LG PHNFP14A0.ENCXBTK Installation guide

Type
Installation guide

LG PHNFP14A0.ENCXBTK:

This device is a 485 Gateway(C, R), part of an air conditioning system. It allows you to connect multiple indoor units to a central controller, giving you centralized control over your entire HVAC system. The device features RS-485 communication, which is a reliable and widely used protocol for industrial automation and building management systems. It also has a variety of LED indicators to provide status updates and troubleshooting information.

Here are some of the key capabilities of the LG PHNFP14A0.ENCXBTK:

  • Centralized control of multiple indoor units
  • RS-485 communication for reliable data transfer

LG PHNFP14A0.ENCXBTK:

This device is a 485 Gateway(C, R), part of an air conditioning system. It allows you to connect multiple indoor units to a central controller, giving you centralized control over your entire HVAC system. The device features RS-485 communication, which is a reliable and widely used protocol for industrial automation and building management systems. It also has a variety of LED indicators to provide status updates and troubleshooting information.

Here are some of the key capabilities of the LG PHNFP14A0.ENCXBTK:

  • Centralized control of multiple indoor units
  • RS-485 communication for reliable data transfer
INSTALLATION MANUAL
AIR
CONDITIONER
www.lg.com
TYPE : PI485 for Indoor Unit
Models: PHNFP14A0
PSNFP14A0
Please read this user/installation manual completely before installing the product.
Usage/Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
Please retain this installation manual for future reference after reading it
thoroughly.
P/NO : MFL67525602
ENGLISH
TÜRKÇE
2 485 Gateway(C, R)
PI 485 INSTALLATION MANUAL
TABLE OF CONTENTS
Safety Precautions....................................................3~4
Part Description .......................................................5~6
Installation Guide ....................................................7~12
Installation Steps .................................................................................7
DIP Switch Configuration.................................................................8~9
Advanced Lock Control Type ...........................................................10
Central Controller Connection Diagram.............................................11
Examples For Product Installation.....................................................12
Accessory Parts .........................................................13
Safety Precautions
Installation Manual 3
ENGLISH
Don't touch with the
hands while the power is
on
There is risk of fire or electric
shock.
Use standard parts(con-
nector).
Do not disassemble or repair
the product. There is risk of fire
or electric shock.
For electrical work, contact
the dealer, seller, a qualified
electrician, or an Authorized
Service Center.
Do not disassemble or repair
the product. There is risk of fire
or electric shock.
Installation
O
N
L
1
2
3
4
K
S
D
O
4
H
O
N
L
1
2
3
4
K
S
D
O
4
H
O
N
L
1
2
3
4
K
S
D
O
4
H
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions
must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
Meanings of symbols used in this manual are as shown below.
WARNING
CAUTION
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage.
Be sure not to do.
Be sure to follow the instruction.
WARNING
Safety Precautions
4 485 Gateway(C, R)
When the product is soaked (flooded or sub-
merged), contact an Authorized Service
Center.
• There is risk of fire or electric shock.
Be cautious that water could not enter the
product.
• There is risk of fire, electric shock, or product
damage.
O
N
L1
2
3
4
K
SD
O4
H
O
N
L
1 2
3
4
K
S
D
O4
H
Operation
Use the correctly rated
breaker or fuse.
• There is risk of fire or electric
shock.
Do not install, remove, or re-
install the unit by yourself
(customer).
• There is risk of fire, electric
shock, explosion, or injury.
For installation, always con-
tact the dealer or an
Authorized Service Center.
• There is risk of fire, electric
shock, explosion, or injury.
O
N
L1 2 3 4
KS
D
O
4
H
O
N
L1 2 3
4
KS
D
O4
H
O
N
L
1
2
3
4
KS
D
O4
H
Part Description
Installation Manual 5
ENGLISH
Part Description
PHNFP14A0
PI485 GATEWAY(C)
BUS_B: RS-485 (-) Terminal
BUS_A: RS-485 (+) Terminal
Reset Switch: PI485(C) Reset
LED01G,02G,03G: Communication Status LED
LED1: RS-485 Communication Status LED
CN_OUT: Indoor Unit Connector
DIP Switch: Product Selection (Refer Page 8~10)
1
2
4
5
6
7
3
1
2
3
4
5
6
7
6 485 Gateway(C, R)
Part Description
PSNFP14A0
PI485 GATEWAY(R)
BUS_B: RS-485 (-) Terminal
BUS_A: RS-485 (+) Terminal
Reset Switch: PI485(R) Reset
LED01G,02G,03G: Communication Status LED
LED1: RS-485 Communication Status LED
CN_OUT: Indoor Unit Connector
DIP Switch: Product Selection (Refer Page 8~10)
6
1
2
5
3
4
7
1
2
3
4
5
6
7
Installation Manual 7
Installation Guide
Installation Steps (PHNFP14A0/PSNFP14A0)
1. Select DIP Switch Configuration(Refer page 8 ~ 10)
2. Connect RS-485 BUS_A(+), BUS_(B)(-) with other network products (ex.
Simple Central Controller , ACP.....)
3. Connect CN_OUT with Indoor Unit by the cable (provided)
4. Check the Communication Status LED
- LED1G(Red)
• OK operation : LED blinks for 5 times and then gets OFF
This process is repeated after every 3 minutes
• NG operation : Check the Indoor Unit°Øs address & wiring connections
- LED2G(Yellow), LED3G(Orange)
• NG operation : Check the DIP Switch setting & wiring connections
5. Check RS-485
OK operation :
(1) LED blinks when PI485 receives data from central controller.
NG operation : Check the wiring connections
6. Finally if all of the above steps are OK then tie the cables by tie wraps & clamp
Installation Guide
6
7
5
1
2
ENGLISH
8 485 Gateway(C, R)
Installation Guide
ON KSDO 4H
L1 2 3 4
Select Air
Conditioner Type
Select Advenced
Control Type
Select Network
Type
ON KSDO4H
ON KSDO4H
L1 2 3 4
L1 2 3 4
DIP Switch Configuration
3 ON+ALL OFF: Using LGAP CAC Products + Central Controller
3, 4 ON+ALL OFF: LGAP CAC Products + Central Controller (ALL
type)-Using LGAP
For CAC products using LGAP
This means Central controller type
(Central controller using LGAP is under development. Next generation controller would
use LGAP.)
• PHNFP14A0
CAUTION:
Wrong products configuration can lead to malfunction.
The wrong setting of air-conditioner switch could cause malfunctioning.
Switch setting must be done carefully.
Installation Manual 9
ENGLISH
Installation Guide
ON KSDO 4H
L1 2 3 4
Select Air
Conditioner Type
Select Advenced
Control Type
Select Networ
k
Type
ON KSDO4H
ON KSDO4H
L1 2 3 4
L1 2 3 4
3 ON+ALL OFF: LGAP RAC/SRAC/PAC Products + Central Controller
(ALL type)-Without LGAP
3, 4 ON+ALL OFF: LGAP RAC/SRAC/PAC Products + Central
Controller (ALL type)-Using LGAP
For RAC/SRAC/PAC products using LGAP
• PSNFP14A0
CAUTION:
Wrong products configuration can lead to malfunctioning
Installation Guide
10 485 Gateway(C, R)
Advanced Lock Control Type
ON KSDO4H
L1 2 3 4
2,3,4 ON+All OFF : LGAP CAC/RAC/SRAC Products + Central
Controller (All types) - Using LGAP
- To use the advanced lock function (Run Mode lock, Fan Speed lock,
Temperature Lock, and Temperature Range lock; adjustable only within certain boundary)
by central controller, Set up the second dip switch according to the type of outdoor product.
- In case of advanced lock function, it can use only the central controller applied to LGAP.
CAUTION:
The wrong setting of air-conditioner switch could cause malfunctioning.
Switch setting must be done carefully.
After setting the dip switch, PI485 must be reset
NOTE : The advanced lock setting
Some products do not support advanced lock function.
In this case, The scond dip switch on PI485 must be on.
In case of product applied to advanced function, it can process the advanced lock function without second dip
switch ON.
If all units support advanced lock function,
It is recommended that the second dip switch be off, so that advanced lock function is processed faster.
Installation Manual 11
Installation Guide
Central Controller Connection Diagram
CAUTION:
After product installation, tie the cables with the clamps & tie-wraps provided.
• PHNFP14A0
• PSNFP14A0
ENGLISH
12 485 Gateway(C, R)
Installation Guide
Examples For Product Installation
CAUTION:
Installation location can be different depending upon product's structure.
(1) The Installation for 4Way Cassette
Product
Check Screw boss for PCB in 4way
Cassette Product then fix it.
(2) The Installation for DUCT Product
Using PCB Holder provided
(3) The Installation for Cassette Product
Cover
Check Screw boss for PCB in 4way
Cassette Product Then fix It
Acceassory Parts
Installation Manual 13
ENGLISH
Acceassory Parts
PCB :6871A20484H Holder for DUCT :3110A 20056A WIRE ASSY 1(for RAC/SRAC/CAC)
Screw 4 EA Installation Manual WIRE ASSY(for Others)
PCB :6871A20484J
WIRE ASSY 1(for RAC/SRAC/CAC)
WIRE ASSY(for Others) Top Case(3110A20124A)
Screw 4 EA Installation Manual
Bottom Case(3110A20125A)
PI485
* Others : Tie Wrap (3 EA) - Cable Tie
Clamp (1 EA)
• PSNFP14A0
• PHNFP14A0
Memo
14 485 Gateway(C, R)
İTHALATÇI FİRMA
Bosch Termoteknik Isıtma ve Klima Sanayi Ticaret A.Ş
Merkez Adresi : Organize Sanayi Bölgesi İkinci Kısım Gaziler Caddesi No:2 45030 Manisa
İrtibat Adresi :Aydınevler Mahallesi İnönü Caddesi No:20 Küçükyalı Ofis Park A Blok 34854
Maltepe / İSTANBUL
Telefonu : (0216) 432 08 00
Telefaksı : (0216) 432 09 86
ÜRETİCİ FİRMA
LG Electronics Inc
Changwon 2nd factory 84, Wanam-ro, Seongsan-gu, Changwon-si Gyeongsangnam-do, KOREA
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15

LG PHNFP14A0.ENCXBTK Installation guide

Type
Installation guide

LG PHNFP14A0.ENCXBTK:

This device is a 485 Gateway(C, R), part of an air conditioning system. It allows you to connect multiple indoor units to a central controller, giving you centralized control over your entire HVAC system. The device features RS-485 communication, which is a reliable and widely used protocol for industrial automation and building management systems. It also has a variety of LED indicators to provide status updates and troubleshooting information.

Here are some of the key capabilities of the LG PHNFP14A0.ENCXBTK:

  • Centralized control of multiple indoor units
  • RS-485 communication for reliable data transfer