Munters 190TGB-1035-H1604 Owner's manual

Category
Dehumidifiers
Type
Owner's manual
Originalinstructions
Usermanual
ML420,ML690,MLT800
ML1100,ML1350,MLT1400
Desiccantdehumidier
190TGB-1035-H1604©MuntersEuropeAB2016
Importantuserinformation
Intendeduse
Muntersdehumidiersareintendedtobeusedforthe
dehumidicationofair.Anyotheruseoftheunit,or
usewhichiscontrarytotheinstructionsgiveninthis
manual,cancausepersonalinjuryanddamagetotheunit
andotherproperty.
Nomodicationoftheunitisallowedwithoutprior
approvalbyMunters.Attachmentorinstallation
ofadditionaldevicesisonlyallowedafterwritten
agreementbyMunters.
Warranty
Thewarrantyperiodisvalidfromthedatetheunit
leftourfactory,unlessotherwisestatedinwriting.
Thewarrantyislimitedtoafreeexchangeofpartsor
componentswhichhavefailedasaresultofdefectsin
materialsorworkmanship.
Allwarrantyclaimsmustincludeproofthatthe
faulthasoccurredwithinthewarrantyperiodand
thattheunithasbeenusedinaccordancewiththe
specications.Allclaimsmustspecifytheunittypeand
fabricationnumber.Thisinformationisstampedonthe
identicationplate,seesectionMarking.
Itisaconditionofthewarrantythattheunitforthefull
warrantyperiodisservicedandmaintainedbyaqualied
MuntersengineerorMuntersapprovedengineer.
Accesstospecicandcalibratedtestequipmentis
necessary.Theserviceandmaintenancemustbe
documentedforthewarrantytobevalid.
AlwayscontactMuntersforserviceorrepair.Operating
faultscanoccuriftheunitismaintainedinsufcientlyor
incorrectly.
Safety
Informationaboutdangersareinthismanualindicated
bythecommonhazardsymbol:
W W
W
ARNING! ARNING!
ARNING!
Indicatesapossibledangerthatcanleadtopersonalinjury.
CA CA
CA
UTION! UTION!
UTION!
Indicatesapossibledangerthatcanleadtodamagetothe
unitorotherproperty,orcauseenvironmentaldamage.
NOTE!Highlightssupplementaryinformationforoptimal
useoftheunit.
ConformitywithDirectives
Thedehumidierisinconformitywiththeessential
safetyrequirementsoftheMachineryDirective
2006/42/EC,andinconformitywiththeprovisionsof
theEcodesignDirective(ErP)2009/125/EC,andof
theEMCDirective2004/108/EC.Thedehumidieris
manufacturedbyanorganizationcertiedaccordingto
ISO9001andISO14001.
Copyright
Thecontentsofthismanualcanbechangedwithout
priornotice.
NOTE!Thismanualcontainsinformationwhichis
protectedbycopyrightlaws.Itisnotallowedtoreproduceor
transmitanypartofthismanualwithoutwrittenconsentfrom
Munters.
Pleasesendanycommentsregardingthismanualto:
MuntersEuropeAB
TechnicalDocumentation
P.O.Box1150
SE-16426KISTASweden
e-mail:t-doc@munters.se
iiImportantuserinformation190TGB-1035-H1604
Tableofcontents
Importantuserinformation...............ii
Intendeduse...........................
ii
Warranty...............................
ii
Safety..................................
ii
ConformitywithDirectives............
ii
Copyright..............................
ii
Tableofcontents...........................iii
1Introduction.................................1
1.1Aboutthismanual.....................
1
1.2Unintendeduse........................
1
1.3Safetyandcautions...................
1
1.4Markings...............................
3
1.5Supervisionofoperation..............
3
1.6Faultindications.......................
3
2Dehumidierdesign.......................4
2.1Productdescription...................
4
2.2Functiondescription..................
4
2.3Maincomponents.....................
5
3Transport,inspectionandstorage.......6
3.1Transport..............................
6
3.2Inspectionofdelivery..................
6
3.3Storingtheequipment................
6
4Installation...................................7
4.1Safety..................................
7
4.2Siterequirements.....................
