Broan B6BW Installation guide

Type
Installation guide
Vertical Wall Mount Air Handler
Please read all information in this manual thoroughly and become familiar with the capabilities
and use of your appliance before attempting to operate or maintain this unit. These instructions
are primarily intended to assist qualifi ed individuals experienced in the proper installation of
this appliance. Some local codes require licensed installation/service personnel for this type
of equipment. Improper installation, service, adjustment, or maintenance may cause explosion,
re, electrical shock or other hazardous conditions which may result in personal injury or
property damage.
Unless otherwise noted in these instructions, only factory authorized kits or accessories may
be used with this product. Keep this manual where you have easy access to it in the future. If a
problem occurs, check the instructions and follow recommendations given. If these suggestions
don’t eliminate your problem, call your servicing contractor.
DO NOT DESTROY. PLEASE READ CAREFULLY AND
KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
IMPORTANT
B6BW Series
INSTALLATION INSTRUCTIONS
2
TABLE OF CONTENTS
Important Safety Information ....................................2
Requirements & Codes ..............................................3
General Information ...................................................4
Before You Install this Unit .........................................4
Locating the Air Handler ............................................4
Minimum Clearances .................................................5
Operation of Air Handler During Construction ...........4
Installation in a Garage .............................................5
Plenums & Air Ducts .................................................5
Acoustical Duct Work .............................................5
Unconditioned Spaces ...........................................5
Filter Requirements ...................................................5
Air Handler Installation ..............................................6
Packaging Removal ...................................................6
Mounting Applications ...............................................6
Connecting Refrigerant Tubing ..................................6
System Depressurization .......................................7
Connecting the Linsets ..........................................7
Condensate Drainage ..............................................7
Electrical Wiring ..........................................................7
Line Voltage ...............................................................8
Grounding..................................................................9
Thermostat Connections ...........................................9
Confi guring Blower Speed for Multi Speed Units ....10
Selecting Continuous Low Speed Fan Operation ....10
Startup & Adjustments ............................................11
Before You Start the Unit .........................................11
Refrigerant Charging ...............................................11
Unit Maintenance ......................................................12
Troubleshooting ........................................................12
Figures & Tables .......................................................13
Figure 4. B6BW Physical Dimensions ..................13
Table 6. B6BW Specifi cations ..............................13
Table 7. Blower Performance Data .......................14
Wiring Diagrams ......................................................15
Figure 5. B6BW 5KW (1.5, 2, & 2.5 Ton) ..............15
Figure 6. B6BW 8KW/10KW (1.5, 2, & 2.5 Ton) ...16
Figure 7. B6BW 5KW/036 (3 Ton) ........................17
Figure 8. B6BW 8KW/10KW (3 Ton) ....................18
Location of Air Handler Components ......................19
Figure 9. Air Handler Components .......................19
Installation / Performance Checklist .......................20
IMPORTANT SAFETY INFORMATION
INSTALLER: Please read all instructions before servicing
this equipment. Pay attention to all safety warnings and
any other special notes highlighted in the manual. Safety
markings are used frequently throughout this manual to
designate a degree or level of seriousness and should not
be ignored. WARNING indicates a potentially hazardous
situation that if not avoided, could result in personal injury
or death. CAUTION indicates a potentially hazardous
situation that if not avoided, may result in minor or moderate
injury or property damage.
WARNING:
B6BW Air Handlers leave the factory with a
nitrogen holding charge. Use caution when
preparing coils for fi eld connections. If repairs
make it necessary for evacuation and charging,
it should only be attempted by qualified,
trained personnel thoroughly familiar with this
equipment. Some local codes require licensed
installation service personnel to service this
type of equipment. Under no circumstances
should the equipment owner attempt to install
and/or service this equipment. Failure to comply
with this warning could result in equipment
damage, personal injury, or death.
NITROGEN
HEALTH
FLAMMABILITY
REACTIVITY
0 Minimal Hazard
1 Slight Hazard
1
0
0
WARNING:
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow safety warnings exactly could
result in serious injury or property damage.
Improper servicing could result in dangerous
operation, serious injury, death or property
damage.
• Before servicing, disconnect all electrical power
to air handler.
When servicing controls, label all wires prior
to disconnecting. Reconnect wires correctly.
Verify proper operation after servicing.
3
REQUIREMENTS & CODES
WARNING:
This unit must be installed in accordance with
instructions outlined in this manual during
the installation, service, and operation of
this unit. Unqualifi ed individuals should not
attempt to interpret these instructions or
install this equipment. Failure to follow safety
recommendations could result in possible
damage to the equipment, serious personal
injury or death.
The installer must comply with all local codes and
regulations which govern the installation of this type
of equipment. Local codes and regulations take
precedence over any recommendations contained in
these instructions. Consult local building codes and the
National Electrical Code (ANSI CI) for special installation
requirements.
This equipment contains nitrogen gas. Installation or
servicing should only be performed by qualifi ed trained
personnel thoroughly familiar with this type equipment.
All electrical wiring must be completed in accordance
with local, state and national codes and regulations
and with the National Electric Code (ANSI/NFPA 70)
or in Canada the Canadian Electric Code Part 1 CSA
C.22.1.
Installation of equipment may require brazing operations.
Installer must comply with safety codes and wear
appropriate safety equipment (safety glasses, work
gloves, fi re extinguisher, etc.) when performing brazing
operations.
Install this unit only in a location and position as specifi ed
on pages 4 & 5. This unit is designed only for Indoor
installations and should be located with consideration
of minimizing the length of the supply and return ducts.
See Table 7 (page 14) and the rating plate for proper
circulating airfl ow data.
Follow all precautions in the literature, on tags, and
on labels provided with the equipment. Read and
thoroughly understand the instructions provided with
the equipment prior to performing the installation and
operational checkout of the equipment.
This air handler may be used for temporary heating
of buildings or structures under construction. See the
guidelines listed on page 4.
Air handler installations in a residential garage must be
installed as specifi ed on page 5.
The information listed below is for reference purposes only
and does not necessarily have jurisdiction over local or state
codes. Always consult with local authorities before installing
any gas appliance.
