Micro Motion Remote Flow Transmitter - Model RFT9729 Owner's manual

Category
Oxygen Equipment
Type
Owner's manual
March 1991
Rosemount, SMART FAMIL~ and HART are trademarks of Rosemount Inc.. Eden Prairie. MN.
Hastelloy is the trademark of Gabot Gorp.. Kokomo. IN.
Teflon is the trademark of E.I. Du Pont de Nemours Go. Inc.. Wilmington. DL.
1991. Micro Motion. Inc
All Rights Reserved
Tables
3
16
Table 1
Table 2
Specifications AFT 9729 to OMS Wiring,
Figures
Mounting Dimensions 8
Back Panel Connections 10
Wiring Diagram for the D6 through D300 14
Wiring Diagram for the D600 15
RS-485 Wiring 17
HART Network Wiring 18
Location of Jumpers and Test Points on the Processor Board 20
Changing the Jumper Settings 20
Figure 1-1
Figure 2-1
Figure 2-2
Figure 2-3
Figure 2-4
Figure 2-5
Figure 3-1
Figure 3-2
Table of Contents
1
1
1
1
1
2
2
2
2
3
1
1.1
1.2
1.2:1
1.2.2
1.2.3
1.3
1.4
1.5
1.5.1
The Remote Flow Transmitter General Description Theory of Operation Communication Fault Detection and Diagnostics Meter Zeroing Independent Exchange of Flow Sensors and Transmitters.
Modular Electronics Display Totalizer Reset Button
2
2.1
2.2
2.3
2.4
2.4.1
2.4.2
2.4.3
2.5
2.5.1
2.5.2
2.5.3
2.5.4
2.5.5
2.5.6
Transmitter Installation 9
General 9
Installing the Transmitter 9
Power Connections 10
Signal Wiring; Sensor to the Transmitter 11
Cable Connections 11
Sensor Conduit Connections 12
Intrinsically Safe Wiring Requirements 12
Transmitter Output Wiring 12
Analog Output Wiring 12
Frequency Output Wiring 13
Flow Direction Wiring 13
DMS Wiring 13
RS-485 Wiring 16
Multidrop Wiring for the Milliamp Output 16
3
3.1
3.2
3.3
3.4
3.5
3.5.1
3.6
3.6.1
3.6.1.1
3.6.1.2
3.7
Start-Up 19
Jumper Configuration on the Processor Board 19
Power. 21
Transmitter Auto Zeroing 21
Using the LED 21
General Guidelines 21
Symptom Definitions 22
Trouble-shooting 22
Trouble-shooting the RFT 9729 23
Wiring 23
Internal Test Points 23
Customer Service 24
Appendix I
Appendix II
Appendix III
Exploded Drawing of the RFT9729 25
RFT9729 Configuration Record 26
Model 268 SMART FAMILY@ Interface Flow Diagram 28
The Remote Flow lrransmitter
1.1 General Description
The Micro Motion@ Remote Flow Transmitter (RFT9729) is a microprocessor-based
mass flow transmitter. The transmitter, in conjunction with a Micro Motion flow sensor,
forms a complete mass flowmeter system.
The transmitter converts the low-Ievel signals from the sensor to 4-20 mA and frequency
outputs. The 4-20 mA signal can be configured to transmit a flow rate, temperature, or
density signal. The frequency output is always a flow rate signal. The transmitter also pro-
duces digital signals for flow rate, flow total, density, and temperature that can be read by
a Rosemount@ Model 268 SMART FAMILY Interface or a HART-compatible controlsys-
tern. Optionally, RS-485 can be selected as a digital communications medium.
1.2 Theory of Operation
Circuitry in the transmitter compensates for individual flow sensor characteristics,
allowing interchange with any Micro Motion Model D flow sensor.
The RFf9729 interfaces with Model D Mass Flowmeters. The input circuit measures the
signals from the left and right velocity detectors on the sensor tube(s). The input data is
digitally filtered to reduce noise and increase the measurement resolution. This input data
is then converted into flow rate data using the flow calibration factor and the sensed
temperature.
The drive circuit generates an oscillatory voltage to vibrate the tubes. The frequency of
oscillation is at the natural frequency of the sensor, and therefore, a process fluid density
measurement can be calculated from the measured natural frequency of the sensor.
A temperature amplifier converts the resistance of the sensor-mounted platinum RTD to a
linearized voltage (i.e., 5 mV per OC) for digitization, temperature compensation of the
sensor, and the Density Monitoring System (DMS) output. The temperature compensa-
tion has a resolution of 0.1°C and a range of -240° to 450°C (-400° to 842°F).
The transmitter can be easily used with another Micro Motion sensor simply by entering
the correct calibration data.
1.2.1 Communication
The transmitter is programmed to communicate with other digital equipment using the
HART protocol. For more information on transmitter protocol, please refer to the Remote
Flow Transmitter Digital Communications Instruction Manual, July, 1989, PIN 1002798.
Device interconnection is accomplished by using the transmitter mA output terminals.
As an alternative, an RS-485 interface is also available through jumper configuration on
the processor board and is compatible with the transmitter protocol.