7
4.3Foundation............................
8
4.4Mirrorhandedductconnections......
8
4.5Ductinstallation.......................
9
4.5.1Generalrecommendations...
9
4.5.2Ductforoutdoorairinlet.......
12
4.5.3Ductforwetairoutlet...........
12
4.6Precautionarymeasuresforunitswith
LIdesiccantrotor......................
13
4.7Electricalconnections................
13
4.8Externalhumiditysensor.............
13
4.9Gasreactivation(ML1100units
only)....................................
14
5Commissioning.............................15
5.1Settingsbeforestart-up...............
15
5.1.1Continuousprocessairfan
operation.......................
15
5.1.2Single-stagehumiditysensor.
15
5.1.3Two-stagehumiditysensor...
15
5.1.4Remotefaultindication........
15
5.2Pre-startchecks.......................
16
5.3Airowcheckandadjustment........
17
6Operation....................................18
6.1General................................
18
6.2Quickstop..............................
18
6.3Beforestarting.........................
18
6.4Operatorpanel........................
19
6.5RH98operatorpanel..................
21
6.6Operatingtheunit.....................
21
6.6.1Manualmode..................
21
6.6.2Automaticmodehumidity
sensorconnected..............
22
6.6.3Automaticmode-RH98or
VariDry(option)................
22
7Serviceandmaintenance.................24
7.1Safety..................................
24
7.2General................................
24
7.3Serviceoptions........................
24
7.4Extendedwarranty....................
25
7.5Cleaning...............................
25
7.6Serviceandmaintenanceschedule..
25
7.7Filterchange...........................
27
8Faulttracing.................................28
8.1General................................
28
8.2Safety..................................
28
8.3Faulttracinglist........................
29
9Technicalspecication....................31
9.1Dimensionsandservicespace.......
31
9.2Capacitydiagrams....................
32
9.3Technicaldata.........................
34
9.4Sounddata.............................
36
9.4.1SounddataML420............
36
9.4.2SounddataML690............
37
9.4.3SounddataMLT800...........
37
9.4.4SounddataML1100...........
38
9.4.5SounddataML1350...........
38
9.4.6SounddataMLT1400..........
39
10Scrapping....................................40
190TGB-1035-H1604Tableofcontentsiii
Appendix1Options.............................41
1.1General................................
41
1.2Runningtimemeter...................
41
1.3Rotorstopalarm.......................
41
1.4Blockedlteralarm....................
41
1.5Filterbox-M5andF7..................
41
1.6Humiditycontrolsystem..............
42
1.6.1Introduction....................
42
1.6.2Transmitter.....................
42
1.6.3Controlunit.....................
42
1.6.4Setpointsandcontrol
parameters.....................
43
1.6.5Display/changesetpointfor
relativehumidity...............
44
1.6.6Display/changeother
parameters.....................
44
1.6.7Processalarms................
47
2ContactMunters............................49
ivTableofcontents190TGB-1035-H1604
DehumidierML420-MLT1400
1Introduction
1.1Aboutthismanual
Thismanualiswrittenfortheuserofthedehumidier.Itcontainsnecessaryinformationforhowtoinstall
andusethedehumidierinasafeandefcientway.Readthroughthemanualbeforethedehumidieris
installedandused.
ContactyournearestMuntersofceifyouhaveanyquestionsregardingtheinstallationortheuseofyour
dehumidier.
Thismanualmustbestoredinapermanentlocationclosetothedehumidier.
1.2Unintendeduse
Thedehumidierisnotintendedforoutdoorinstallation.
Thedehumidierisnotintendedforuseinclassiedareaswhereexplosionsafetycompliantequipment
isrequired.
Thedehumidiermustnotbeinstallednearanyheatgeneratingdevicesthatcancausedamagetothe
equipment.
1.3Safetyandcautions
Everymeasurehasbeentakeninthedesignandmanufactureofthedehumidiertoensurethatitmeetsthe
safetyrequirementsofthedirectivesandstandardslistedintheECDeclarationofConformity.
Theinformationinthismanualshallinnowaytakeprecedenceoverindividualresponsibilitiesorlocal
regulations.