Duct Systems
US and CANADA: Air Conditioning Contractors Association
(ACCA) Manual D, Sheet Metal and Air Conditioning
Contractors National Association (SMACNA), or American
Society of Heating, Refrigeration, and Air Conditioning
Engineers (ASHRAE) Fundamentals Handbook
Electrical Connections
US: National Electrical Code (NEC) ANSI/NFPA 70
CANADA: Canadian Electrical Code CSA C22.1
General Installation
US: Current edition of the NFGC and the NFPA 90B. For
copies, contact the National Fire Protection Association
Inc., Batterymarch Park, Quincy, MA 02269; or American
Gas Association, 400 N. Capitol, N.W., Washington DC
20001 or www.NFPA.org
CANADA: NSCNGPIC. For a copy, contact Standard Sales,
CSA International, 178 Rexdale Boulevard, Etobicoke
(Toronto), Ontario, M9W 1R3 Canada
Safety
US: (NFGC) NFPA 54–1999/ANSI Z223.1 and the
Installation Standards, Warm Air Heating and Air
Conditioning Systems ANSI/NFPA 90B.
CANADA: CAN/CGA-B149.1 and .2–M00 National
Standard of Canada. (NSCNGPIC)
4
GENERAL INFORMATION
This appliance has been tested for capacity and effi ciency
in accordance with A.R.I. Standards and will provide
many years of safe and dependable comfort, providing
it is properly installed and maintained. Abuse, improper
use, and/or improper maintenance can shorten the life
of the appliance and create unsafe hazards. Please read
all instructions before installing the unit.
Before You Install this Unit
This equipment is securely packaged at the time of
shipment and upon arrival should be carefully inspected
for damage prior to installing the equipment at the job
site. Claims for damage (apparent or concealed) should
be fi led immediately with the carrier.
The cooling load of the area to be conditioned must be
calculated and a system of the proper capacity selected.
It is recommended that the area to be conditioned be
completely insulated and vapor sealed.
Check the electrical supply and verify the power supply
is adequate for unit operation. The system must be wired
and provided with circuit protection in accordance with
local building codes. If there is any question concerning
the power supply, contact the local power company.
Verify the air delivery of the air handler is adequate to
handle the static pressure drop of the coil, fi lter, and
duct work.
Table 1. Minimum Unit Clearances
INSTALLATION CLEARANCES
Left Side ......... 0 Inches Right Side ...... 0 Inches
Back ...............0 Inches
Front ...........
See Notes
NOTES:
Alcove Installations - Allow 24 in. minimum clearance
from front of unit to nearest wall or partition for servicing.
Recommended clearance is 36 in.
Closet installations - require a return air grill installed in
the door or a partially louvered door across the opening
for proper air circulation. For clearances 6” or greater, the
closet must have an open free area of 235 in
2
minimum.
For special clearances between 1” - 5”, requirements
are a louvered door with a minimum of 250 in
2
(1613
cm
2
) free area. A fully louvered closet door is strongly
recommended for both installation types.
REAR
RIGHT
SIDE
LEFT
SIDE
FRONT
Locating the Air Handler
Survey the job site to determine the best location for
mounting the unit. Consideration should be given to
availability of electric power, service access, and noise.
The dimensions of the room or alcove must be able
to accommodate the overall size of the unit and the
installation clearances listed in Table 1. Physical
dimensions for this air handler are also shown in Figure
4 (page 13).
The air handler should be installed before routing the
refrigerant tubing.
Minimum Clearances
This appliance must be installed in accordance with
clearances listed in Table 1. The air handler must be
installed with ample clearance for easy access to the
air fi lter, blower assembly, burner assembly, controls,
and vent connections.
Suffi cient clearance for unobstructed airfl ow through a
louvered door must be maintained in order to achieve
rated performance.
Operation of Air Handler During Construction
CAUTION:
Failure to follow these instructions will void the
factory warranty and may signifi cantly reduce
the life or the performance of the air handler,
and/or result in other unsafe conditions. It is
the responsibility of the installing contractor
to insure these provisions are met.
Operating an air handler in a construction environment
can cause the appliance a variety of problems. Proper
use of commercial portable space heating equipment
during construction is recommended. This air handler
may be used during construction if it is not in violation of
any applicable codes and the following criteria are met:
The installation (including electrical supply, gas supply,
and duct work), must meet all applicable codes and
be permanently installed according to the instructions
supplied with the air handler.
The air handler must be controlled by a properly installed
thermostat that complies with the current provisions
of the NEC (ANSI/NFPA 70) and all applicable codes
having jurisdiction. Thermostat connections must be
made in accordance with instructions supplied with the
air handler and thermostat.
The installation must include a properly installed fi lter in
the return air system with no by-pass air. The fi lter must
be inspected frequently and replaced when necessary.
Return air must be supplied unrestricted and located
such that dust and gases from construction activity are
not introduced into the circulating air system.
• Before occupying the structure: The fi lter must be
replaced or cleaned, the duct work must be inspected
and cleaned of any construction debris, and the furnace
5
must be cleaned and/or repaired if found to be dirty,
damaged, or malfunctioning in any way by a qualifi ed
HVAC technician. The air handler shall be inspected
and approved by applicable local authority even if this
requires redundant inspections.
• The serial number for the air handler used during
construction must be submitted in writing (fax and
email also acceptable). This information will be used to
track the long-term affects of air handler usage during
construction. Proof of this submittal shall be available for
the fi nal inspection of the air handler prior to occupancy.
Installation in a Garage
WARNING:
Do not place combustible materials on or against
the cabinet. Do not place fl ammable materials,
(gasoline, paint thinners, etc.) or any other
ammable vapors and liquids, in the vicinity
of the air handler.
The B6BW air handler may be installed in a residential
garage with the provision that the unit must be located or
protected to prevent physical damage by vehicles.
Standard for the Installation of Warm Air Heating and
Air Conditioning Systems (NFPA No. 90B).
Design the duct work according to methods described
by the Air Conditioning Contractors of America (ACCA).
The return air duct must have the same free area as
the opening provided on the blower coil unit.
The ducts should be appropriately sized to the capacity
of the air handler to ensure its proper airfl ow rating.
It is good practice to seal all connections and joints
with industrial grade sealing tape or liquid sealant.