1.2.2 Fault Detection and
Diagnostics
The SMART FAMILY Interface (268) allows direct digital configuration and access to
diagnostics of the transmitter. The 268 connects to the transmitter via the 4-20 mA
current output loop and communicates with the transmitter at the transmitter site, from the
control room, or from any other wiring termination point in the loop. The 268 is generic
and can be used with any RFT9729 transmitter. The same 268 can also be used with any
Rosemount SMART FAMILY transmitter. For more information on the 268, see the
instruction manual entitled Using the SMART FAMILY Interface 268 with the Micro
Motion Remote Flow Transmitter, Section 1.
The digital communications protocol is designed to assist in fault detection and
diagnostics. Fault detection is designed to ensure the functional integrity of the meter and
electronics including the velocity transducers, drive coil, and RTD. During start-up, the
RFT9729 microprocessor checks its RAM and EPROM. A watchdog timer monitors the
operation of the microprocessor to ensure recovery from software malfunctions.
Detected faults, which could cause an error exceeding the accuracy specification, can be
displayed on the 268. Within the RFT9729 itself, if a fault is detected that may indicate
malfunc.'tion of the flowmeter, the mA and frequency outputs are set to an upscale or
downscale level (see Section 3.1, Jumper Configuration on the Processor Board) as an
indication that a failure has occurred. Also, the LED on the front panel flashes on at 4 Hz if
a fault condition occurs. The LED flashes on at 1 Hz during normal operation.
1.2.3 Meter Zeroing
Zero flow adjustment (i.e., sensor offset adjustment) is accomplished with the Set Zero
Flow key switch on the front panel, an externally wired set zero switch, or with the
communications protocol auto zero command. During zero flow adjustment, the LED on
the front panel remains on indicating that a zero flow calibration is in progress. The
transmitter will not allow an excessive sensor offset during meter zeroing, protecting
against zeroing while excessive fluid flow exists. See Section 3.3, Transmitter Auto
Zeroing.
1.3 Independent Exchange of
Flow Sensors and
Transmitters
Transmitters and flow sensors may be replaced separately since each sensor is
calibrated at the factory and marked with flow calibration and density calibration factors.
Sensors and transmitters calibrated at the factory have matching serial numbers on their
respective nameplates. To match different transmitters and flow sensors, the calibration
factors are simply entered into the transmitter using the communications protocol. No ad-
ditional calibration or equipment is necessary. For sensors manufactured before calibra-
tion factors were put on each unit, contact Micro Motion at 1-800/522-MASS (522-6277)
in Boulder, Colorado for the U.S., or 31-08385-63911 in Veenendaal, the Netherlands, for
Europe. Also, your local service/sales office can assist you.
1.4 Modular Electronics
The electronics in the transmitter can be removed from the housing and replaced
separately, This is facilitated by modular construction and plug-in cable connectors (See
Appendix I, Exploded Drawing). Interchangeability allows one electronics module to
serve as a spare for many transmitters.
1.5 Display
A 4 line, 20 character display is incorporated in the RFT9729 front panel. This display
shows the following information:
Flowrate (*)
Density (*)
Temperature (*:
Totalizer
(*) denotes which process variable is the mA output (one only).
2
1.5.1 Totalizer Reset Button
The totalizer reset button has 2 functions. If the button is depressed and kept in position,
the totalizer value is stopped. When released the totalizer value is reset to zero.
Table 1 Specifications
Flow Sensor Compatibility
Functional Specifications
Compatible with all Model D sensors with either 7 -wire or 9-wire feedthroughs and 3-wire
platinum RTD (temperature sensor).
Compatible with all Model DL sensors with either 7-wire or 9-wire feedthrough or Camloc
connector and 3-wire platinum RTD.
Compatible with all Model D sensors with 2-wire copper RTD when rewired as 3-wire at
sensor cable interconnection. Temperature and density measurement accuracy will be
somewhat degraded.
Rangeability
Flow: Minimum span equal to 4.0 microsec. of time difference between velocity sensor
signals. Maximum span equal to 240.0 microsec. of time difference between velocity
sensor signals. Range limits from -120.0 microsec. to +120 microsec. time difference
between velocity signals. Zero may be suppressed or elevated. The 50:1 electronics
rangeability encompasses the range limits of the flow sensor. See sensor specifications
for min. and max. spans of individual sensors.
Density: Minimum span of 0.1 g/cc.
Maximum span of 5.0 g/cc.
Range limits from 0.0 to 5.0 g/cc
Temperature: Lower limit of -240°C (-400°F)
Upper limit of 450°C (840°F)
Minimum span of 20°C
Maximum span of 690°C
Power Supply
Standard: 12 to 30 VDC, 6.5 watts typical, 14 watts maximum. 1 amp minimum start-up
current. Fuse rating: 2 amp. Fuse located on back panel.
Optional: 115 VAG :t25%, 48 to 62 Hz, 9 watts typical, 14 watts maximum or 230 VAG
:t25%, 48 to 62 Hz, 9 watts typical, 14 watts maximum. Fuse rating: 0.25 amp. Fuse
located on back panel.
Humidity Limits
Meets SAMA PMC 31.3, Section 5.2
Ambient Temperature Limits
Operating
0 to 50°C (32 to 122°F)
Storage
-20 to 70°C (-4 to 158°F)
3
Output Signals
* 4 to 20 mA, internally powered, galvanically isolated to :t50 VDC, 0 to 1000 ohm load.
The mA output can represent flow rate, temperature, or density (user-configurable). Maxi-
mum ripple of 1.5% of span at greater than 20 kHz.
* 0 to 15 volt frequency representing flow rate, 2.2k ohm pull-up, galvanically isolated to
:t50 VDC. Sinking capability 0.10 amps in the .'on" condition (0 V level), 30 VDC compli-
ance with the internal pull-up removed in the '.off" condition. Maximum "on" pulse width
of 6, 12, or 24 milliseconds, depending on configuration.
* Bell 202 digital communications signal superimposed on 4-20 mA signal, available for
host control system interface. Frequency 1.2 and 2.2 kHz, amplitude 1.0 to 2.0 mA peak-
to-peak, baud rate 1200 bits-per-second. Load resistance between 250 and 1000 ohms
required. HART protocol compatible.
Optional: RS-485 digital communication signal referenced ~o sensor ground. Amplitude
:t5 V square wave, baud rate 1200 bits-per-second. HARr protocol compatible.
* 0 to 15 volt flow direction, 2.2k ohm pull-up, referenced to frequency output return line.
Sinking capability 0.10 amps in the "on" condition (reverse flow) 30 VDC compliance
with the internal pull-up removed in the "off" condition (forward flow).
* 2.5 VAG at sensor natural frequency, referenced to sensor ground, 10k ohm output
impedance. Used for interface to Micro Motion Density Monitoring System.
* 5 mVrC sensor temperature, referenced to sensor ground, 10k ohm output
impedance. Used for interface to Micro Motion Density Monitoring System.
ScaJeabJe mA Output Adjustment
Engineering units and range points user-selectable between rangeability limits for either
flow rate, temperature, or density.
Scaleable Frequency Output Adjustment
* Frequency set point scaleable from 1 to 10,000 Hz in 1 Hz increments.
* Flow rate set-point scaleable from minimum span to upper range limit. Zero flow rate
always equals zero Hz, frequency linear to flow rate.
Frequency output replaced by 2ND mA output
The secondary milliamp output replaces the frequency output. This has consequences for the
hardware as well as the software.
Hardware
The connection terminal points for the secondary milliamp output are:
-48-pin connector (24b) 4-20mA-
(28b) 4-20mA+
Software. (Programming)
Standardwise both mA-outputs will be adjusted to meet in our factory the desired range unless
otherwise specified.
In case the secondary mA-output must be (re)adjusted one will have to do this through the fre-
quency function key with a SFI268 interface.
The 10.000 Hz point corresponds with the 20 mA output.
For example: -desired range 0-500 kg/h
-secondary mA-output 4-20 mA over the above mentioned rate.
Frequency must be programmed to be 10.000 Hz at 500 kg/h. Automatically
the 20 mA will correspond with 500 kg/h.
4
Slug Flow Inhibit
Transmitter senses density outside of user-selectable density limits and drives the flow
outputs to indicate zero flow.
Scaleable Low Flow Cutoff
Engineering units and low-ftow cutoff value user-selectable. Below selected value, digital,
milliamp and frequency outputs are driven to zero.
Damping
User-selectable: 0.2, 0.4, 0.8, 1.6, 3.2, 6.4, or 12.8 seconds time constant.
Over Range Capability
* Milliamp output 2 mA (-12.5% of span) to 22 mA (+112.5% of span)
* Frequency output 11 ,520 Hz
Diagnostics
User-selectable downscale (2 mA and a Hz) or upscale (22 mA and 11520 Hz) when
failure of auto zero, sensor, temperature sensor, or electronics is detected.
Output Testing
* Current source:
Transmitter may be commanded to supply a specified current between 2 and 22 mA.
* Frequency source:
Transmitter may be commanded to supply a specified frequency between 1 and 10,000
Hz.
Turn-On Time
Less than 10 seconds
Warm-Up Time
Transmitter reaches stable operation in less than 30 minutes.
Sensor Compensation
Sensors are flow and density calibrated and assigned calibration factors at the factory.
The calibration factors are entered into the transmitter enabling interchangeability of sen-
sors within 0.1% of reading on flow accuracy, 0.001 g/cc on density accuracy and 0.5°C
:to.25% of reading in °C on temperature accuracy.
Hazardous Location Certification
CENELEC
[EEx ib] lIB* or [EEx ib] IIC*
* with approved sensor
5
Performance Specifications
(Reference operating conditions unless otherwise specified. Definitions per AN81/18A
851.1 -1979 unless otherwise specified.)
Accuracy (sensor included):
(includes effects of linearity, hysteresis, and repeatability)
Flow: :to.2010 of rate :to.O1010 of sensor upp~r range limit.
Density: .:to.001 g/cc; DL 100, DL200, D300, and D600
:to.002 g/cc; D65, D100 and D150
:to.004 g/cc; D40, D25, D12, ~nd D6
Temperature: :t1 °G :to.5% of reading expr~ssed in "G
Repeatability (sensor included):
Flow: :!=0.05% of rate :!=0.005% of sensor upper range limit
Density:
:to.OOO5 g/cc; OL 100, OL200, 0300, and 0600
:to.OO10 g/cc; 065, 0100 and 0150
:to.OO2 a g/cc; 040, 025, 01 ~, and 06
:to.2°C
Temperature:
Ambient Temperature Effect (transmitter on/~)
Flow: Zero effect :to.OO2% of sensor upper range limit tC.
Span effect :to.OO2% of span tC.
Density:
:to.00005 g/cc/"F; OL 100, OL200, 0300, and 0600
:to.0001 g/ccrF; 065, 0100 and 0150
:to.0002 g/ccrF; 040, 025, 012, and 06
Temperature:
Analog :to.O1 "Ct'C
Digital :to.10''Ct'C
RFI Effect (sensor excluded)
Level 1, :to.8% of span at 1 Vim per IEC 8d1.3 -1984
Level 2, :t4.00% of span at 3 Vim per IEC 801.3 -1984
Class 3, A, B, C, :to.8% of span at 1 Vim pftr SAMA PMC 33.1
Class 1, A, B, C, :t4.00% of span at 3 Vim per SAMA PMC 33.1
Class 2, A, B, C, :t15% of span at 10 Vim per SAMA PMC 33.1
Conductive conduit for sensor cable, which is earth grounded at both ends, is required
for RFI protection within this specification.
Vibration Effect (transmitter only)
Meets SAMA PMC 31.1, Level
6
Supply Voltage Effect (sensor included)
Meets supply voltage effect requirements of SAMA PMC 31
5.10.5
section 5.10.1 through
Physical Specifications
Electronics Housing
Half 19" cassette. 42TEx 3HE; gray PVC-coated panels
Dimensions: 213 W by 128 H by 235 mm D (8.4 W by 5 H by 9.3 in D)
Weight: 2,6 kg (5.7 Ib)
Electrical Connections
Din 41612 Type F 48 pole connector for sensor and output signals. Separate main
supply connector is available.
Cable from Sensor to Transmitter
3 individually shielded twisted pairs, ,minimum 20 AWG, for 7 wire sensors. Less than 30
pF-per-foot interwire capacitance u~ to 500 ft (150 meters) total cable length.
4 individually shielded twisted pairs,: minimum 22 AWG, minimum 18 AWG for drive pair
for 9 wire sensors. Less than 30 pF-li>er-foot interwire capacitance up to 1000 ft (300 me-
ters) total cable length.
7
Figure 1.1
Mounting Dimensions
RFT9729
37 TE
(188 mm)
~
~ ~ RFT 9729 Remote Flow T"c,m,l!e,
~
6'
E
E
...
"'
~
E
UJ E
I "
M aj
N
I~ ~~-~
0
42 TE
(213 mm)
FRONT
SIDE
8
2
Transmitter Installation
2.1 General
For information regarding installation of the flow sensor, please refer to the Micro Motion
Sensor Instruction Manual. This instruction manual is included with the sensor when
shipped from the factory.
The transmitter should be placed in an easily accessible place in a safe area.
Use separate conduits or cable trays for power and signal wiring. Cable tray installation
requires Micro Motion supplied Teflon@ wiring or equivalent cable tray compatible wiring.
Transmitter wiring connections are located on the back panel of the unit.
Wiring connections to the 025 through 0300 sensors are made within the supplied
juction box. The juction box is not attached to the sensor when shipped. Attach and posi-
tion the junction box on the sensor manifold as desired. Unscrew the junction box cover
to access the 9-position terminal strip. Wiring instructions are placed in the juction box
when it is shipped from the factory with a sensor. Refer to these directions when making
connections to the transmitter.
For applications in which cable temperatures are above 150°F (65°C) or below 32°F
(0°C), the light blue, Teflon-jacketed cable should be used. For applications in which
temperatures stay between 32° to 150°F (0° to 65°C), the medium blue, PVC-jacketed
cable can be used. The standard cable supplied is 10 feet (3 meters) long. Up to 1000
feet (300 meters) of cable can be used between the transmitter and sensor. Cable lengths
between 10 and 1000 feet are available from the factory.
~ Note: Operation of the meter may be detrimentally affected if cable other than Micro Mo-
tion color-coded cable is used.
WARNING: To maintain intrinsic safety and performance, only low power signal
cables can be routed through the conduit alongside the sensor wiring.
2.2 Installing the Transmitter
When mounting the transmitter, Micro Motion recommends following the practices
described below.
1. Mount the transmitter in an environment which protects it from ambient temperatures
below 00 or above 50°C (below 32°F or above 122°F).
2. Accessibility is important when mounting the transmitter. Be sure to mount the unit so
that it is accessible for calibration, reconfiguration, reading data or servicing.
9
2.3 Power Connections
'k / DANGER: POWER MUST BE OFF WHEN MAKING WIRING CONNECTIONS.
The transmitter comes set up for either 12 to 30 VDG, 100/115 VAG, or 220/230 VAG.
CAUTION: Power supply voltage must agree with the voltage stated on the
selector switch mounted on the back panel.
AC input power connections are made at seperate terminals of the transmitter indicated
with P, N, and the ground symbol. The individual terminal blocks may be disconnected
and removed from the housing for ease of wiring and service. When the meter is used
with a OC power supply, terminal 20 is positive and terminal 28 is negative. Earth ground
is established at the ground lug at the back panel and must be connected (See Fig. 2-1 ).
CAUTION: Failure to connect earth ground to the ground lug in the terminal
compartment will nullify the meter's intrinsically safe rating.
Figure 2-1
Back Panel
Connections
i 13TE
1!66MM>
-..
w
F: MAINS SELECTOR
(S) ON
Dp
EARTH
O,25A O ZER~
ZERO +
2A O Mb
MA+
~ D '-'NU I
LED +
BACKPLANE BOARD RFT9729 = D
W.O96.B.443 REV 1 LED -
S.O97.B.203 REV 1 D
~
@1
H
~
("\
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I
U
A
230V
J1
188 BI
1%:
O
(/)
z
w
(/)
~
.:1
A
~
BACK
10
2.4 Signal Wiring; Sensor to
the Transmitter
2.4.1 Cable Connections
Signal connections are made via the interconnect cable between the sensor unit and
terminals 8 through 26 of the transmitter. Refer to Figures 2-2 for Models 06 through
0300 and Figure 2-3 for the Model 0600. Only low power signal cables may be routed
through conduit alongside the sensor wiring if intrinsic safety requirements must be
maintained.
The transmitter end of the cable must be prepared in the field. Micro Motion, Inc. supplies
the necessary butt-splices, sp'ade-Iugs, shrink-tubing, solder-sleeve connection wire, and
instructions with each meter. Individual wires are color-coded for easy identification.
Refer to Figure 2-2 or 2-3 to connect cable to the transmitter.
Wiring connections to the 025 through 0300 sensors are made within the supplied junc-
tion box. The junction box is not attached to the sensor when shipped. Attach and posi-
tion the junction box on the sensor manifold as desired. Unscrew the junction box cover
to access the 9-position terminal strip. Wiring instructions are placed in the junction box
when it is shipped from the factory with a sensor. Refer to these directions when making
connections to the transmitter.
~ Note: For 7-wire feedthrough sensors, the wires must be paired exactly as shown below.
~ If the cable is not supplied by Micro Motion, Inc., make certain each pair is individually
shielded and that 20 gauge or larger diameter wire is used. The ground shield for the wire
pair connected to terminal 14 and 16 must be connected to the yellow wire at the sensor
junction box and to terminal 12 at the transmitter. Be sure that the bare shields are insu-
lated against potential shorting, such as to the meter case.
-Wires connected to transmitter terminals 10d (brown) and 8d (red) must be paired to-
gether.
-Wires connected to terminals 14d (orange) and 16d (violet) must be paired together.
-Wires connected to terminals 20d (green) and 24d (blue) must be paired together.
-Ground shield for the pair connected to terminals 14d and 16d must connect to terminal
12d (yellow)
-Ground shields for the other wire pairs connect to terminal 26d at the transmitter and are
not connected at the sensor.
For 9-wire feedthrough sensors, the pairing is as follows:
-Wires connected to transmitter terminals 10d (brown) and Bd (red) must be paired to-
gether.
11
Wires connected to terminals 14d (orange) and 16d (violet) must be paired together.
Wires connected to terminals 20d (green) and 18d (white) must be paired together.
Wires connected to terminals 24d (blue) and 22d (gray) must be paired together.
-Ground shield for the pair connected to terminals 14d and 16d must connect to terminal
12d (yellow)
-Ground shields for the other wire pairs connect to terminal 26d at the transmitter and are
not connected at the sensor.
2.4.2 Sensor Conduit
Connections
Flexible conduit shou!d be UL listed as explosion-proof. Explosion-proof conduit is not
required with the sensor wiring for intrinsic safety on sensors up to and including the
D300. The connection must, however, be sealed.
2.4.3 Intrinsically Safe Wiring
Requirements
The terminal area of the transmitter is partitioned to separate intrinsically safe wiring from
non-intrinsically safe wiring. Intrinsically safe wiring to the sensor is labeled "Intrinsically
Safe Terminals." Only sensor wiring should enter this connector.
2.5 Transmitter Output Wiring
Wiring to output devices should be separated from input power wiring to avoid possible
electrical interference. Therefore, separate connectors are provided for output devices.
Outputs are not intrinsically safe.
2.5.1 Analog Output Wiring
When connecting a receiver to the RFT9729 milliamp output circuit, terminals 14b and
16b are used. Terminal 16b is the signal line (+) and terminal 14b is the return (-). The
negative signal (terminal 14) may be grounded or left ungrounded since it is galvanically
isolated up to :t50 VDC. Twisted pair, shielded cable should be used for long runs.
The 4-20 mA signal output can power loop-powered process indicators, such as the Mi-
cro Motion Model PI 4-20 Process Indicator. A minimum loop resistance of 250 ohms is
required for SMART FAMILY communication. The maximum loop resistance cannot ex-
ceed 1000 ohms. Shields for the output signals should be connected to ground only at
the transmitter end (terminal 2z, 4 b d z).
12
2.5.2 Frequency Output Wiring
(Optionally replacable
by 2nd current output)
The frequency output is galvanically isolated up to :f:50 VDC. The output circuit is rated to
30 VDC, 0.1 ampere maximum sinking capability. The output from the transmitter is a
nominal 15 volt logic level square wave, unloaded. The output impedance is 2.2k ohms at
the 15 volt logic level. If receivers other than Micro Motion products are used, please refer
to their instruction or operating manuals their input voltage and current requirements.
To connect a frequency output receiver, use terminal 28b (+) as the signal line and
terminal 24 (-) as the return. The frequency output wiring should be twisted pair and no
smaller than 22 gauge shielded cable. Shields for the output signals should be
connected to ground only at the transmitter end (terminal 2z, 4 b d z).
2.5.3 Flow Direction Wiring
To connect the transmitter for flow direction indication, use terminal 26b (+) as the signal
line and terminal 24b (-) as the return. The output circuit is rated to 30 VDC, 0.1 ampere
maximum sinking capability. The output from the transmitter is a nominal 0 to 15 volt
logic level, unloaded. The output impedance is 2.2k ohms at the 15 volt logic level. With
forward flow, the output is high (+15 V); with reverse flow, the output is low (0 V). Near
zero flow, this output could be in either state due to zero stability. The flow direction out-
put can be used as an input to directional totalizers such as the Micro Motion DRT.
2.5.4 OMS Wiring
To connect the RFT9729 to a Density Monitoring System (DMS), use three-wire shielded
cable. Use of a DMS barrier is not necessary with the RFT9729. No more than 500 feet of
shielded cable should be used between the RFT9729 and the DMS. Wire size should be
22 gauge or larger diameter.
13
Figure 2-2
Wiring Diagram for
the D6 through D300
Installation Instructions
Type Cenelec
Intrinsically safe outputs
CNc ad drive- -red
10d drive+ -brn
12d temp gnd -yel
14d temp- -or
16d temp+ -viol
18d LPO- -whc
20d LPO+ -grn
22d RPO- -grey
24d RPO+ -blue
2ad shield -shield
Non Intrinsically safe outputs
CN2 2d see terminal connection
2b on page 16
2z
4bdzL
6b zero-
8b zero+
1Ob 485A
12b 4858
14b mA-
16b mA+
18b DMS gnd
2Ob DMS temp
22b DMS period
24b Freq FIR-
26b FIR+
28b Freq.+
3Ob Led+
32b Led-
Non-h.z.rdou. Art.
(~ution
1 10 malnt~ln Intrlnsl(1
sale1 y, sale wlrin!,
must be separatec
Ifrom all other
wlrln(j
d b
d b
2
W'
o
o
~
[8]
0=0
*
110/11SV ...
.
p
N
Intrinsi(~l(y s~fe
output termin~(s
e>
I
220/230V p N
/ Potential Equalizer
/
Caution: power supply must agree with the
voltage stited on selectorswitch.
-+
32
32
I Transmitter I
I RFT9729 I
/
~ Bro",ni
Red
Orange
2
or Gry "nd Vlht
(for 9 vlir"" only) 3
Shield Gnd (Yel)
Green
[Jlue
Violet
/'"7
,'-~,,- /)~
'~-;;i~-~~..-':;;'
Malch wire color
~ ov,;recOIOrw;lh , the 7 or 9 butl spl;ces
al sensor
,CL-.-f '--'-' c
!c L-! ~
:, "~LI c
e
7 WIRES
Brov/n
-Red
-Orange
-Shield Gnd (Yell
-Green
= Blue
-Violet
or 9 WiRES
Brown
-Red
-Orange
-While -
-Shield Gnd (Yell
-Gray
~ Green
Blue
-V,olel
',',cro Mo:iOn mass flowmc!cr
sys:cm Conncc!;on lor
in"insically sa!e ODCra'ion
For use """ '"oce's
DC ','" D3C-) ," ,ers'crs SuD"ti"c
"S c:"S'CJ"1 so"'
--
Model D25D300
'oGol DG/u'2
*
See page 16
14
Installation Instructions
Type Cenelec
Figure 2-3
Wiring Diagram for
the D600
Non Intrinsically safe outputs
CN2 2d see terminal connection
2b on page 16
2z
4bdz-,
6b zero-
8b zero+
10b 485A
12b 485B
14b mA-
16b mA+
18b DMS gnd
20b DMS temp
22b DMS period
24b Freq FIR-
26b FIR+
28b Freq+
3Ob Led+
32b Led-
Intrinsically safe outputs
CN1 8d drive- -red
1Od drive+ -brn
12d temp gnd -yec
14d temp- -or
16d temp+ -vioc
18d LPo- -whL
20d LPO+ -grn
22d RPo- -grey
24d RPO+ -blue
26d shield -shield
Ciution
I To milntiln Intrinsic sitety. site ~iring I
2 must be sepirited
Itrom ill other
.~Irlno
d b' z
o
o
~
[8]
0:0
110/115V I p I N I.
0
I
*
Intrinsically safe
output terminals
220/23~~j p I N I.
I !J 32
Potential Equalizer
Caution: power supply must agree with the
voltage stated on selectorswitch.
132
I Tr~nsmitter I
I RFT9729 I
~
(
safe
{for 9 WIRE only)
I ~I
/
r
CAUTION Power supply vollagc
musl agrcc w;th the vollagc stalcd
on Ihc vollagc labcl ;ns;dc Ihc
explos;on.proof hous;ng
100/115 VAC 50160 Hz G N H
220/230 VAC 60160 Hz G L2 L,
E
ID
.to be sealed
afterw;r;ng
123456789
eeeee~eeee
Power -~
To d,;ve co;1
k)cated ;n
mass flow
meter Idr;ve
co;1 ;s
prool also)
~
,0
M"ro Mol;on mass Ilowmeter
sY"em connection lor
;n"ins"ally safe operation
I Cablejunclion
I box
~~~
e
For use w;'h modo'
D600 ;n vers;ons suPp';od as
;nlr;ns;cally salel
explos;on proof
/ Explosion-proof housing
Voltage label -
Explo5;On-proof I lnlr;n5;cally sale
Model DSOO
* See page 16
15
FAST.ON I SOLDERING TERMINAL
d b z
d,-,z
J~I~g~ ~~earth
ie-d ,-~p
-~~I~ C)N
; ,
04 mm2-J I .
earth
p
N
r-,--c -
P'N:...
L-:--L~-
h
J:~Q:~- --,"
; red :
:;f~!-*-i : -:~~~==~~
L-L-L-' J ; :
l-~~-=-:~-::'~ 0,4 mm2
BACK VIEW RFT9729
---
BACK VIEW RFT9729
~~
CN2
BACK VIEW
CN2
BACK VIEW
CN1
CN1
NOTES 1. CN1 IS USED FOR SENSOR CONNECTION, ONLY ON ROW "d" SEE IOM
CN2 IS USED FOR OUTPUT CONNECTION, ONLY ON ROW "b" SEE I.OM
2. FOR SUPPLY VOLTAGE CONNECTION 3 POSSIBILITIES
a AC VOLTAGE DIRECTLY TO 3-POLE CONNECTOR OF AFT
b AC VOLTAGE TO CN2 "P" TO 6z OR 2d
"N" TO 2b
"+"TO2zOR4zOR4bOR4d
AFT MUST BE WIRED AS .
c DC VOLTAGE TO CN2 "+" TO 6z OR 2d
"-,, TO 2b
NOTES 1, CNI IS USED FOR SENSOR CONNECTION, ONLY ON ROW "d" SEE IOM
CN2 IS USED FOR OUTPUT CONNECTION, ONLY ON ROW "b" SEE IOM
2, FOR SUPPLY VOLTAGE CONNECTION 3 POSSIBILITIES
a AC VOLTAGE DIRECTLY TO 3-POLE CONNECTOR OF RFT
b AC VOLTAGE TO CN2 "P" TO 6z
"N" TO 2b
" " " TO 2z OR 4z OR 4b
RFT MUST BE WIRED AS '.
C DC VOLTAGE TO CN2 " + " TO 6z
"-" TO 2b
Table 2
RFT9729 to OMS Wiring
RFT91729
Terminal #
Signal
Description
DMS
Terminal #
18b to
2Ob to
22b to
18b to
7 and 10
8
9
None
Signal Ground
Temperature
Period
Ground shield
2.5.5 RS-485 Wiring
To connect the RFT9729 to an RS-485 network, use terminal 10b as the "A" line and
terminal12b as the "8" line. RS-485 wiring should not exceed 4000 feet (1200 meters) of
twisted pair cable. Cable should consist of 24 gauge or larger diameter wire. Twisted pair,
shielded cabl~ should be used if the cable passes through any area which might produce
electromagnetic interference.
A 120 ohm, V2 watt resistor should be installed at each end of the network cable. These
termination resistors ensure proper communications by reducing electrical reflections in
the cable. See Figure 2-4, RS-485 Wiring.
As many as 15 RFT9729 units can be connected to a single network. Using the RFT9729
in a networking (multidrop) mode requires each transmitter to be assigned a unique ad-
dress in order to prevent contention on the line. In the RS-485 networking mode, it may
be desirable to engage the "485 mA Live" jumper selection (see Section 3.1, Jumper
Configuration on the Processor Board) in order to preserve active milliamp outputs on
each transmitter. For further information on the communications protocol requirements
needed to implement an RS-485 network, refer to the Remote Flow Transmitter Digital
Communications Instruction Manual, July, 1 1989, PIN 1002789, or contact Micro Mo-
tion, Inc. at 1-8001322-JUMP, in the U.S. or at 31-08385-63312 in Europe.
2.5.6 Multidrop Wiring for
the Milliamp Output
To connect the RFT9729 in a HART compatible network, the milliamp outputs from each
transmitter in the network need to be connected together feeding into a common load re-
sistor of approximately 250 ohms. Before connecting each transmitter into the network,
the transmitter must be assigned a unique multidrop address using the numbers 1
through 15. Doing this will default the milliamp output to a constant 4 mA level. The "485
mA Live" jumper (see Section 3.1) should not be engaged in this mode of operation to
limit the overall current into the common load resistor.
A maximum of 10 transmitters may be connected in a HART multidrop network. Other
Rosemount SMART FAMILY transmitters may participate in a HART compatible network.
See Figure 2-5, HART Network Wiring. A single 268 or HART compatible control system
can communicate with any of the transmitters in the network over the same two wire pair.
16
SCREW TERMINAL
y~~~~ ---", earth
~ , !~~---;. p
ipiN!..: : -:-~~---; N
LC~~~~~-: :,-~:;j 0.4 mm2
BACK VIEW RFT9729
~
CN2
BACK VIEW
NOTES 1. CNI IS USED FOR SENSOR CONNECTION, ONLY ON ROW "d" SEE I.OM
CN2 IS USED FOR OUTPUT CONNECTION, ONLY ON ROW "b" SEE I.OM
2, FOR SUPPLY VOLTAGE CONNECTION 3 POSSIBILITIES
a AC VOLTAGE DIRECTLY TO 3-POLE CONNECTOR OF RFT
b AC VOLTAGE TO CN2 "P" TO 6z OR 2d
"N" TO 2b
" + " TO 2z OR 4z OR 4b OR 4d
RFT MUST BE WIRED AS .
c DC VOLTAGE TO CN2 "+" TO 6z OR 2d
"-" TO 2b
NOTES 1" CN1 IS USED FOR SENSOR CONNECTION" ONLY ON ROW ""d"" SEE IOM
CN2 IS USED FOR OUTPUT CONNECTION, ONLY ON ROW "b" SEE IOM
2" FOR SUPPLY VOLTAGE CONNECTION 3 POSSIBILITIES
a AC VOLTAGE DIRECTLY TO 3-POLE CONNECTOR OF RFT
b AC VOLTAGE TO CN2 ""P"" TO 6z
"N"" TO 2b
" b " TO 2z OR 4z OR 4b
RFT MUST BE WIRED AS -.
c DC VOLTAGE TO CN2 "+" TO 6z
"-" TO 2b
Table 2
RFT9729 to DMS Wiring
RFT9729
Terminal #
Signal
Description
OMS
Terminal #
18b to
2Ob to
22b to
18b to
7 and 10
8
9
None
Signal Ground
Temperature
Period
Ground shield
2.5.5 RS.485 Wiring
To connect the RFT9729 to an RS-485 network, use terminal 10b as the "A" line and
terminal12b as the "8" line. RS-485 wiring should not exceed 4000 feet (1200 meters) of
twisted pair cable. Cable should consist of 24 gauge or larger diameter wire. Twisted pair,
shielded cabl~ should be used if the cable passes through any area which might produce
electromagnetic interference.
A 120 ohm, 112 watt resistor should be installed at each end of the network cable. These
termination resistors ensure proper communications by reducing electrical reflections in
the cable. See Figure 2-4, RS-485 Wiring.
As many as 15 RFT9729 units can be connected to a single network. Using the RFT9729
in a networking (multidrop) mode requires each transmitter to be assigned a unique ad-
dress in order to prevent contention on the line. In the RS-485 networking mode, it may
be desirable to engage the "485 mA Live" jumper selection (see Section 3.1, Jumper
Configuration on the Processor Board) in order to preserve active milliamp outputs on
each transmitter. For further information on the communications protocol requirements
needed to implement an RS-485 network, refer to the Remote Flow Transmitter Digital
Communications Instruction Manual, July, 1 1989, PIN 1002789, or contact Micro Mo-
tion, Inc. at 1-8001322-JUMP, in the U.S. or at 31-08385-63312 in Europe.
2.5.6 Multidrop Wiring for
the Milliamp Output
To connect the RFT9729 in a HART compatible network, the milliamp outputs from each
transmitter in the network need to be connected together feeding into a common load re-
sistor of approximately 250 ohms. Before connecting each transmitter into the network,
the transmitter must be assigned a unique multidrop address using the numbers 1
through 15. Doing this will default the milliamp output to a constant 4 mA level. The "485
mA Live" jumper (see Section 3.1) should not be engaged in this mode of operation to
limit the overall current into the common load resistor.
A maximum of 10 transmitters may be connected in a HART multidrop network. Other
Rosemount SMART FAMILY transmitters may participate in a HART compatible network.
See Figure 2-5, HART Network Wiring. A single 268 or HART compatible control system
can communicate with any of the transmitters in the network over the same two wire pair.
16
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35

Micro Motion Remote Flow Transmitter - Model RFT9729 Owner's manual

Category
Oxygen Equipment
Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI