ABB i-bus KNX Room Master Premium RM/S 2.1 User manual

Type
User manual
ABB i-bus
®
KNX
Room Master Premium
RM/S 2.1
Intelligent Installation Systems
ABB
Product Manual
This manual describes the function of the Room Master Premium RM/S 2.1.
Subject to changes and errors excepted.
Exclusion of liability:
Despite checking that the contents of this document match the hardware and
software, deviations cannot be completely excluded. We therefore cannot accept
any liability for this.
A
ny necessary corrections will be inserted in new versions of the manual.
Please inform us of any suggested improvements.
ABB i-bus
®
KNX Contents
© 2008 ABB STOTZ-KONTAKT GmbH i
Contents
Page
1
General 5
1.1 Room Master: Areas of application ......................................................6
1.1.1 Hotel...................................................................................................6
1.1.2 Hospitals ............................................................................................6
1.1.3 Residential homes..............................................................................7
1.1.4 Apartments.........................................................................................7
1.2 Product and functional overview...........................................................8
1.2.1 Product overview................................................................................9
1.2.2 Functional overview .........................................................................11
2 Device technology 13
2.1 Technical data ....................................................................................13
2.1.1 Electronic outputs.............................................................................14
2.1.2 Binary inputs ....................................................................................14
2.1.3 Rated current output 6 A ..................................................................15
2.1.4 Rated current output 16 A................................................................16
2.1.5 Lamp load output .............................................................................17
2.1.6 Rated current output 20 A................................................................18
2.1.7 Lamp load output .............................................................................19
2.2 Connection schematics.......................................................................20
2.3 Dimension drawing .............................................................................22
2.4 Assembly and installation ...................................................................23
3 Commissioning 25
3.1 Overview.............................................................................................25
3.1.1 Functions of the inputs.....................................................................27
3.1.2 Functions of the outputs...................................................................27
3.2 Parameters .........................................................................................28
3.2.1 Parameter window General .............................................................29
3.2.2 Parameter window Enable Inputs a-f...............................................32
3.2.2.1 Parameter window a: Switch Sensor.............................................34
3.2.2.1.1 Parameter Distinction between
short and long operation – no 36
3.2.2.1.2 Parameter Distinction between
short and long operation – yes 41
3.2.2.1.3 Special function Fault monitoring input 42
3.2.2.2 Parameter window a: Dim Sensor.................................................44
3.2.2.3 Parameter window a: Shutter Sensor............................................49
3.2.2.4 Parameter window a: Value/Forced operation..............................53
3.2.2.4.1 Parameter Distinction between
short and long operation – no 55
3.2.2.4.2 Parameter Distinction between
short and long operation – yes 60
3.2.3 Parameter window Enable Inputs g-l Enable Inputs m-r..................61
3.2.4 Parameter window Enable Outputs A-D..........................................62
3.2.4.1 Parameter window A: Output (20 A/16 AX C-Load)......................63
3.2.4.1.1 Parameter window A: Output - Time 69
3.2.4.1.2 Parameter window A: Output - Scene 75
3.2.4.1.3 Parameter window A: Output - Logic 78
ABB i-bus
®
KNX Contents
© 2008 ABB STOTZ-KONTAKT GmbH ii
3.2.5 Parameter window Enable Outputs E-J .......................................... 81
3.2.5.1 Parameter window E: Output (6 A)............................................... 83
3.2.5.1.1 Parameter window E: Output -Time, Flashing 85
3.2.6 Parameter window Enable Outputs K-U.......................................... 89
3.2.6.1 Parameter window K: Shutter (6 A).............................................. 91
3.2.6.1.1 Parameter window K: Shutter (6 A) - Drive 95
3.2.6.1.2 Parameter window K: Shutter (6 A) - Automatic 97
3.2.6.1.3 Parameter window K: Shutter (6 A) - Scene 100
3.2.6.1.4 Parameter window K: Shutter (6 A) - Safety 102
3.2.6.2 Parameter window K: Blinds (6 A).............................................. 104
3.2.6.2.1 Parameter window K: Blinds - Drive 108
3.2.6.2.2 Parameter window K: Blinds (6A) - Automatic 110
3.2.6.2.3 Parameter window K: Blinds (6A) - Scene 110
3.2.6.2.4 Parameter window K: Blinds (6A) - Safety 110
3.2.6.3 Parameter window L, M, N: Fan (3 x 6 A) multi-level ................. 111
3.2.6.3.1 Parameter window - Status messages 117
3.2.6.3.2 Parameter window - Automatic operation 122
3.2.6.3.3 Parameter window - Direct operation 128
3.2.6.4 Parameter window L, M, N: Fan (3 x 6A) two speed.................. 130
3.2.6.5 Parameter window L, M, N: Fan (3 x 6 A) one-level................... 131
3.2.6.5.1 Parameter window - Status messages 134
3.2.6.5.2 Parameter window - Automatic operation 137
3.2.7 Parameter window Control input................................................... 141
3.2.7.1 HVAC System – 1 Control value/2 pipe...................................... 143
3.2.7.2 HVAC-System – 1 Control value/4 pipe,
with switching object................................................................... 144
3.2.7.3 HVAC System – 2 Control values/2 pipe.................................... 145
3.2.7.4 HVAC System – 2 Control values/2 pipe,
with switching object................................................................... 146
3.2.7.5 HVAC System – 2 Control values/4 pipe.................................... 148
3.2.8 Parameter window O, P: Valve HEATING (0.5 A AC)
– 3 point, opening and closing....................................................... 149
3.2.9 Parameter window O, P: Valve HEATING (0.5 A AC)
– Continuous, PWM....................................................................... 152
3.2.9.1 Parameter window - Function..................................................... 155
3.2.9.2 Parameter window - Curve ......................................................... 159
3.2.10 Parameter window Q, R: Valve COOLING (0.5 A AC).................. 161
3.2.11 Commissioning without bus voltage .............................................. 162
3.3 Communication objects.................................................................... 163
3.3.1 General.......................................................................................... 163
3.3.2 Communication objects L, M, N: Fan (3 x 6 A)............................. 164
3.3.2.1 Communication objects Multi-level fan....................................... 165
3.3.2.2 Communication objects Fan one-level........................................ 172
3.3.3 Control input .................................................................................. 176
3.3.3.1 Communication objects HVAC System
1 Control value/2 pipe................................................................. 176
3.3.3.2 Communication objects HVAC System
1 Control value/4 pipe, with switching object.............................. 177
3.3.3.3 Communication objects HVAC System
2 Control values/2 pipe............................................................... 178
3.3.3.4 Communication objects HVAC System
2 Control values/2 pipe, with switching object............................ 179
3.3.3.5 Communication objects HVAC System
2 Control values/4 pipe............................................................... 180
3.3.3.6 Communication object Fault control value.................................. 181
3.3.4 Communication objects Valve HEATING...................................... 182
3.3.5 Communication objects Valve COOLING ..................................... 185
ABB i-bus
®
KNX Contents
© 2008 ABB STOTZ-KONTAKT GmbH iii
3.3.6 Communication objects Inputs a-r .................................................186
3.3.6.1 Communication objects Switch sensor........................................187
3.3.6.2 Communication objects Switch/Dim sensor................................189
3.3.6.3 Communication objects Shutter sensor.......................................191
3.3.6.4 Communication objects Value/forced operation..........................193
3.3.7 Communication objects Outputs....................................................195
3.3.7.1 Communication objects Output A................................................196
3.3.8 Communication objects Output K: Shutters and blinds .................200
4 Planning and application 208
4.1 Input..................................................................................................208
4.1.1 Operation with central function (Switch light).................................209
4.1.2 Fault monitoring input.....................................................................210
4.1.3 Operation of the illumination (dimming lights)................................212
4.1.4 Operation of shutters......................................................................213
4.2 Output ...............................................................................................215
4.2.1 Function chart ................................................................................215
4.2.2 Function time..................................................................................216
4.2.2.1 Staircase lighting .........................................................................217
4.2.2.2 Switching ON and OFF delay......................................................218
4.2.2.3 Flashing .......................................................................................219
4.2.3 Connection/Logic ...........................................................................220
4.2.4 Scene function ...............................................................................222
4.3 Output K............................................................................................224
4.3.1 Drive types .....................................................................................224
4.3.2 General functions ...........................................................................224
4.3.2.1 Travel times .................................................................................224
4.3.2.2 Safety...........................................................................................226
4.3.2.3 Determination of the current position .........................................227
4.3.2.4 Move to position in % [0…100]....................................................227
4.3.3 Automatic control ...........................................................................228
4.3.3.1 Automatic sun protection .............................................................228
4.3.3.2 Status feedback...........................................................................233
4.4 Heating, ventilation, climate control with Fan Coil units ..................234
4.4.1 Terms .............................................................................................234
4.4.2 Fan operation .................................................................................235
4.4.2.1 Fan in a changeover configuration ..............................................236
4.4.2.2 Fan with speed switching ...........................................................236
4.4.3 Configuration of a HVAC system with Fan Coil units.....................237
4.4.4 Design of a Fan Coil unit...............................................................237
4.4.5 Pipe systems..................................................................................238
4.4.5.1 2 pipe system, configuration........................................................239
4.4.5.2 2 pipe system HEATING and COOLING.....................................240
4.4.5.3 2 pipe system HEATING or COOLING .......................................241
4.4.5.4 3 pipe system, configuration........................................................242
4.4.5.5 4 pipe system, configuration........................................................243
4.5 System configuration with the Room Master....................................244
4.5.1 Automatic operation .......................................................................245
4.5.2 Direct operation..............................................................................247
4.5.3 Switchover between automatic and direct operation .....................247
4.5.4 Logic of the stage switching...........................................................248
4.5.5 Fan operation functional diagram ..................................................249
4.6 Valve drives, valves and controller ...................................................250
4.6.1 Electromotor valve drives...............................................................250
4.6.2 Electro-thermal valve drives...........................................................250
4.6.3 Valve curve ....................................................................................251
ABB i-bus
®
KNX Contents
© 2008 ABB STOTZ-KONTAKT GmbH iv
4.6.4 Control types ................................................................................. 254
4.6.4.1 Continuous control ...................................................................... 254
4.6.4.2 Pulse width modulation (PWM)................................................... 255
4.6.4.3 Pulse width modulation – calculation.......................................... 257
4.7 Behaviour with, … ............................................................................ 258
4.7.1 Bus voltage recovery ..................................................................... 258
4.7.2 Reset via bus................................................................................. 260
4.7.3 Download....................................................................................... 261
4.7.4 Reaction on bus voltage failure ..................................................... 262
4.8 Priorities with, … .............................................................................. 262
4.8.1 Valve HEATING/COOLING ........................................................... 262
4.9 Fast heat up/cool down .................................................................... 263
4.9.1 Heat up .......................................................................................... 263
4.9.2 Cooling down................................................................................. 264
4.10 Assembly of a distribution board
with the Room Master Premium....................................................... 265
A Appendix 267
A.1 Scope of delivery.............................................................................. 267
A.2 Status byte fan, forced/operation ..................................................... 268
A.3 Status byte shutter/blinds................................................................. 269
A.4 Code table scene (8 bit) ................................................................... 270
A.5 Input 4 bit dimming command.......................................................... 271
A.6 Ordering information ........................................................................ 272
ABB i-bus
®
KNX General
© 2008 ABB STOTZ-KONTAKT GmbH 5
1 General
The Room Master Premium RM/S 2.1 provides intelligent engineering
technology for hotel rooms and apartments.
Modern buildings require intelligent building engineering technology for safe
and efficient operation. Many buildings world-wide already utilise the full
potential of networked electrical installations.
Hotels, hospitals, senior citizen and student residential homes, assisted
living accommodation and much, much more: the Room Master covers new
possibilities for buildings in the residential and hotel sectors.
The Room Master has been developed for all rooms of this type. It covers all
requirements of the electrical installation of this application and offers the
following functions in compact form:
• Switch lighting
• Control heating/cooling
• Shading (using shutters or curtains)
• Switching of electrical sockets and loads
In addition to these basic functions, further automation functions can be
implemented by a combination with a presence detector.
The communication of the devices via the KNX bus also enables control
functions as well as sending of emergency signals from the rooms to a
control centre.
The integration into a hotel management system enables the efficient
management and provision of rooms. For example, when a guest checks out
the room is automatically set to standby mode.
This manual provides you with detailed technical information relating to the
Room Master Premium, its installation and programming. The application of
the device is described using examples.
This manual is divided into the following sections:
Chapter 1 General
Chapter 2 Device technology
Chapter 3 Commissioning
Chapter 4 Planning and application
Chapter A Appendix
ABB i-bus
®
KNX General
© 2008 ABB STOTZ-KONTAKT GmbH 6
1.1 Room Master:
Areas of application
1.1.1 Hotel
The Ro
om Master Premium offers all functions which are required in a
modern hotel room. During operation a range of advantages are achieved in
comparison to a conventional installation:
• comfortable and simple operation of the room functions by the guests,
• temperature control dependent on the season, external temperature and
occupancy,
• transmission of messages to the reception, e.g. clean the room, panic
alarm,
• fast localization of faults in the rooms and simplified room maintenance.
The advantages of the Room Master are obvious not just during operation,
but also for planning:
• world-wide use,
• compact design: can be installed in a simple in distribution board
together with circuit-breakers, see Assembly of a distribution board
with the Room Master Premium
, page 265,
• a standard solution for many projects.
1.1.2 Hospitals
Whe
n used in hospitals and buildings with a similar purpose, the Room
Master features many functions which support the efficient operation of a
modern operation:
• simple operation of the room functions by the patients, e.g. automatic
control of the room climate,
• day/night service,
• indication of the ward round,
• remote control of the room and display of the room state in the nurses
station,
• fast localization of faults in the rooms and simplified room maintenance.
ABB i-bus
®
KNX General
© 2008 ABB STOTZ-KONTAKT GmbH 7
1.1.3 Residential homes
The Room Master enables comfort and security in residential homes and
supports senior citizens in their daily routine:
• simple operation of the room functions,
• automatic control of the room climate,
• automatic transmission of messages to the control station, e.g.
emergency signals,
• fast localisation of faults in the rooms,
• indication of room states in the control station,
• day/night service.
1.1.4 Apartments
Apartment
s gain in both their appeal and the quality of life they offer with the
Room Master – decisive factors for sale and rental:
• automatic switching of different lighting arrangements in the room,
• automatic control of heating and cooling,
• shading using shutters or curtains,
• comfortable and simple operation of the room functions.
ABB i-bus
®
KNX General
© 2008 ABB STOTZ-KONTAKT GmbH 8
1.2 Product and
functional overview
The Room Master Premium RM/S is used as a single room solution specially
for hotel rooms. The RM/S is used to control the lighting, the heating and the
air-conditioning as well as the shutters. The input signals are detected via
binary inputs or directly via the sensors connected to the KNX.
Hotel management systems can directly access the RM/S via the ABB i-bus
®
and activate controls in the room. Accordingly, it is possible to quickly adapt
the hotel room to individual customers and guests requirements.
The Room Master is a modular installation device with a module width of
12 space units in ProM Design for installation in the distribution board.
The connection to the ABB i-bus
®
is established using the front side bus
connection terminal.
The Room Master Premium does not require an auxiliary supply.
The assignment of the physical addresses as well as the parameterisation is
carried out with Engineering Tool Software ETS (from Version ETS2 V1.3a)
with a *.VD2 file. If ETS3 is used a *.VD3 type file or higher must be
imported.
Note
The illustrations of the parameter windows in this manual correspond to
the ETS3 parameter windows. The user program is optimised for ETS3.
In the ETS2 it is possible that the parameter page is automatically split if
all parameters are used.
ABB i-bus
®
KNX General
© 2008 ABB STOTZ-KONTAKT GmbH 9
1.2.1 Product overview
The Room Master Premium RM/S 2.1 controls a single-phase fan with up to
three fan speeds via a step or changeover control. This ensures that no two
fan speeds can be switched on simultaneously with a changeover control.
An additional programmable switch-over delay is provided for this purpose.
Three-phase drives are not supported.
Electromotor or electro-thermal actuator drives for HEATING and COOLING
as well as multi-speed fans can be connected directly to the Room Master.
The outputs of the actuator drives (valves) are short-circuit protected by self-
restoring fuses.
A changeover contact is available for control of a shutter or a curtain.
A separate, floating contact is available for the connection of an auxiliary
electrical heating system.
Nine outputs for direct connection of lighting circuits are provided.
These include:
• lamps on the left/right of the bed,
• bathroom lamps,
• entrance lighting,
• two room illuminations and
• indicator lamps before the room door for
• Do not disturb,
• Please clean the room and
• Room occupied/vacant.
Four other contacts can also be manually operated directly on the Room
Master, they are used for supply of power to:
• the power outlets in the room,
• a socket for switching a floor/table lamp,
• a connection for the bathroom fan and
• a connection for switching an auxiliary heating system.
ABB i-bus
®
KNX General
© 2008 ABB STOTZ-KONTAKT GmbH 10
Eighteen binary inputs are available. These are used to report room
information to the Room Master Premium, e.g. switch light ON/OFF:
• in the room entrance area,
• in the bathroom,
• the lamps assigned to the beds,
• the floor/table lamp,
• move the shutter UP/DOWN,
• signalling contacts for window contact and dew point monitoring,
• switching of auxiliary heating,
• door contacts, card readers,
• transmission of an emergency signal,
• door bell,
• for activation of Do not disturb, Room service and Room
occupied/vacant.
The scanning voltage for the binary inputs is provided by the device.
The binary inputs are divided into six groups of three inputs each.
Overview of the number and allocation of the inputs and outputs:
Inputs RM/S 2.1
Binary via contact scanning 18
Outputs RM/S 2.1
Switching contact 20 A (16 AX) 3
Switching contact 16 A (10 AX) 1
Switching contact 6 A 12
Electronic 0.5 A 4
Changeover contact 6 A (shutter) 1
ABB i-bus
®
KNX General
© 2008 ABB STOTZ-KONTAKT GmbH 11
1.2.2 Functional overview
Functional overview based on a hotel room:
18 inputs switch Designation RM/S 2.1
Hall a 1
Main room b 1
Bathroom c 1
Master d 1
Bedside left e 1
Bedside right f 1
Shutter open g 1
Shutter close h 1
Window contact I 1
Floor or desk light j 1
Bathroom blower k 1
Auxiliary electrical heater l 1
Drip tray m 1
Key card n 1
Emergency call o 1
Do not disturb p 1
Room service q 1
Living room r 1
ABB i-bus
®
KNX General
© 2008 ABB STOTZ-KONTAKT GmbH 12
3 outputs with 20 A (16 AX) switch Designation RM/S 2.1
Power outlets (sockets) A 1
Floor or desk light B 1
Blower bathroom C 1
1 output with 16 A (10 AX) switch
Auxiliary electrical heater D 1
10 outputs with 6 A switch
Light bedside left E 1
Light bedside right F 1
Light main room G 1
Light bathroom H 1
Light hall I 1
Light living room J 1
Shutter K 1
Fan L, M, N 3
4 outputs with 0.5 A switch
Valve HEATING O, P 2
Valve COOLING Q, R 2
3 outputs with 6 A switch
Display Do not disturb S 1
Display Room service T 1
Display Room occupied U 1
ABB i-bus
®
KNX Device technology
© 2008 ABB STOTZ-KONTAKT GmbH 13
2 Device technology
RM/S 2.1
The Room Master Premium is a modular installation device (MDRC) in
ProM design. It is intended for installation in the distribution board on
35 mm mounting rails. The assignment of the physical address as well as
the parameter settings is carried out with ETS 2 from version V1.3a or
higher.
The device is powered via the ABB i-bus
®
and does not require and
additional auxiliary voltage supply.
The RM/S 2.1 is operational after connection of the bus voltage.
2.1 Technical data
Supply Bus voltage 21…32 V DC
Current consumption, bus < 24 mA (Fan-In 2)
Leakage loss, bus Maximum 500 mW
Leakage loss, device Maximum 7.65 W*
*The maximum power consumption of the
device results from the following
specifications:
KNX bus connection
Relay 20 A
Relay 16 A
Relay 6 A
Electronic outputs 0.5 A
0.25 W
3.0 W
1.0 W
2.4 W
1.0 W
Connections KNX Via bus connection terminals
0.8 mm Ø, solid
Load circuits
Ferrules without/with plastic sleeves
TWIN ferrules
Tightening torque
Screw terminals with universal head (PZ 1)
0.2…4 mm² stranded, 2 x (0.2…2.5 mm²)
0.2…6 mm² single core, 2 x (0.2…4 mm²)
without: 0.25…2.5 mm²
with: 0.25…4 mm²
0.5…2.5 mm²
Contact pin length at least 10 mm
Maximum 0.8 Nm
Fans/valves/inputs
Tightening torque
Screw terminal, slot head
0.2…2.5 mm² stranded
0.2…4 mm² solid core
Maximum 0.6 Nm
Operating and display elements Programming button/LED for assignment of the physical address
Enclosure IP 20 to DIN EN 60 529
Safety class II to DIN EN 61 140
Isolation category Overvoltage category III to DIN EN 60 664-1
Pollution degree 2 to DIN EN 60 664-1
KNX safety extra low voltage SELV 24 V DC
2CDC 071 079 F0008
ABB i-bus
®
KNX Device technology
© 2008 ABB STOTZ-KONTAKT GmbH 14
Temperature range Operation
Transport
Storage
-5 °C…+45 °C
-25 °C…+70 °C
-25 °C…+55 °C
Ambient conditions Maximum air humidity 93 %, no condensation allowed
Design Modular installation device (MDRC) Modular installation device, ProM
Dimensions 90 x 216 x 64.5 mm (H x W x D)
Mounting width in space units 12 modules at 18 mm
Mounting depth 64.5 mm
Installation On 35 mm mounting rail to DIN EN 60 715
Mounting position as required
Weight 0.7 kg
Housing/colour Plastic housing, grey
Approvals KNX to EN 50 090-1, -2 Certification
CE mark in accordance with the EMC guideline and
low voltage guideline
2.1.1 Electronic outputs
Rated values Number 4, non-isolated, short-circuit proofed
U
n
rated voltage 24…230 V AC (50/60 Hz)
I
n
rated current (per output pair) 0.5 A
Continuous current 0.5 A resistive load at T
A
up to 20 °C
0.3 A resistive load at T
A
up to 60 °C
Inrush current Maximum 1.6 A, 10 s at T
A
up to 60 °C
T
A
= ambient temperature
2.1.2 Binary inputs
Rated values Number 18
1)
U
n
scanning voltage 32 V, pulsed
I
n
scanning current 0.1 mA
Scanning current I
n
at switch on Maximum 355 mA
Permissible cable length ≤ 100 m one-way, at cross-section 1.5 mm²
1)
All binary inputs are internally connected to the same potential.
ABB i-bus
®
KNX Device technology
© 2008 ABB STOTZ-KONTAKT GmbH 15
2.1.3 Rated current
output 6 A
Rated values Number 13 contacts
U
n
rated voltage 250/440 V AC (50/60 Hz)
I
n
rated current (per output) 6 A
Switching currents AC3* operation (cos Ï• = 0.45)
DIN EN 60 947-4-1
6 A/230 V
AC1* operation (cos Ï• = 0.8)
DIN EN 60 947-4-1
6 A/230 V
Fluorescent lighting load to DIN EN 60 669-1 6 A/250 V (35 μF)
2)
Minimum switching performance 20 mA/5 V
10 mA/12 V
7 mA/24 V
DC current switching capacity (resistive load) 6 A/24 V=
Service life Mechanical endurance > 10
7
Electronic endurance
to DIN IEC 60 947-4-1
AC1* (240 V/cos Ï• = 0.8) > 10
5
AC3* (240 V/cos Ï• = 0.45) > 1.5 x 10
4
AC5a* (240 V/cos Ï• = 0.45) > 1.5 x 10
4
Switching times
1)
Maximum relay position change per
output and minute if only one relay is
switched.
2.683
1)
The specifications apply only after the bus voltage has been applied to the device for at least 10 seconds. Typical delay of the relay is approx. 20 ms.
2)
The maximum inrush-current peak may not be exceeded
*What do the terms AC1, AC3 and AC5a mean?
In Intelligent Installation Systems different switching capacity and performance specifications
which are dependent on the special application have become established in industrial and
residential systems. These performance specifications are rooted in the respective national and
international standards. The tests are defined so that typical applications, e.g. motor loads
(industrial) or fluorescent lamps (residential) are simulated.
The specifications AC1 and AC3 are switching performance specifications which have become
established in the industrial field.
Typical application:
AC1 – Non-inductive or slightly inductive loads, resistive furnaces
(relates to switching of ohmic/resistive loads)
AC3 – Squirrel-cage motors: Stating, switching off motors during running
(relates to (inductive) motor load)
AC5a – Switching of electric discharge lamps
These switching performances are defined in the standard DIN EN 60947-4-1 Contactors and
motor-starters - Electromechanical contactors and motor-starters. The standard describes
starter and/or contactors which previously preferably used in industrial applications.
ABB i-bus
®
KNX Device technology
© 2008 ABB STOTZ-KONTAKT GmbH 16
2.1.4 Rated current
output 16 A
Rated values Number 1
U
n
rated voltage 250/440 V AC (50/60 Hz)
I
n
rated current 16 A
Switching currents AC3* operation (cos Ï• = 0.45)
DIN EN 60 947-4-1
8 A/230 V
AC1* operation (cos Ï• = 0.8)
DIN EN 60 947-4-1
16 A/230 V
Fluorescent lighting load AX
to DIN EN 60 669-1
16 A/250 V (70 μF)
2)
Minimum switching performance 100 mA/12 V
100 mA/24 V
DC current switching capacity (resistive load) 16 A/24 V =
Service life Mechanical service life > 3 x 10
6
Electronic endurance
to DIN IEC 60 947-4-1
AC1* (240 V/cos Ï• = 0.8) > 10
5
Switching times
1)
Maximum relay position change per
output and minute if only one relay is
switched.
313
1)
The specifications apply only after the bus voltage has been applied to the device for at least 10 seconds. Typical delay of the relay is approx. 20 ms.
2)
The maximum inrush-current peak may not be exceeded
*What do the terms AC1, AC3 and AC5a mean?
In Intelligent Installation Systems different switching capacity and performance specifications
which are dependent on the special application have become established in industrial and
residential systems. These performance specifications are rooted in the respective national and
international standards. The tests are defined so that typical applications, e.g. motor loads
(industrial) or fluorescent lamps (residential) are simulated.
The specifications AC1 and AC3 are switching performance specifications which have become
established in the industrial field.
Typical application:
AC1 – Non-inductive or slightly inductive loads, resistive furnaces
(relates to switching of ohmic/resistive loads)
AC3 – Squirrel-cage motors: Stating, switching off motors during running
(relates to (inductive) motor load)
AC5a – Switching of electric discharge lamps
These switching performances are defined in the standard DIN EN 60947-4-1 Contactors and
motor-starters - Electromechanical contactors and motor-starters. The standard describes
starter and/or contactors which previously preferably used in industrial applications.
ABB i-bus
®
KNX Device technology
© 2008 ABB STOTZ-KONTAKT GmbH 17
2.1.5 Lamp load output
Lamps Incandescent lamp load 2300 W
Fluorescent lamp T5 / T8
Uncorrected
Parallel compensated
DUO circuit
2300 W
1500 W
1500 W
Low-voltage halogen lamps Inductive transformer
Electronic transformer
1200 W
1500 W
Halogen lamp 230 V 2300 W
Dulux lamp
Uncorrected
Parallel compensated
1100 W
1100 W
Mercury-vapour lamp
Uncorrected
Parallel compensated
2000 W
2000 W
Switching performance (switching
contact)
Maximum peak inrush-current I
P (150 μs) 400 A
Maximum peak inrush-current I
P (250 μs) 320 A
Maximum peak inrush-current I
P (600 μs) 200 A
Number of electronic ballasts (T5/T8,
single element)
1)
18 W (ABB EVG 1 x 58 CF) 23
24 W (ABB EVG-T5 1 x 24 CY) 23
36 W (ABB EVG 1 x 36 CF) 14
58 W (ABB EVG 1 x 58 CF) 11
80 W (Helvar EL 1 x 80 SC) 10
1)
For multiple element lamps or other types the number of electronic ballasts must be determined using the peak inrush current of the electronic
ballasts.
ABB i-bus
®
KNX Device technology
© 2008 ABB STOTZ-KONTAKT GmbH 18
2.1.6 Rated current
output 20 A
Rated values Number 3
U
n
rated voltage 250/440 V AC (50/60 Hz)
I
n
rated current 20 A
Switching currents AC3* operation (cos Ï• = 0.45)
DIN EN 60 947-4-1
16 A/230 V
AC1* operation (cos Ï• = 0.8)
DIN EN 60 947-4-1
20 A/230 V
Fluorescent lighting load AX
to DIN EN 60 669-1
20 A/250 V (140 μF)
2)
Minimum switching performance 100 mA/12 V
100 mA/24 V
DC current switching capacity (resistive load) 20 A/24 V=
Service life Mechanical service life > 10
6
Electronic endurance
to DIN IEC 60 947-4-1
AC1* (240 V/cos Ï• = 0.8) > 10
5
AC3* (240 V/cos Ï• = 0.45) > 3 x 10
4
AC5a (240 V/cos Ï• = 0.45) > 3 x 10
4
Switching times
1)
Maximum relay position change per
output and minute if only one relay is
switched.
93
1)
The specifications apply only after the bus voltage has been applied to the device for at least 10 seconds. Typical delay of the relay is approx. 20 ms.
2)
The maximum inrush-current peak may not be exceeded
*What do the terms AC1, AC3 and AC5a mean?
In Intelligent Installation Systems different switching capacity and performance specifications
which are dependent on the special application have become established in industrial and
residential systems. These performance specifications are rooted in the respective national and
international standards. The tests are defined so that typical applications, e.g. motor loads
(industrial) or fluorescent lamps (residential) are simulated.
The specifications AC1 and AC3 are switching performance specifications which have become
established in the industrial field.
Typical application:
AC1 – Non-inductive or slightly inductive loads, resistive furnaces
(relates to switching of ohmic/resistive loads)
AC3 – Squirrel-cage motors: Stating, switching off motors during running
(relates to (inductive) motor load)
AC5a – Switching of electric discharge lamps
These switching performances are defined in the standard DIN EN 60947-4-1 Contactors and
motor-starters - Electromechanical contactors and motor-starters. The standard describes
starter and/or contactors which previously preferably used in industrial applications.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216
  • Page 217 217
  • Page 218 218
  • Page 219 219
  • Page 220 220
  • Page 221 221
  • Page 222 222
  • Page 223 223
  • Page 224 224
  • Page 225 225
  • Page 226 226
  • Page 227 227
  • Page 228 228
  • Page 229 229
  • Page 230 230
  • Page 231 231
  • Page 232 232
  • Page 233 233
  • Page 234 234
  • Page 235 235
  • Page 236 236
  • Page 237 237
  • Page 238 238
  • Page 239 239
  • Page 240 240
  • Page 241 241
  • Page 242 242
  • Page 243 243
  • Page 244 244
  • Page 245 245
  • Page 246 246
  • Page 247 247
  • Page 248 248
  • Page 249 249
  • Page 250 250
  • Page 251 251
  • Page 252 252
  • Page 253 253
  • Page 254 254
  • Page 255 255
  • Page 256 256
  • Page 257 257
  • Page 258 258
  • Page 259 259
  • Page 260 260
  • Page 261 261
  • Page 262 262
  • Page 263 263
  • Page 264 264
  • Page 265 265
  • Page 266 266
  • Page 267 267
  • Page 268 268
  • Page 269 269
  • Page 270 270
  • Page 271 271
  • Page 272 272
  • Page 273 273
  • Page 274 274
  • Page 275 275
  • Page 276 276