Requirements for sealing ducts vary from region to
region. Consult with local codes for requirements specifi c
to your area.
Acoustical Duct Work
Certain installations may require the use of acoustical
lining inside the supply duct work.
Acoustical insulation must be in accordance with the
current revision of the Sheet Metal and Air Conditioning
Contractors National Association (SMACNA) application
standard for duct liners.
Duct lining must be UL classifi ed batts or blankets with
a fi re hazard classifi cation of FHC-25/50 or less.
Fiber duct work may be used in place of internal duct
liners if the fi ber duct work is in accordance with the
current revision of the SMACNA construction standard
on fi brous glass ducts. Fibrous duct work and internal
acoustical lining must be NFPA Class 1 air ducts when
tested per UL Standard 181 for Class 1 ducts.
Unconditioned Spaces
All duct work passing through unconditioned space must
be properly insulated to minimize duct losses and prevent
condensation. Use insulation with an outer vapor barrier.
Refer to local codes for insulation material requirements.
Filter Requirements
B6BW Air Handlers are supplied with a single air fi lter
when shipped from the factory. Accessing the fi lter does
not require tools and can be removed from the front of
the unit. See Unit Maintenance (page 12) for fi lter sizes
and installation information.
WARNING:
Never operate the furnace without a fi lter in
place. Dust and lint can build up on internal
components, resulting in loss of effi ciency,
equipment damage, and possible fi re.
Plenums & Air Ducts
This unit is designed only for use with a supply and return
duct. Air ducts should be installed in accordance with the
standards of the National Fire Protection Association
Standard for Installation of Air Conditioning Systems
(NFPA 90A), Standard for Installation of Residence Type
Warm Air Heating and Air Conditioning Systems (NFPA
90B), and all applicable local codes. NFPA publications
are available by writing to: National Fire Protection
Association, Batterymarch Park, Quincy, ME 02269 or visit
www.NFPA.org on the web.
WARNING:
All return ducts must be secured to the air
handler with sheet metal screws. All return
ducts must be adequately sealed. When return
air is provided through the bottom of the unit,
the joint between the air handler and the return
air plenum must be air tight.
Return air and circulating air ducts must not be
connected to any other heat producing device
such as a fi replace insert, stove, etc. This may
result in fi re, explosion, carbon monoxide
poisoning, personal injury, or property damage.
Plenums and air ducts must be installed in accordance
with the Standard for the Installation of Air Conditioning
and Ventilating Systems (NFPA No. 90A) or the
6
AIR HANDLER INSTALLATION
The B6BW Air Handler is shipped ready for vertical upfl ow
installation and can be mounted directly on a wall or
recessed between framing studs as shown in Figure 1 .
Units are also approved for closet or alcove installation
with zero clearance to combustibles. See Table 1 (page
4) for required installation clearances. This appliance is
only for indoor use.
The unit must be leveled at installation and attached to
a properly installed duct system.
The surface that the air handler is mounted on must
provide sound physical support of the unit.
The air handler must be installed so that all electrical
components are protected from water.
If a louvered door is installed across the front of this
unit, the appliance must be mounted fl ush or behind
front edge of fi nished wall. See Figure 1.
Packaging Removal
Remove the shipping crate and User’s Manual from the
equipment. Take care not to damage the tubing connections
when removing the crate.
Mounting Applications
Units have a bottom and/or front return. Units are shipped
for installation in a front return application. Front close-
off panel (if supplied) may be discarded. If installed in a
bottom return application, attach bottom access panel to
the front of the unit below the top service panel.
NITROGEN
HEALTH
FLAMMABILITY
REACTIVITY
0 Minimal Hazard
1 Slight Hazard
1
0
0
If the air handler is recessed in a wall, attachment to the
framing studs are through the inside of the front fl ange.
For hanging applications, these units are provided with
2-piece offset hanging bracket (Figure 1) attached to the
rear of the cabinet. Mounting bracket dimensions are
shown in Figure 4 (page 13).
Connecting Refrigerant Tubing
WARNING:
Evaporator Coils are factory shipped with a
nitrogen charge. Avoid direct face exposure
or contact with valve when gas is escaping.
Always ensure adequate ventilation is present
during the depressurization process. Address
any uncertainties before proceeding. Failure
to comply with this warning could result in
equipment damage, personal injury, or death.
18"
(457 mm)
24” Clearance from
nearest wall or
partition
Full Louvered
Door
Wall
Mount
Closet
Installation
Alcove
Installation
6”
(152mm)
Typical Closet Door
with Return Air Grill
Installed
OR
Recessed
Wall
Wall
2-Piece
Mounting
Bracket
24” Clearance from
nearest wall or
partition
Figure 1. Unit Installation
7
CAUTION:
This unit uses refrigerant R-410A. DO NOT use
any other refrigerant in this unit. Use of another
refrigerant will damage the unit.
• Every effort should be made by the installer to ensure
that the fi eld installed refrigerant containing components
of the system have been installed in accordance with
these instructions and sound installation practices to
insure reliable system operation and longevity.
Always refer to the installation instructions supplied with
the outdoor unit for piping requirements. The suction
and liquid lines must be sized in accordance with the
condensing unit specifi cations. See Figure 4 (page 13)
for liquid and suction line locations.
• When connecting refrigerant linesets together, it is
recommended that dry nitrogen be fl owing through the
joints during brazing. This will prevent internal oxidation
and scaling from occurring.
Refrigerant tubing should be routed in a manner that
minimizes the length of tubing and the number of bends
in the tubing. It should be supported in a manner that
prevents it from vibrating or abrading during system
operation. Tubing should be kept clean of foreign debris
during installation.
If precise forming of refrigerant lines is required, a copper
tubing bender is recommended. Avoid sharp bends and
contact of the refrigerant lines with metal surfaces.
Refrigerant lines should be wrapped with pressure
sensitive neoprene or other suitable material where
they pass against sharply edged sheet metal.
CAUTION:
Before brazing the B6BW, remove the core from
the service port. Failure to comply may result in
leakage at the service valve. Replace the core
and cap once brazing is complete.
The B6BW air handler is charged through service valves
on the end of the liquid tube for each circuit. These must
be removed before brazing the line sets.
System Depressurization
1. Remove the cap from the end of the liquid line.
2. Verify pressurization by depressing the Schrader valve
on the end of the liquid line. Listen for any escaping gas.
If there is no pressure, test the unit for leakage.
If leakage is found, clearly mark the location of the leak
and return the unit to the distributor for processing.
• If no leaks are found, the air handler may be installed.
3. Depress the valve to relieve all pressure from the coil.
Connecting the Linesets
Notes: Before proceeding, perform steps 1 - 3 in the
System Depressurization section.
1. Route and cut both lineset tubes to proper length in
accordance with the outdoor unit specifi cations. Verify
the ends are round, clean, and free of any burrs.
2. Connect the suction and liquid lineset tubes.
CAUTION:
It is recommended that a wet rag be wrapped
around the suction line before applying heat.
Failure to keep components cool during brazing
may result in structural damage, premature
equipment failure, or possible personal injury.
3. Braze the individual connections with dry nitrogen fl owing
through the joints. This will prevent internal oxidation
and scaling from occurring.
4. Wrap the refrigerant lines with pressure sensitive
neoprene or other suitable material especially where
the lines enter the opening in the sheet metal.
5. Evacuate the system of moisture and non-condensables
to prevent low effi ciency operation or damage to the
unit. The suggested range of evacuation is 250 - 500
microns.
6. Charge the system with refrigerant. Refer to the
outdoor unit installation manual for additional charging
instructions.
7. Check the system for leaks, including the lineset and the
brazed joints. NOTE: Apply a soap and water solution on
each joint or union with a small paintbrush. If bubbling
is observed, the connection is not adequately sealed.
8. Properly dispose of all removed parts.
Condensate Drainage
The drain pan that is supplied with this air handler contains
a primary and secondary drain fi tting. The condensate is
drained from the unit through two 3/4” male pipe fi ttings
located on the front side of the unit as shown in Figure
2 (page 8).
CAUTION:
The air handler must be level to ensure proper
condensate drainage. An unlevel installation
may result in structural damage, premature
equipment failure, or possible personal injury.
The method for disposing of condensate varies according
to local codes. Consult your local code or authority
having jurisdiction.
The drain lines can be routed out the bottom, left or right
side of the air handler, but must maintain a downward
slope to ensure proper condensate drainage. If the
bottom access panel is moved to the front (for bottom
return air), the condensate drain tubes must be routed
8
Rubber
Washers
Side Drainage
Bottom Drainage
1/2” I.D.
Drain Tubes
3/4” NPT Adapters
w/ 1/2” Hose Barb
NOTES:
1. Field supplied drain lines must be looped to form a trap.
2. Drain lines must be routed to the outside of the cabinet.
3. Avoid sharp bends and pinching of the tubing.
Knockouts for condensate drain tubes
(bottom, left, or right side of unit
Primary & Secondary
Drain Locations
See Notes
See Notes
Figure 2. Condensate Drainage
thru one of the side openings. DO NOT route the
condensate drain tubes thru the front panel.
Drain pan MUST be drained with fi eld supplied tubing and
looped to form a trap. Failure to install a trap could result
in condensation overfl owing the drain pan, resulting in
substantial water damage to surrounding area. Both
drains must be trapped separately. See Figure 2.
It is recommended that both drain tubes have a minimum
internal diameter of 1/2” and be separately routed to
a suitable drain, avoiding sharp bends and pinching of
the lines. Refer to local codes and restrictions for proper
condensate disposal requirements.
• Both adapters should be made of PVC or similar
material and contain a rubber washer. Hand tightened
the adapters to the drain pan. DO NOT use pliers or
any other tools. Overtightening may crack the drain
pan and cause condensate to leak.
During system checkout, inspect the drain line and
connections to verify proper condensate drainage.
ELECTRICAL WIRING
WARNING:
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow safety warnings exactly could
result in serious injury or property damage.
Improper servicing could result in dangerous
operation, serious injury, death or property
damage.
• Before servicing, disconnect all electrical power
to air handler.
When servicing controls, label all wires prior
to disconnecting. Reconnect wires correctly.
Verify proper operation after servicing.
• Electrical connections must be in compliance with
all applicable local codes and ordinances, and with
the current revision of the National Electric Code
(ANSI/NFPA 70).
For Canadian installations, the electrical connections
and grounding shall comply with the current Canadian
Electrical Code (CSA C22.1 and/or local codes).
Line Voltage
An electrical disconnect must be located within sight
of and readily accessible to the unit. This switch shall
be capable of electrically de-energizing the outdoor unit.
See unit data label for proper incoming fi eld wiring. Any
other wiring methods must be acceptable to authority
having jurisdiction.
• It is recommended that the line voltage to the unit be
supplied from a dedicated branch circuit containing the
correct fuse or circuit breaker for the unit.
Overcurrent protection must be provided at the branch
circuit distribution panel and sized as shown on the unit
rating label and according to applicable local codes. See
the unit rating plate and Table 2 (page 9) for maximum
circuit ampacity and maximum overcurrent protection
limits.
Refer to the unit wiring label for proper high and low
voltage wiring.
Use only copper wire for the line voltage power supply
to this unit. Use proper code agency listed conduit and
a conduit connector for connecting the supply wires to
the unit.
• If replacing any of the original wires supplied with the
unit, the replacement wire must be copper wire consisting
of the same gauge and temperature rating.
Provide power supply for the unit in accordance with
the unit wiring diagram, and the unit rating plate. The
installer should become familiar with the wiring diagram/
schematic before making any electrical connections to
the unit. See Figures 5 - 8 (pages 15 - 18).
9
All 208/230 Volt units are shipped from the factory wired
for 240 volt operation. For 208V operation, remove the
lead from the transformer terminal marked 240V and
connect it to the terminal marked 208V.
Grounding
WARNING:
The unit cabinet must have an uninterrupted or
unbroken electrical ground to minimize personal
injury if an electrical fault should occur. Do not
use gas piping as an electrical ground!
This unit must be electrically grounded in accordance
with local codes or, in the absence of local codes, with
the National Electrical Code (ANSI/NFPA 70) or the CSA
C22.1 Electrical Code. Use the grounding lug provided in
the control box for grounding the unit.
