LST ECO1002 User manual

  • Hello! I am an AI chatbot trained to assist you with the LST ECO1002 User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
ECO1002_DBL_LST_EN_0804.PDF • PAGE 1
ABuilding Safety. Building Security.
Optical-Thermal Detector
ECO1002
Description
The Optical-Thermal Detector ECO1002 uses both the
scattered light principle as well as a separate thermal
detection unit. It was developed to detect the charac-
teristics of re in a wide range of applications, and to
avoid deceptive alarms. The modern design of both
measurement systems and the analysis of the parame-
ters by means of a special algorithm allow to reliably
evaluate the characteristics of re. This makes it an
all-rounder that is used in virtually all elds of re de-
tection.
An internal drift compensation adjusts the alarm thres-
hold by continually evaluating the contamination of the
detector. With that, the sensitivity of the detector is
kept constant for a long time.
Addressable conventional technology is used for alarm
transmission to the re detection control panel. By
means of the Address Module NG58-1, each detector
can be addressed individually.
A test activation of the detector can be carried out
using the Remote Test Unit ECO1000RTU. The detec-
tor can be attached to various detector bases and it
can be protected against theft.
Addressable conventional technology
Combination of optical and thermal
characteristics of fi re
Drift compensation
Individual detector addressing by
means of optional address module
Optional connection of remote
indicator
Function testable with Remote Test
Unit ECO1000RTU
Specifi cations
Operating voltage Supply through the detector line voltage
Current consumption typ. 80µA (quiescent)
Alarm temperature 58°C (maximum-heat component)
Operating temperature max. +45°C
Ambient temperature -30°C to +70°C
Relative humidity 5 – 95% (no condensation)
Dimensions ø × H 102 × 40.5 (mm)
Colour white
Weight 75g
Approval VdS G201067
Order number 241046
Order name Optical-Thermal Detector/Conv./1000/SS ECO1002
/