Duringoperationandotherworkwithamachineitisalwaystheresponsibilityoftheindividualtoconsider
thefollowing:
Thesafetyofallpersonsconcerned.
Thesafetyoftheunitandotherproperty.
Theprotectionoftheenvironment.
ThetypesofdangersthatareindicatedinthismanualaredescribedinthesectionImportantuserinformation.
190TGB-1035-H1604Introduction1
DehumidierML420-MLT1400
W W
W
ARNING! ARNING!
ARNING!
-Theunitmustnotbesplashedwithorimmersedinwater.
-Theunitmustneverbeconnectedtoavoltageorfrequencyotherthanthatforwhichitwasdesigned.Refertothe
identicationplate.Linevoltagethatistoohighcancauseanelectricalshockhazardanddamagetotheunit.
-Donotinsertngersoranyobjectsintotheairvents.
-Allelectricalinstallationsmustbecarriedoutbyaqualiedelectricianandinaccordancewithlocalregulations.
-Thedehumidiercanrestartautomaticallyafterapowercut.Alwayssetandlockthemainpowerswitchinthe
OFFpositionbeforecarryingoutanyservicework.
-Useonlyapprovedliftingequipmenttopreventpersonalinjuryanddamagetotheequipment.
-AlwayscontactMuntersforserviceorrepair.
2Introduction190TGB-1035-H1604
DehumidierML420-MLT1400
1.4Markings
Reg.luft
Reac.air
Reg.Luft
Air de regeneration
' ' '
Processluft
Process air
Prozessluft
Air a traiter
`
Våtluft
Wet air
Nassluft
Air humide
Torrluft
Dry air
Trockenluft
Air sec
3
1
4
5
2
Figure1.1Identicationplateandmarkings
Figure1.2Identicationplate,example
3
Figure1.3Labelsforairinletsandoutlets
1.Unitidenticationplate
4.Processairinlet
2.Dryairoutlet5.Reactivationairinlet
3.Wetairoutlet
Explanationof"Fabr.no"ontheidenticationplate:
09=yearofmanufacture,19=weekofmanufacture,190XXX=articlenumber,XXXXX=serialnumber
1.5Supervisionofoperation
Thedehumidieriscontrolledandmonitoredusingtheoperatorpanellocatedonthefrontoftheunit.
1.6Faultindications
Faultsareclearlyindicatedontheoperatorpanel,seesection6.4,Operatorpanel.
Alarmsrelatingtorelativeairhumidityaregiveninthedisplayofthehumiditycontrolsystem(ifinstalled),
seeappendix1.6,Humiditycontrolsystem.
190TGB-1035-H1604Introduction3
DehumidierML420-MLT1400
2Dehumidierdesign
2.1Productdescription
ThedesiccantdehumidiersintheMLserieshavebeendevelopedtoeffectivelydehumidifytheairin
environmentsrequiringlowairhumidity.
Thedehumidierisequippedwithanencapsulatedrotorunit.Therotorcasingisconstructedofdurable
thermosetplasticandcontainsisolatedsectionsthatprovideaprecisebalanceforthedehumidication,
reactivationandheatrecoveryairows.
ThedehumidierismanufacturedinaccordancewithuniformEuropeanstandardsandestablished
requirementsforCE-marking.
2.2Functiondescription
1.Processair
2.Dryair
3.Reactivationair
2
4
3
1
Figure2.1Internalairows
4.Wetair
Thedesiccantrotoristheadsorptiondehumidifyingcomponentintheunit.Therotorstructureis
comprisedofalargenumberofsmallairchannels.
Thedesiccantrotorismadeofacompositematerialthatishighlyeffectiveinattractingandretainingwater
vapour.Therotorisdividedintwozones.Theairowtobedehumidied,processair,passesthroughthe
largestzoneoftherotorandthenleavestherotorasdryair.Sincetherotorrotatesslowly,theincomingair
alwaysmeetsadryzoneontherotor,thuscreatingacontinuousdehumidicationprocess.
Theairowthatisusedtodrytherotor,reactivationair,isheated.Thereactivationairpassesthrough
therotorintheoppositedirectiontotheprocessairandleavestherotoraswetair(warm,moistair).This
principleenablesthedehumidiertoworkeffectively,evenatfreezingtemperatures.
4Dehumidierdesign190TGB-1035-H1604
DehumidierML420-MLT1400
2.3Maincomponents
11
1
4
5
6
8
9
2
16
3
12
14
13
15
10
7
Figure2.2Maincomponents
1.Lowerrotorcover9.Drivemotor
2.Roller,beltguide10.Pulley,beltdrive
3.Drivebelt11.
Reactivationairlter
4.Rotor12.Reactivationairimpeller
5.
Sealingring,rotor
13.
Reactivationfanmotor
6.Upperrotorcover14.
Processfanmotor
7.
Electricalcontrolpanel15.Processairimpeller
8.Reactivationheater16.
Processairlter
NOTE!TheML420unithasonlyonefanmotorthatisplacedbetweentheprocessandreactivationimpeller.
190TGB-1035-H1604Dehumidierdesign5
DehumidierML420-MLT1400
3Transport,inspectionandstorage
3.1Transport
Thedehumidierisdeliveredonapalletandmustbehandledcarefully.Allpaneldoorsontheunitmustbe
closedduringtransport.Providedthatthedehumidierisstillsecuredtoitsdeliverypallet,itcanbemoved
usingafork-lifttruck.
W W
W
ARNING! ARNING!
ARNING!
Movethedehumidiercarefullyasthereisariskofthedehumidiertippingover.
Figure3.1Correctlengthonforkliftarms
Weightofthedehumidiercanbefoundinsection9.1,Dimensionsandservicespace.
3.2Inspectionofdelivery
Doaninspectionofthedeliveryandcomparewiththedeliverynote,orderconrmationorother
deliverydocumentation.Makesurethateverythingisincludedandnothingisdamaged.
ContactMuntersimmediatelyifthedeliveryisnotcompleteordamagedinordertoavoidinstallation
delays.
Removeallpackagingmaterialfromtheunit,andmakesurethatnodamagehasbeenmadeduring
transportation.
AnyvisibledamagemustbereportedinwritingtoMunterswithin3daysandpriortoinstallationof
theunit.
Discardthepackagingmaterialaccordingtolocalregulations.
3.3Storingtheequipment
Followtheseinstructionsifthedehumidieristobestoredpriortoinstallation:
Placethedehumidierinanuprightpositiononahorizontalsurface.
Re-usethepackagingmaterialtoprovideprotectionfortheunit.
Protectthedehumidierfromphysicaldamage.
Storethedehumidierundercoverandprotectitfromdust,frost,rainandaggressivecontaminants.
6Transport,inspectionandstorage190TGB-1035-H1604
DehumidierML420-MLT1400
4Installation
4.1Safety
W W
W
ARNING! ARNING!
ARNING!
-Theunitmustnotbesplashedwithorimmersedinwater.
-Theunitmustneverbeconnectedtoavoltageorfrequencyotherthanthatforwhichitwasdesigned.Refertothe
identicationplate.Linevoltagethatistoohighcancauseanelectricalshockhazardanddamagetotheunit.
-Donotinsertngersoranyobjectsintotheairvents.
-Allelectricalinstallationsmustbecarriedoutbyaqualiedelectricianandinaccordancewithlocalregulations.
-Thedehumidiercanrestartautomaticallyafterapowercut.Alwayssetandlockthemainpowerswitchinthe
OFFpositionbeforecarryingoutanyservicework.
-Useonlyapprovedliftingequipmenttopreventpersonalinjuryanddamagetotheequipment.
-AlwayscontactMuntersforserviceorrepair.
CA CA
CA
UTION! UTION!
UTION!
Thewetairductmustalwaysbeinsulatedwhenthereisariskoffreezing.Condensationbuildsupeasilyonthe
insideoftheductbecauseofthehighmoisturecontentofthewetairleavingthedehumidier.
CA CA
CA
UTION! UTION!
UTION!
Thedehumidierhasbeendesignedtooperateatspecicprocessairowscorrespondingtothefansizes
installed.
4.2Siterequirements
Thedehumidierisonlyintendedforindoorinstallation.Avoidinstallingthedehumidierinadamp
environmentwherethereisariskofwaterenteringtheunitorinaverydustyenvironment.Ifindoubt,
contactMunters.Itisimportantthattheintendedinstallationsitemeetsthelocationandspacerequirements
fortheequipmentinordertoachievethebestpossibleperformance.
Fortheunitdimensionsandservicespacerequirements,seesection9.1,Dimensionsandservicespace.
NOTE!Ifthereisaneedforreductionofvibrationsfromthedehumidier,contactMuntersforinstructions.
190TGB-1035-H1604Installation7
DehumidierML420-MLT1400
4.3Foundation
Thedehumidiermustbeinstalledonaleveloor,oronaplatformcapableofsupportingthemachine
weight.Ifthemaximumoorloadingweightisnotexceeded,specialfoundationsarenotrequired.
Whenthedehumidierhasbeeninstalled,checkthatitislevel.
Iflocalregulationsrequirethattheunitispermanentlyxedinposition,thexingholescanbeusedfor
boltingtheunittotheoor.
Figure4.1Drillingpattern
4.4Mirrorhandedductconnections
Thefrontandrearpanelsareinterchangeable,sothattheconnectionsforprocessairanddryairmaybe
situatedeitherontheleftorrightsideoftheunit.
Thedehumidiersaredeliveredwiththeprocessanddryairconnectionsontheleftsideoftheunit.If
itisrequiredtochangetheorientation,sothattheconnectionsareontherightsideoftheunit,proceed
asfollows.
W W
W
ARNING! ARNING!
ARNING!
Makesurethatthedehumidierisdisconnectedfromthemainspowerbeforechangingthepositionsofthe
processairanddryairconnections.
8Installation190TGB-1035-H1604
DehumidierML420-MLT1400
Figure4.2ChangingpanelpositionsFigure4.3Rotorstop(E)andltermonitors(F)
1.Removethetwobolts(B)securingthefrontpanelandcarefullyremovethepanel.
2.Removethetwoboltssecuringtherearpanelandcarefullyremovethepanel.
3.Removethetwobolts(A)andwasherssecuringthecontrolandtoppanels,thencarefullyremovethe
toppanel.
4.Removethecableductcovers(C),re-routethecablesandtthecontrolpanel(D)ontotheoppositeside
oftheunit.Retthecableductcovers.
5.Loosentherotorstop(E)andthetwoltermonitors(F).Removethecableties.
6.Fittherotorstopandltermonitorsontheoppositesideoftheunit.Tiethecables.
7.Fitthefront,rearandtoppanelsintheirnewpositions.
4.5Ductinstallation
4.5.1Generalrecommendations
Theconnectionsforprocessandreactivationairaredesignedinaccordancewiththerecommendationsin
ISO13351.TherectangularductconnectionscontaintappedinsertsforM8screws.
Figure4.4Ductconnections
190TGB-1035-H1604Installation9
DehumidierML420-MLT1400
Partnumber170-013448–005170-013448–004170-013448–003170-013448–002170-013448–001
A
Ø100Ø125Ø160Ø200Ø250
B
Seesection9.1,Dimensionsandservicespace.
L(mm)
210210200140150
ML420XX
ML690XX
MLT800XX
ML1100XX
ML1350XX
MLT1400XX
CA CA
CA
UTION! UTION!
UTION!
Thedehumidierhasbeendesignedtooperateatspecicprocessairowscorrespondingtothefansizes
installed.
Theprocessairanddryairductsshouldbethesamediameter.Thesameappliestothereactivationair
andwetairducts.
Thelengthofductworkmustbekeptasshortaspossibletominimisestaticairpressurelosses.
Tomaintainperformance,allrigidprocessorreactivationairductworkjointsmustbeairandvapour
tight.
Theprocessairductworkmustbeinsulatedtopreventcondensationdevelopingontheoutsideofthe
duct,wheneverthetemperatureoftheairwithintheductfallsbelowthedewpointtemperatureofthe
ambientairthroughwhichtheductworkisrouted.
Theductsmustalwaysbeinsulatedwhenthereisariskoffreezing.
Thewetairleavingthedehumidierwill,becauseofhighmoisturecontent,condenseontheinsideduct
walls.Byinsulatingtheducts,theamountofcondensateisreduced.
Horizontalwetairductsmustbeinstalledwithaslightdecline(awayfromthedehumidier)todrain
awaypossiblecondensation.Suitablecondensationdrainsmustbeinstalledatlowpointsinthewet
airoutletduct,seeFigure4.7.
Ensurethataccessforoperationandservicingisnotrestrictedwhendesigningandinstallingducting.
Formoreinformation,refertosection9.1,Dimensionsandservicespace.
Toreducenoiseand/orvibrationbeingtransmittedalongrigidducts,goodquality,airtightexible
connectionscanbetted.
Ductsmounteddirectlyontotheunitmustbeindependentlysupportedtominimisetheloadontheunit.
Dampersforadjustingtheairowsmustbeinstalledinthesupplyairoutletandreactivationairinlet
ducts.Correctairowsareessentialfortheoperatingefciencyoftheunit.Forairowadjustment
instructions,seesection5.3,Airowcheckandadjustment.
Thetotalpressuredropintheprocessandreactivationductworkmustnotexceedtheavailablepressure
ofthefansttedtothedehumidier.Fordetailsofminimumavailablestaticpressure,seesection
9.3,Technicaldata.
10Installation190TGB-1035-H1604
DehumidierML420-MLT1400
ML
Munter s
420
1
2
3
5
5
4
C
B
D
A
Figure4.5Ductsrequiredforinstallation
A.Processairinlet1.Dryairdamper
B.Dryairoutlet
2.Externallterbox(option)
C.Reactivationairinlet
3.Ducttransition
D.Wetairoutlet4.Reactivationairdamper
5.Outlet/inletduct(wirenetting)
190TGB-1035-H1604Installation11
DehumidierML420-MLT1400
4.5.2Ductforoutdoorairinlet
Whenbringingambientairfromoutdoorsintothedehumidier,theinletductopeningmustbelocated
sufcientlyhighabovegroundleveltopreventdustanddebrisfromentering.
Theductingmustbedesignedtopreventrainandsnowfrombeingdrawnintothedehumidier.Theair
inletmustbelocatedawayfrompossiblecontaminantssuchasengineexhaustgases,steamandharmful
vapours.
Topreventthewet(outlet)airfromhumidifyingthereactivation(inlet)air,theairinletforreactivationmust
belocatedatleast2mfromthewetairoutlet.
Attachawirenetwithameshwidthofapproximately10mmintheouterendoftheducttopreventanimals
fromenteringthedehumidierducting.
Figure4.6Outdoorairinletdesign
A.Rectangularducting
B.Roundducting
C.Wirenetting
4.5.3Ductforwetairoutlet
Thematerialforthewetairductmustwithstandcorrosionandtemperaturesofupto100°C.Thewetair
ductingmustalwaysbeinsulatedifthereisariskofcondensation.Thewetairleavingthedehumidierwill
easilycausecondensationontheinsideoftheductwallsduetothehighmoisturecontent.
Horizontalductsmustbeinstalledslopingdownwards(awayfromthedehumidier)todrainawaypossible
condensation.Theductslopemustbeatleast2cm/m.Inaddition,drainageholes(5mm)shouldbemadeat
lowpointsintheducttopreventwateraccumulation.
Attachawirenetwithameshwidthofapproximately10mmintheouterendoftheducttopreventanimals
fromenteringthedehumidierducting.
Figure4.7Wetairoutletdesign
A.Horizontalwetairoutlet
B.Verticalwetairoutlet
C.Wirenetting
D.Downwardslope
E.Condensatedrainage
12Installation190TGB-1035-H1604
DehumidierML420-MLT1400
4.6PrecautionarymeasuresforunitswithLIdesiccantrotor
ThestandarddeliveryisMuntershighperformancedesiccantrotorHPS(HighPerformanceSilicagel).
IfthedehumidierisdeliveredwithanLIrotor(lithiumchloride)itisimportantthattherotordoesnot
becomeloadedwithmoisturewhenthedehumidierisoff.