Minimum Circuit Ampacity & Maximum Overcurrent Protection
Model #
B6BW-
240VAC, 50 & 60Hz 208VAC, 50 & 60Hz
MCA MOP MCA MOP
018K-05 26.1 30 22.8 25
018K-08 40.2 50 34.8 40
024K-05 26.5 30 23.1 30
024K-08 40.6 50 35.1 40
024K-10 51.5 60 44.8 50
030K-05 26.6 30 23.2 30
030K-08 40.8 50 35.2 40
030K-10 51.6 60 44.9 50
036K-05 29.2 30 25.9 30
036K-08 43.4 50 37.9 40
036K-10 54.2 60 47.5 50
MCA = Minimum Circuit Ampacity, MOP = Maximum Over-Current
Protection
Table 2. Electrical Rating Data
Thermostat Connections
Thermostat connections shall be in accordance with the
instructions supplied with the thermostat and the indoor
equipment. The low voltage wires must be properly
connected to the units low voltage terminal block.
A single stage thermostat is used with this equipment
and must operate in conjunction with any installed
accessories. Typical AC and air handler hookups are
shown in Figure 3.
The thermostat should be mounted about 5 feet above the
oor on an inside wall. DO NOT install the thermostat on
an outside wall or any other location where its operation
may be adversely affected by radiant heat from fi replaces,
sunlight, or lighting fi xtures, and convective heat from
warm air registers or electrical appliances. Refer to the
thermostat manufacturer’s instruction sheet for detailed
mounting and installation information.
Thermostat
Thermostat
GR
W2
E
Y
G
R
W2
E
Y
CO
NOTE: Jumper between
W2 & E is required when
no OD T-stat is used.
Grey
White
W1
Red R
Green
G
R
W2
OD
Stat
C
O
Y
C
Air Handler Heat pump
Typical Heat Pump & Wall Mount Air Handler Connection
Air Handler Air
Conditioner
Typical AC & Wall Mount Air Handler Connection
Grey
C
White
W1
Red R
Green
G
C
Y
Figure 3. Typical Thermostat Connections
10
Confi guring the Blower Speed for Multi-Speed
Units
The blower speed is preset at the factory for operation
at the same speed for heating and cooling, by using the
jumping terminal on the blower motor and connecting it
to the desired speed with both the red and black wires
connected to the jumping terminal.
CAUTION:
To avoid personal injury or property damage,
make sure the motor leads do not come into
contact with any uninsulated metal components
of the unit.
For optimum system performance and comfort, it may be
necessary to change the factory set speed. See Table 7
for airfl ow data.
1. Disconnect all electrical power to the unit and remove
the upper door.
2. Remove the black and red wires from the blower motor
jumping terminal. Discard the blower motor jumping
terminal.
3. Connect the heating speed wire (red) and the cooling
speed wire (black) to the desired blower speed marked
on the terminal block of the blower motor.
Table 3. Control Board Operation
Control Signal
& MODE
Operation Total KW Board Action
W
(EHEAT)
ON
5 KW
Stage 1 Heat on instantly
Heat blower on after 3 second delay
10 KW
Stage 1 Heat on instantly
Heat blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
OFF
Heat stages off instantly
Blower off after 15 second delay
W & Y
(AUX HEAT)
ON
5 KW
Stage 1 Heat on instantly
Cool blower on after 3 second delay
10 KW
Stage 1 Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
OFF
Heat stages off instantly
Heat blower turns off after 40 second delay
G
(FAN)
ON Cool blower on after 3 second delay
OFF Cool blower off instantly
Y
(H.P. & COOL)
ON Cool Blower on after 3 second delay
OFF Cool Blower off after 40 second delay
Minimum Heating Speed:
018 = Low
024 = High
030 & 036 = Medium
Standard 2 Speed Motors:
Terminal 4 = Hi speed
Terminal 5 = Low speed
Terminal 6 = Not Used
Standard 3 Speed Motors:
Terminal 4 = Hi speed
Terminal 5 = Med speed
Terminal 6 = Low speed
5 Speed Motor Terminals (036 units or T-Board)
Terminal M1 = Low speed
Terminal M2 = Medium Low speed
Terminal M3 = Medium speed
Terminal M4 = Medium Hi speed
Terminal M5 = Hi speed
4. Replace the upper door and secure it to the unit.
5. Restore power to the unit.
Selecting continuous low speed fan operation
(Standard Blower)
The air handler is equipped with the option of continuous
low speed fan operation. When G is energized without Y/
Y2, the air handler will operate using the Cooling speed.
With G & Y/Y2 or Y/Y2 is energized, the air handler will
operate in the selected cooling speed (including 40 sec
blower-off delay).
11
STARTUP & ADJUSTMENTS
WARNING:
The evaporator coil is shipped from the factory
with a nitrogen charge. Use caution when
preparing coils for fi eld connections. If repairs
make it necessary for evacuation and charging,
it should only be attempted by qualified,
trained personnel thoroughly familiar with this
equipment. Some local codes require licensed
installation service personnel to service this
type of equipment. Under no circumstances
should the equipment owner attempt to install
and/or service this equipment. Failure to comply
with this warning could result in equipment
damage, personal injury, or death.
NITROGEN
HEALTH
FLAMMABILITY
REACTIVITY
0 Minimal Hazard
1 Slight Hazard
1
0
0
5. Inspect the unit rating plate for the proper type of
refrigerant and quantity.
6. Weigh in the proper amount of new (or reclaimed)
refrigerant.
Refrigerant Charging
The system refrigerant charge can be checked and
adjusted through the service ports provided at the front
panel. Use only gauge lines which have a Schrader
depression device present to actuate the valve.
Air Circulation
Running the Blower Continuously
Set the thermostat’s system mode to OFF and the
thermostat’s fan mode to ON. The blower motor should
run continuously. Check for air delivery at the register(s).
Ensure that there are no obstructions at the registers or
in the ducts.
Turning the Blower Off
Set thermostat’s fan mode to AUTO, the blower will shut
down immediately.
NOTE: If blower is turning opposite of arrow direction, shut
off main power to the unit and switch any two fi eld wires
at the disconnect. DO NOT alter unit wiring.
System Cooling
1. Set the thermostat’s system mode to COOL and fan
mode to AUTO. Lower the thermostat’s temperature
mode below room temperature and observe that the
blower energizes. Check the air being discharged at
the register is cooler than room temperature. Verify
unit refrigerant pressures are in order. Blower should
be turning in direction indicated by arrow. NOTE: If
refrigerant pressures are abnormal and blower is rotating
in the opposite direction of the arrow, shut off main
power to the unit and switch any two fi eld wires at the
disconnect. Ensure proper rotation of both compressors.
DO NOT alter unit wiring. Listen for any unusual noises.
Locate the source and correct as needed.
2. Allow the unit to run for several minutes and then set
the thermostat’s temperature above room temperature.
Verify the blower cycles off with the thermostat.
System Heating
1. Set the thermostat’s system mode to HEAT and the fan
mode to AUTO. Increase the thermostat’s temperature
above room temperature and observe that the blower
energizes. Check the air being discharged at the register
is warmer than room temperature.
2. Allow the unit to run for several minutes and then set
the thermostat’s temperature below room temperature.
Verify the blower cycles off with the thermostat.
Before You Start the Unit
Prior to start-up, complete the following inspections:
Verify the unit is level and mounted securely to the wall.
Also make sure the air handler is properly located with
adequate clearances for servicing the unit as listed in
Table 1 (page 4).
Check condensate drain line(s) for proper drainage.
Verify the surrounding area and top of the unit is free
from obstructions and debris.
Check all duct connections. Make sure the duct work
is adequately sealed to prevent air leakage.
Check all coil connections for leaks.
Verify that the line voltage power leads are securely
connected and the unit is properly grounded.
Verify the thermostat is wired correctly. Make sure all
low voltage wires are securely connected to the correct
leads of the low voltage terminal strip.
Verify the power supply branch circuit overcurrent
protection is sized properly.
Verify fi lter is properly and securely installed.
IMPORTANT: Before you start unit, perform the following
procedures to install the initial charge on units that are
factory shipped with a nitrogen holding charge:
1. Read all installation instructions fi rst.
2. Purge the nitrogen holding charge.
3. Evacuate the unit to 350 - 500 microns.
4. Allow the unit to remain under vacuum for at least 30
minutes.
12
UNIT MAINTENANCE
Proper maintenance is most important to achieve the best
performance from a furnace. Follow these instructions for
years of safe, trouble free operation.
WARNING:
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow safety warnings exactly could
result in serious injury or property damage.
Improper servicing could result in dangerous
operation, serious injury, death or property
damage.
• Before servicing, disconnect all electrical power
to air handler.
When servicing controls, label all wires prior
to disconnecting. Reconnect wires correctly.
Verify proper operation after servicing.
These maintenance instructions are primarily intended
to assist qualifi ed technicians experienced in the proper
maintenance and operation of this appliance.
Always reinstall the doors on the furnace after servicing
or cleaning/changing the fi lters. Do not operate the
furnace without all doors and covers in place.
Verify that the thermostat is properly installed and is
not being affected by drafts or heat from lamps or other
appliances.
To achieve the best performance and minimize
equipment failure, it is recommended that a yearly
maintenance checkup be performed. At a minimum,
this check should include the following items:
Air Filter(s)
WARNING:
Never operate the furnace without a fi lter in
place. Dust and lint in the return air can build
up on internal components, resulting in loss of
effi ciency, equipment damage, and possible fi re.
B6BW Air Handlers are supplied with a single air fi lter
when shipped from the factory. It is recommended that
the fi lter be cleaned or replaced monthly. Newly built or
recently renovated homes may require more frequent
changing until the construction dust has minimized. Filter
sizes shown in Table 4 are available at most local retailers.
Filters designed to remove smaller particles such as
pollen, may require additional maintenance.
Blower Compartment
Dirt and lint can create excessive loads on the motor
resulting in higher than normal operating temperatures
and shortened service life. It is recommended that the
blower compartment be cleaned of dirt or lint that may
have accumulated in the compartment or on the blower
and motor as part of the annual inspection.
Blower Fan Wheel
Inspect the blower wheel blades for accumulations of dirt
and clean if necessary. Inspect mounting nut for tightness
when done.
Blower Motor & Assembly
Inspect the blower assembly and motor mounting
brackets for tightness and corrosion. Correct defi ciencies
if necessary. The blower motor contains sealed bearings
and under normal operating conditions, no maintenance
is necessary for the life of the equipment.
TROUBLESHOOTING
If the air handler fails to operate, check the following:
• Is the electric turned on?
• Is the thermostat operating properly?
• Are the blower compartment door(s) in place?
• Is the furnace disconnect closed?
Has the circuit breaker tripped or the control board fuse
burned open?
• Are any manual reset switches open?
• Is the fi lter dirty or plugged?
Is the LED on the furnace control board constantly ON?
If not, refer to Table 5 to determine fault condition.
Red LED (AN2) Diagnostic Description
OFF Control Fault (No Power)
Flash Blower Fault
ON Normal Operation
Table 5. Furnace Control Board Fault Conditions
Model Number Filter Size
B6BW-018K
16” x 20 x 1”
B6BW-024K
B6BW-030K 20” x 20 x 1”
B6BW-036K 24” x 20 x 1”
Table 4. Filter Sizes
13
“B”
18 5/8
1
1
Ø3/8" K.O.
3/4
15
1 1/2
1 1/2
2 5/8
6 1/4
10 1/2
19
10 1/2
Drain
Knockout
Optional
Refrigerant
Line Entry
1 5/8
20 1/2
1 5/8
Liquid Line
2 1/8
Suction
Line
1
7/8
1 1/4
1
1 7/8
3/4
Ø3/8" Low
Voltage
Optional
Refrigerant
Line Entry
Drain
Knockout
Ø1 1/8" K.O.
Power Entry
Ø1 1/8" K.O.
Power Entry
1 5/8
FRONT VIEW
RIGHT
SIDE
LEFT
SIDE
BOTTOM
VIEW
3/4
TOP
VIEW
Primary & Secondary
Drain Connections
“A”
Table 6. B6BW Specifi cations
Model
B6BW-
Refrigerant Connections
Supply Air
Duct Dimension
AB
Suction Dia. Liquid Dia.
018K 3/4 3/8 9 x 17 1/4 36 3/8 9 1/2
024K 3/4 3/8 9 x 17 1/4 36 3/8 9 1/2
030K 3/4 3/8 9 x 17 1/4 43 1/2 9 1/2
036K 3/4 3/8 15 x 17 1/4 43 1/2 15 1/2
Figure 4. B6BW Physical Dimensions
FIGURES & TABLES
8”
8”
7/8”
20 3/8”
10 3/16”
Ø 7/32”
(3 places)
3 1/2”
1 3/4”
1 3/4”
.07”
MTG BRACKET
14
AIRFLOW DATA
Table 7. Blower Performance Data
036K
Motor Speed 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Low
936 901 891 840 789 739 688 613
Med-Low
1,160 1,122 1,087 1,046 1,001 950 899 855
Medium
1,287 1,253 1,213 1,178 1,142 1,092 1,049 1,002
Med-High
1,434 1,394 1,353 1,328 1,297 1,248 1,220 1,202
High
1,550 1,515 1,495 1,457 1,429 1,416 1,388 1,355
030K
Motor Speed 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Low
869 832 795 758 704 639 579 507
Medium
933 903 866 820 770 714 640 576
High
1,014 971 929 884 833 780 714 640
024K
Motor Speed 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Low
846 795 756 707 668 589 533 467
High
926 890 845 791 732 672 603 536
018K
Motor Speed 0.1 0.2 0.3 0.4 0.5 0.6
Low
665 645 592 521 422
326
High
769 719 656 565 459 347
NOTES:
1) Airfl ow is shown in cfm, +/- 5%.
2) External static pressure is shown in inches W.C.
3) All airfl ows are measured with fi lter and with dry coil. For wet coil, subtract .1” external static pressure.
4) See unit nameplate or installation instructions for maximum recommended external static pressure.
15
WIRING DIAGRAMS
3. The transformer may have a dual voltage primary tap. Match the tap position
with the supply voltage used.
4. If the Internal wiring is replaced, use only 105°C copper wire of the same
gauge.
0410
FIELD WIRING
LEGEND:
LOW VOLTAGE
HIGH VOLTAGE
WIRING DIAGRAM
Wall Mount B6BW (5KW)
NOTES:
1. The blower motor speed tap connection may not be as shown. See
the Installation Instructions.
2. Disconnect all power before servicing.
710937B
(REPLACES 710937A)
¢710937;¤
CONTROL
BOARD
R
C
L2
L1
HEAT
COOL
EAC
L1
L2
HEATER
BLWDTC
R
Y
W
GC
R
YELLOW
WHITE
GRAY
RED
GREEN
TRANSFORMER
24V
230V
LIMIT
ELEMENT RELAY
ELEMENT
SUPPLY VOLTAGE
PSC
MOTOR
(3-SPEED)
1
3
5
2
4
6
1=COM
2=CAP.
3=CAP.
4=HI
5=MED
6=LOW
CAP.
MOTOR CONNECTION
SEE NOTE
NOTE:
1. B6BW-030: USE 3-SPEED MOTOR CONNECTION AS ABOVE.
2. B6BW-018 AND B6BW-024: USE 2-SPEED MOTOR CONNECTION.
2-SPEED
MTR
1=COM
2=CAP.
3=CAP.
4=HI
5=LOW
1
3
5
2
4
6
CAP.
L2
HEAT
COOL
RED
GRAY
WHITE
BLACK
GRAY
CIRCUIT
BREAKER
ORANGE
COM
NO
BLACK
RED
RED
BLACK
BLACK
WHITE
HARNESS
HARNESS
HARNESS
CONNECTOR
RED
WHITE
BLACK
BLACK
BROWN
BROWN
CONNECTOR
WHITE
RED
BLACK
BROWN
BROWN
Figure 5. Wiring Diagram for B6BW-018K, B6BW-024K, & B6BW-030K (1.5, 2, & 2.5 Ton Units)
16
3. The transformer may have a dual voltage primary tap. Match the tap position
with the supply voltage used.
4. If the Internal wiring is replaced, use only 105°C copper wire of the same
gauge.
0510
FIELD WIRING
LEGEND:
LOW VOLTAGE
HIGH VOLTAGE
WIRING DIAGRAM
Wall Mount B6BW (8KW/10KW)
NOTES:
1. The blower motor speed tap connection may not be as shown. See
the Installation Instructions.
2. Disconnect all power before servicing.
710938B
(REPLACES 710938A)
¢710938A¤
CONTROL
BOARD
R
C
L2
L1
HEAT
COOL
EAC
L1
L2
HEATER
BLWDTC
R
Y
W
GC
R
BLACK
WHITE
GRAY
RED
GREEN
TRANSFORMER
24V
230V
LIMIT
ELEMENT RELAY
ELEMENT RELAY
ELEMENT
ELEMENT
SUPPLY VOLTAGE
NOTE:
1. B6BW-030: USE 3-SPEED MOTOR CONNECTION AS ABOVE.
2. B6BW-018 AND B6BW-024: USE 2-SPEED MOTOR CONNECTION.
MOTOR CONNECTION
SEE NOTE
PSC
MOTOR
(3-SPEED)
1
3
5
2
4
6
1=COM
2=CAP.
3=CAP.
4=HI
5=MED
6=LOW
CAP.
2
1
4
3
CIRCUIT
BREAKER
GRAY
ORANGE
RED
WHITE
BLACK
GRAY
2-SPEED
MTR
1=COM
2=CAP.
3=CAP.
4=HI
5=LOW
1
3
5
2
4
6
CAP.
L2
HEAT
COOL
GRAY
COMNO
COMNO
BLUE
CONNECTOR
RED
WHITE
BROWN
BROWN
BLACK
BLACK
RED
RED
RED
RED
BLACK
BLACK
BLACK
WHITE
BLACK
HARNESS
HARNESS
BLACK
HARNESS
CONNECTOR
WHITE
RED
BLACK
BROWN
BROWN
Figure 6. Wiring Diagram for B6BW-018K, B6BW-024K, & B6BW-030K (1.5, 2, & 2.5 Ton Units)
17
3. The transformer may have a dual voltage primary tap. Match the tap position
with the supply voltage used.
4. If the Internal wiring is replaced, use only 105°C copper wire of the same
gauge.
0410
FIELD WIRING
LEGEND:
LOW VOLTAGE
HIGH VOLTAGE
WIRING DIAGRAM
Wall Mount B6BW (5KW/036)
NOTES:
1. The blower motor speed tap connection may not be as shown. See
the Installation Instructions.
2. Disconnect all power before servicing.
¢711038®¤
711038B
(REPLACES 711038A)
CIRCUIT
BREAKER
LIMIT
ELEMENT RELAY
ELEMENT
SUPPLY VOLTAGE
CONTROL
BOARD
R
C
L2
L1
HEAT
COOL
EAC
L1
L2
BLWDTC
R
Y
W
GC
R
YELLOW
WHITE
GRAY
RED
GREEN
TRANSFORMER
24V
230V
ECM
MOTOR
COM1
U1 U2
T-BOARD
RED
BLACK
WHITE
GRAY
RELAY 1
RELAY 2
HEATER
ORANGE
BLACK
WHITE
GRAY
COM
NO
21
4
3
21
4
3
M1
M2
M3
M4
M5
HUM
RED
BLACK
BLACK
WHITE
RED
BLACK
RED
GRAY
BLACK
HARNESS
HARNESS
HARNESS
RED
WHITE
BLACK
RED
GRAY
RED
BLACK
BLACK
WHITE
Figure 7. Wiring Diagram for B6BW-036K-05 (3 Ton Units)
18
3. The transformer may have a dual voltage primary tap. Match the tap position
with the supply voltage used.
4. If the Internal wiring is replaced, use only 105°C copper wire of the same
gauge.
0510
FIELD WIRING
LEGEND:
LOW VOLTAGE
HIGH VOLTAGE
WIRING DIAGRAM
Wall Mount B6BW (8KW/10KW/036)
NOTES:
1. The blower motor speed tap connection may not be as shown. See
the Installation Instructions.
2. Disconnect all power before servicing.
¢711039&¤
711039B
(REPLACES 711039A)
CONTROL
BOARD
R
C
L2
L1
HEAT
COOL
EAC
L1
L2
BLWDTC
R
Y
W
GC
R
CIRCUIT
BREAKER
YELLOW
WHITE
GRAY
RED
GREEN
TRANSFORMER
24V
230V
ELEMENT RELAY
ELEMENT RELAY
ELEMENT
ELEMENT
SUPPLY VOLTAGE
ECM
MOTOR
COM1
U1 U2
T-BOARD
RED
BLACK
WHITE
GRAY
BLACK
WHITE
RELAY 1
RELAY 2
HEATER
BLUE
ORANGE
LIMIT
2
1
4
3
COMNO
COM
NO
21
4
3
21
4
3
M1
M2
M3
M4
M5
HUM
GRAY
RED
GRAY
BLACK
BLACK
RED
RED
RED
BLACK
BLACK
BLACK
WHITE
HARNESS
HARNESS
HARNESS
RED
WHITE
RED
BLACK
BLACK
GRAY
RED
GRAY
RED
BLACK
BLACK
WHITE
Figure 8. Wiring Diagram for B6BW-036K-08 & B6BW-36K-10 (3 Ton Units)
19
Circuit
Breaker (60A)
Coil
Assembly
Distributor
Mounting
Bracket
Drain Pan
Heating Element
Assembly
Limit
Switch
Element Relay
Blower Housing
Transformer
Capacitor
Blower Wheel
T-Board
PCB
Board
Motor Mount
Blower Motor
Figure 9. Air Handler Components
LOCATION OF AIR HANDLER COMPONENTS
709090A (Replaces 7090900)
¢709090$¤
INSTALLATION / PERFORMANCE CHECK LIST
INSTALLER NAME:
CITY: STATE:
INSTALLATION ADDRESS:
CITY: STATE:
UNIT MODEL #
UNIT SERIAL #
Minimum clearances per Table 1
(page 4)?
YES NO
Is the unit properly installed and
leveled?
YES NO
Does condensate drain properly
in both drain tubes?
YES NO
Has the owner’s information been
reviewed with the home-owner?
YES NO
Has the literature package been
left near the appliance?
YES NO
ATTENTION INSTALLERS:
It is your responsibility to know this product better than your customer.
This includes being able to install the product according to strict
safety guidelines and instructing the customer on how to operate
and maintain the equipment for the life of the product. Safety should
always be the deciding factor when installing this product and using
common sense plays an important role as well. Pay attention to
all safety warnings and any other special notes highlighted in the
manual. Improper installation of the furnace or failure to follow safety
warnings could result in serious injury, death, or property damage.
These instructions are primarily intended to assist qualifi ed individuals
experienced in the proper installation of this appliance. Some local
codes require licensed installation/service personnel for this type of
equipment. Please read all instructions carefully before starting the
installation. Return these instructions to the customer’s package for
future reference.
ELECTRICAL SYSTEM:
Electrical connections tight? YES NO
Line voltage polarity correct? YES NO
Supply Voltage: ____________________________
_______(V)
Has the thermostat been calibrated?
YES NO
Is the thermostat level?
YES NO
Is the heat anticipator setting correct?
YES NO
VENTING SYSTEM:
Is there adequate fresh air supply for
ventilation?
YES NO
Vent free from restrictions? YES NO
Filter properly installed? YES NO
Filter clean? YES NO
Flue connections tight? YES NO
Is there proper draft? YES NO
Return Air Temp: ____________________________
_______(° F)
Supply Air Temp: ___________________________________(° F)
Temperature Rise: __________________________________(° F)
PROPOSITION 65 WARNING: This product
contains chemicals known to the state of
California to cause cancer, birth defects or
other reproductive harm.
WARNING:
Specifi cations & illustrations subject to change without notice or incurring obligations.
O’ Fallon, MO | Printed in U.S.A. (06/10)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Broan B6BW Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI