Omega DPi1701 Owner's manual

Type
Owner's manual

Omega DPi1701 Temperature & Process Input Graphic Display Panel Meter and Data Logger with Wireless Option

The Omega DPi1701 is a versatile and powerful device that can be used for a wide range of applications. With its ability to measure temperature, process voltage, and process current, it is ideal for use in industrial settings, laboratories, and other environments where precise measurements are required.

The DPi1701 features a large, easy-to-read graphic display that can show real-time data, historical data, and alarm information. It also has a built-in data logger that can store up to 10,000 data points. This data can be exported to a computer for further analysis.

Omega DPi1701 Temperature & Process Input Graphic Display Panel Meter and Data Logger with Wireless Option

The Omega DPi1701 is a versatile and powerful device that can be used for a wide range of applications. With its ability to measure temperature, process voltage, and process current, it is ideal for use in industrial settings, laboratories, and other environments where precise measurements are required.

The DPi1701 features a large, easy-to-read graphic display that can show real-time data, historical data, and alarm information. It also has a built-in data logger that can store up to 10,000 data points. This data can be exported to a computer for further analysis.

DPi1701
Temperature & Process Input
Graphic Display Panel Meter
and Data Logger
with Wireless Option
LINE GRAPH
CHARTING
MODE
MAIN SCREEN -
INVERT MODE
HORIZONTAL
BAR GRAPH
MODE
For latest product manuals:
www.omegamanual.info
Shop online at
omega.com
®
User’s Guide
For complete product manual:
www.omega.com/manuals/manualpdf/M5021.pdf
RoHS 2 Compliant
2-1
Figure 1. View of DPi1701 Back Panel With USB & Wireless Options
Figure 2. Power & Mechanical Relay Output Connections
Figure 3. Different Input Type Connections
L(+)
POWER
N(-)
NO
NC
C
OUTPUT 1
NO
NC
C
OUTPUT 2
FUSE 1
SW
90/240
Vac
L
N
FUSE 2
EXTERNAL LOAD
L
N
FUSE 2
L
EXTERNAL LOAD
N
POWER & RELAY OUTPUT CONNECTIONS
Fuse 1 = 100 mA(T)
Fuse 2 = 3 A(T)
L(+)
POWER
N(-)
OUTPUT 1
NO
NC
C
OUTPUT 2
1(-)
I N P U T
2(+)
3
4
5
12345678910
6
7
8
9
10
+
+
V
+
I
–EXC+
OUT
R S 2 3 2
GND
RX TX
NO
NC
C
+
ANTENNA
USB PORT
DPi1701 Temperature & Process Input Graphic Display Panel Meter and Data Logger with Wireless Option
1(-)
I N P U T
2(+)
3
4
5
6
7
8
9
10
THERMOCOUPLE CONNECTION
1(-)
I N P U T
2
3
4
5
6
7
8
9
10
RTD (100 OHMS) CONNECTION
3 WIRE
2 WIRE
1(-)
I N P U T
2
3(+)
4
5
6
7
8
9
10
PROCESS (VOLTS) CONNECTION
+
0/10V
V
1(-)
I N P U T
2
3
4(+)
5
6
7
8
9
10
PROCESS (CURRENT) CONNECTION
+
0/20mA or 4/20mA
I
+
Figure 4. RS232 Connections Figure 5. Excitation Voltage & Analog Output Connections
Figure 6. Configuration Menu Flow Chart
Wiring Connections
2
2-2
1
I N P U T
2
3
4
5
6
7
8
9
10
RS232 CONNECTION
GND
RX
TX
EXCITATION & ANALOG OUTPUT
ARE NOT AVAILABLE
RS232
I N P U T
INTERNAL EXCITATION CONNECTION
I N P U T
ANALOG OUTPUT CONNECTION
+ OUT
+
-EXC+
1(-)
2
3
4(+)
5
6
7
8
9
10
GND
+EXC
+
+
EXC.
TWO WIRE TRANSMITTER CONNECTION
1
2
3
4
5
6
7
8
9
10(-)
V/I
LINE GRAPH TIME SPEED: 1 sec
LINE/BAR GRAPH TOP VALUE: 800.0
LINE/BAR GRAPH BOTTOM VALUE: 300.0
CONFIG. MENU 1
CATEGORY: Te mperature E. UNIT: °F
DECIMAL POINT: xxx.x
MIN. DISPLAY VALUE: -148.0
CONFIG. MENU 2
CONFIG. MENU 3
SET POINT: 450.0
INPUT TYPE: TC-J
MAX. DISPLAY VALUE: 1400.0
INPUT: TC-J ALARM1: ON ALARM 2: OFF
°F
UNLOCK
PRESS
PRESS
PRESS
ENTER BUTTON. SAVE SELECTION AND RUN THROUGH
ENTRIES OF A CONFIG. SUB-MENU.
INCREMENT PARAMETER VALUE/SELECTION OF AN ENTRY.
DECREMENT PARAMETER VALUE/SELECTION OF AN ENTRY.
REAL TIME
(RUN MODE)
DISPLAY SPAN ADJUST: 0
OUTPUT TYPE: 0-5V
DISPLAY MODE: NORMAL
CONFIG. MENU 5
DISPLAY ZERO ADJUST: 10
PRESS
DEAD BAND: 10.0
[ALARM 1]
STATUS: ENABLED
UNLATCH
LOW
CONFIG. MENU 4
SET POINT: 700.0
PRESS
DEAD BAND: 10.0
[ALARM 2]
STATUS: ENABLED
LATCH
HIGH
568.3
°F
CONFIG. MENU 6
CURRENT DATE: 01/03/2012
TIME FORMAT: 12 Hour MM/DD/YYYY
LOG MODE: STOP WHEN FULL
CURRENT TIME: 03:53:45 PM
PRESS
PRESS
CONFIG. MENU 7
START LOGGING
KEY PRESS
STOP LOGGING
KEY PRESS
PRESS
CONFIG. MENU 8
TIME OUT: 6
WIRELESS CHANNEL: 12
WIRELESS NETWORK ID: 13106
TRANS ADDR: 1 RECEIVER ADDR: 0
PRESS
NOTE: CONFIG MENU 8 SHOWS
UP ONLY WHEN INPUT TYPE IS
SELECTED AS WIRELESS.
567.3
3-1
Operation
3
Figure 7. Display Screen Flow Chart
Figure 8. MAX/MIN Flow Chart
Figure 9. Lock/Unlock Flow Chart
INPUT: TC-J ALARM1: ON ALARM 2: OFF
°F
UNLOCK
°F
INPUT: TC-J
AL2:0
AL1:1
PRESS
PRESS
800
300
SPEED:1s
567.3
°F
ELAPS:00:01:08
PRESS
PRESS
DIGITAL DISPLAY
(DEFAULT)
BAR GRAPH
DISPLAY
LINE GRAPH
DISPLAY
°F
LARGE DISPLAY
567.3
567.3
567.3
INPUT: TC-J ALARM1: ON ALARM 2: OFF
°F
UNLOCK
PRESS
PRESS
PRESS
DIGITAL DISPLAY
(DEFAULT)
MAX. DISPLAY
MODE
MIN. DISPLAY
MODE
INPUT: TC-J ALARM1: ON ALARM 2: OFF
°F
UNLOCK
INPUT: TC-J ALARM1: ON ALARM 2: OFF
°F
UNLOCK
PRESS TO RESET
MIN/MAX VALUES
567.3
784.2
395.6
INPUT: TC-J ALARM1: ON ALARM 2: OFF
°F
UNLOCK
PRESS & HOLD
FOR 3 SECONDS
INPUT: TC-J
ALARM1: ON
ALARM 2: OFF
°F
LOCK
+
567.3
567.3
Operation
3
3-2
Figure 10. Data Logging Screen Flow Chart
SPECIFICATIONS SUMMARY
GENERAL
Thermocouple Accuracy
Type J, Type K, Type E:, Type T: 0.5ºC (0.9ºF)
Type R & S: 1°C (1.8°F) or 0.5% of full scale
Thermocouple Range
Type J: -100 to 760ºC (-148 to 1400ºF)
Type K: -100 to 1260ºC (-148 to 2300ºF)
Type E: -200 to 849°C (-328 to 1560°F)
Type T: -200 to 400ºC (-328 to 752ºF)
Type R & S: 100 to 1760ºC (212 to 3200ºF)
Thermocouple Warm up Period: 45 minutes
Thermocouple Zero Drift: 0.06°C/°C
Open Thermocouple Detection: Up scale
Thermocouple Lead Resistance: 100 ohms max.
RTD: 100 ohms Platinum, 2 or 3 wire, 0.00385
curve
RTD Accuracy: 0.5ºC (0.9ºF)
RTD Range: -200 to 850ºC (-328 to 1562ºF)
Open RTD Detection: Up scale
Process (Voltage or current)
Input Accuracy: 0.1% of Rdg
Voltage Input Range: 0 to 10 Vdc
Current Input Range: 0 to 20 mA and 4 to 20 mA
Sampling Rate: 4 samples per second
General Power: 90/240 Vac +/-10%, 50-400 Hz
Operating Conditions: 0 to 50ºC (32 to 122ºF), 90% RH non-
condensing
Protection: NEMA-1/Type 1 Front bezel
Dimensions: 48H x 96W x 118mm D (1.89 x 3.78 x 4.65")
Panel Cutout: 45H x 92mm W (1.772 x 3.622")
Weight: 295 g (0.65 lbs)
PRESS
PRESS
PRESS
PRESS
LINE GRAPH
DISPLAY
(REAL TIME)
LINE GRAPH
DISPLAY
LINE GRAPH
DISPLAY
REAL TIME
LOGGING MODE
PAST TIME
LOGGING MODE
SCROLL FORWARD THROUGH DATA.
MOVE FORWARD IN TIME.
SCROLL BACKWARD THROUGH DATA.
MOVE BACKWARD IN TIME.
DIGITAL
DISPLAY
(DEFAULT)
BASED ON
TIME/DATE OR
ALARM 1, 2
800
300
SPEED:1s
567.3
°F
ELAPS:00:01:08
R/T
800
300
SPEED:1s
567.3
°F
ELAPS:00:01:08
LOG
F:1
800
300
01/03/2012
517.8
°F
03:54:35 PM
LOG
F:1
-OR-
INPUT: TC-J ALARM1: ON ALARM 2: OFF
°F
UNLOCK
567.3
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of 61 months
from date of purchase. OMEGA’s WARRANTY adds an additional one (1) month grace period to the normal five (5) year product
warranty to cover handling and shipping time. This ensures that OMEGA’s customers receive maximum coverage on each product.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an
Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to
be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any action
of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper
repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows
evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specifica-
tion; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components in which wear is not war-
ranted, include but are not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes respon-
sibility for any omissions or errors nor assumes liability for any damages that result from the use of its products
in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts
manufactured by the company will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES
OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL
IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are
exclusive, and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negli-
gence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which
liability is based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component” under 10
CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any
Product(s) be used in or with any nuclear installation or activity, medical application, used on humans, or misused in any way,
OMEGA assumes no responsibility as set forth in our basic WARRANTY / DISCLAIMER language, and, additionally, purchaser will
indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in
such a manner.
FOR WARRANTY RETURNS, please have the following infor-
mation available BEFORE contacting OMEGA:
1. Purchase Order number under which the product was
PURCHASED,
2. Model and serial number of the product under warranty, and
3. Repair instructions and/or specific problems relative to the
product.
FOR NON-WARRANTY REPAIRS,
consult OMEGA for current
repair charges. Have the following information available BEFORE
contacting OMEGA:
1. Purchase Order number to cover the COST of the repair,
2. Model and serial number of the product, and
3. Repair instructions and/or specific problems relative to the
product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and
engineering. OMEGA is a registered trademark of OMEGA ENGINEERING, INC.
© Copyright 2013 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied, reproduced, translated, or reduced to any electronic
medium or machine-readable form, in whole or in part, without the prior written consent of OMEGA ENGINEERING, INC.
RETURN REQUESTS / INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING ANY
PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER
SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number should then be marked on the
outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit.
Servicing North America:
Omega Engineering, Inc., One Omega Drive, P.O. Box 4047
Stamford, CT 06907-0047 USA
Toll-Free: 1-800-826-6342 (USA & Canada only)
Customer Service: 1-800-622-2378 (USA & Canada only)
Engineering Service: 1-800-872-9436 (USA & Canada only)
Tel: (203) 359-1660 Fax: (203) 359-7700
For Other Locations Visit omega.com/worldwide
The information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains, and reserves the
right to alter specifications without notice.
WARNING: These products are not designed for use in, and should not be used for, human applications.
MQS5021/0814
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6

Omega DPi1701 Owner's manual

Type
Owner's manual

Omega DPi1701 Temperature & Process Input Graphic Display Panel Meter and Data Logger with Wireless Option

The Omega DPi1701 is a versatile and powerful device that can be used for a wide range of applications. With its ability to measure temperature, process voltage, and process current, it is ideal for use in industrial settings, laboratories, and other environments where precise measurements are required.

The DPi1701 features a large, easy-to-read graphic display that can show real-time data, historical data, and alarm information. It also has a built-in data logger that can store up to 10,000 data points. This data can be exported to a computer for further analysis.