree: IP40 on the front panel
Dimensions: 70 x 90 x 58 mm (4 modules DIN)
VOLTAGE INPUT
Direct: Up to 300 Vrms phase-neutral
or 519 Vrms phase-phase
Overload: 900 Vrms phase-phase for 1 sec
Power Supply: 230/240Vac +/- 10% 50/60Hz
Self consumption: < 3VA
MODELS
PFA6431-02 FEMTO D4 RS485 230-240V 70A
ENERGY ANALYSER
PFA6431-12 FEMTO D4 RS485 230-240V 70A 1DI 2DO
ENERGY ANALYSER
PFTE000-00 TA external 70A for FEMTO D4
A TA already included with the instrument
*Order additional 2 TA for the three-phase
akse srl Via Aldo Moro, 39 42100 Reggio Emilia Italy
Tel. +39 0522 924 244 Fax +39 0522 924 245 [email protected] www.akse.it
VAT IT 01544980350 R.E.A. 194296 Cap. Soc. Euro 85.800,00 i.v.
S1 S2S1 S2S1S2 A B
T
10 11 12
17 18 19 20V1 V2 V3 N
I1 I2 I3 RS-485 AUX
AUXVOLTAGE INPUT POWER
L1
L2
L3
N
RB
RB
RB
The instrument is tted with a separate power supply. The power supply terminals
are numbered (17) and (18). Use cables with max cross-section of 2,5 mm2 if
exible, 4 mm2 if rigid.
4W Star (4 wire) 3PH-4W 3W Delta (3 wire) 3PH-3W SINGLE 1PH-2W
POWER SUPPLY
C
10
1
11
2
12
AUX
IN/OUT
!
Common
12
11
10
Output 2
Output 1
Common
20
19
Input
1
19
C
20
AUX
IN/OUT
!
S1 S2S1 S2S1 S2 A B
T
10 11 12
17 18 19 20V1 V2 V3 N
I1 I2 I3 RS-485 AUX
AUXVOLTAGE INPUT POWER
L1
L2
L3
RB
RB
RB
S1 S2S1 S2S1 S2 A B
T
10 11 12
17 18 19 20V1 V2 V3 N
I1 I2 I3 RS-485 AUX
AUXVOLTAGE INPUT POWER
LN
FUSE
(50mA T)
230 ÷ 240 V ±10%
RS-485
AB
T
S1 S2S1 S2S1 S2 A B
T
10 11 12
17 18 19 20V1 V2 V3 N
I1 I2 I3 RS-485 AUX
AUXVOLTAGE INPUT POWER
L1
N
RB
BI-PHASE 2PH-2W
INPUTS AND OUTPUTS CONNECTION
(only in the version PFA6411-12)
S1 S2S1 S2S1 S2 A B
T
10 11 12
17 18 19 20V1 V2 V3 N
I1 I2 I3 RS-485 AUX
AUXVOLTAGE INPUT POWER
L1
L2
RB
S1 S2S1 S2S1 S2 A B
T
10 11 12
17 18 19 20V1 V2 V3 N
I1 I2 I3 RS-485 AUX
AUXVOLTAGE INPUT POWER
NO
C
NC
NO
C
NC
Max
27 Vdc
27 mA
(-)
(+)
230 Vac
FROM:
- TRANSDUCER WITH CONTACT CLEAN
- GME
- STATE ON-OFF
- STATE ALARMS
R
e
l
a
y
R
e
l
a
y
Power
Supply
Digital Inputs
Supply voltage (external): from 10 to 30
Vdc
Current consumption: from 2 to 10mA
Maximum frequency
counting:
10 o 100Hz
N.B. For meters gas (need a separator
galvanic, second legislation ATEX)
Digital outputs optocoupled transistor
(NPN)
The second standard DIN 43864.
Maximum voltage applicable: 27 Vdc
Maximum current switchable: 27mA
Voltage connection
Use cables with max cross-section of 2,5 mm2 if exible 4 mm2 if rigid and connect them to the terminals marked voltage input on the instrument according to the applicable
diagrams that follow.
Current connection
Use only the TA provided with the instrument. Connect the TA to the terminals marked I1, I2, I3 (current input) the second gure drawings.
Warning: The phase relationship among voltage and current signals, R-B must be carefully respected. All disregard of this rule or of the wiring diagram leads to severe
measurement errors. Do not lengthen the cables TA.
VOLTAGE AND CURRENT CONNECTION
CONFIGURATION SETUP
LIST SETUP
ENTER SETUP
(Push at the same time and for 2 seconds)
REQUEST PASSWORD 0000 ... 9999
RS-485
Address 485 1 ... 247
Speed 2400, 4800, 9600, 19200, 38400
Bit Data 7 o 8
Parity N = no parity, E = parity, O = Odd-parity
Stop Bit 1 o 2
NETWORK
Type 3PH-3W, 3PH-4W, 2PH-2W, 1PH-2W
Export NO, YES
I FS 14A o 70A
VT 400000/999
CLEAR TOTAL COUNTERS NO, YES
CLEAR PARTIAL COUNTERS NO, YES
CLEAR MIN-MAX NO, YES
CLEAR MAX DEMAND NO, YES
ENTER NEW PASSWORD 0000 ... 9999
EXIT SETUP (Push for 2 seconds)
EXPLANATION BUTTONS
Click Changing the value of the
selected eld
Changing the value of the
selected eld
Go to the next eld
Click
2 sec
Go to the next window Back to the rst window
displays
Exits from setup
The instrument is programmed with the following default values:
Address 485
Communication
27
9600, 8, N, 1
Type
Export
I FS
VT
1PH-2W
No
70
000001/001
Initial Password 0000
S1 S2S1 S2S1 S2 A B
T
10 11 12
17 18 19 20V1 V2 V3 N
I1 I2 I3 RS-485 AUX
AUXVOLTAGE INPUT POWER
Es.
Input M8 Supervisor
12C C34
(-) (+)
(-) (+) (+)
Es. PLC
Out PLC
from 10 to
30 Vdc
/