NOTE!Makesurethatnoairpassingthroughtherotorhasarelativehumiditygreaterthan80%.
Itisrecommendedtoinstallclosingdampersintheprocessandreactivationairinletstoavoidthatairwith
highrelativehumidityisdrawnthroughtherotorandintotheroom.
Thisisparticularlyimportantwhentheprocessairisdrawnfromoutdoors,orwhenthesystemhasbeen
ttedwithapre-cooler.
4.7Electricalconnections
W W
W
ARNING! ARNING!
ARNING!
Allelectricalequipmentconnectionsmustbecarriedoutinaccordancewithlocalregulationsandbyqualied
personnel.Riskofelectricalshock.
W W
W
ARNING! ARNING!
ARNING!
Theunitmustneverbeconnectedtoavoltageorfrequencyotherthanthatforwhichitwasdesigned.Refertothe
unitidenticationplate.
Eachunitissuppliedcompletewithalltheinternalwiringinstalledandconguredinaccordancewiththe
speciedvoltageandfrequencyontheidenticationplate.
NOTE!Thesupplyvoltagemustnotdifferfromthespeciedoperatingvoltagebymorethan+/-10%.
Forconnectiondetails,seetheidenticationplateandthewiringdiagramorsection9.3,Technicaldata.
4.8Externalhumiditysensor
ML-seriesdehumidiersarewiredsothatwhentheunitissettoAUTOmatic,itcanbecontrolledfrom
anexternallymountedhumiditysensor.
Allmodelshaveatwo-stageheater,andcanbecontrolledbyatwo-stagehumiditysensor.Thismethodis
moreefcientandallowsformoreaccuratedehumidicationcontrol.
Theelectricalconnectionsaremadeatterminalsintheelectricalcontrolpanel.Forwiringandconnection
details,seethewiringdiagram.
NOTE!Wherenohumiditysensorisconnectedtotheunit,thedehumidierwillbeoperatingatmaximumoutput
foraslongastheunitisswitchedon.
Aroomhumiditysensoristobemounted1-1.5mabovetheoor.Itmustbepositionedsothatitisnot
directlyexposedtodryairfromtheunitortohumidairowinginthroughopeningdoors.Positionitaway
fromheatsourcesanddirectsunlight.
Thehumiditysensorconnectingcableshouldhaveaconductorareaofnotlessthan
0,75mm
2
andmusthaveaninsulationresistanceratinginexcessof500VAC.
ThehumiditysensormustbedesignedsothatthecontactscloseonarisingRHtocompletethecontrol
circuitandstartthedehumidier.
190TGB-1035-H1604Installation13
DehumidierML420-MLT1400
Voltagedropscanoccurwhenusingexcessivelylongcables.
Ifthevoltageacrosstheterminalsusedforconnectingthehumiditysensorislessthan20VAC,aseparate
relaycontrolledbythehumiditysensormustbeused.
4.9Gasreactivation(ML1100unitsonly)
Forfurtherinformationoninstallation,start-upandmaintenanceofgasburners,seeappendixaboutgas
reactivationprovidedwiththeunit.
14Installation190TGB-1035-H1604
DehumidierML420-MLT1400
5Commissioning
TheML420-MLT1400dehumidiershaveseveralstandardfunctionsthatneedtobesetbeforeinitial
start-up.Someofthefunctionsrequireconnectiontoexternalequipment.
Somefeaturesrequireconnectionofexternalequipment.Forwiringdetails,seethewiringdiagram.
5.1Settingsbeforestart-up
5.1.1Continuousprocessairfanoperation
Standardsettingsautomaticallyactivatetheprocessairfanonlywhendehumidicationisrequired.
However,continuousprocessairowcanbedesirableevenwhendehumidicationisnotrequired.
Continuousprocessairowcanbeset,seethewiringdiagram.
5.1.2Single-stagehumiditysensor
NOTE!Whennohumiditysensorisconnected,thedehumidierwillrunatmaximumeffectcontinuously.
Ifasingle-stagehumiditysensoristted,thiswillswitchthedehumidieronandoff.Asingle-stage
humiditysensorisconnectedaccordingtothewiringdiagram.
Tomaintainaircirculation,preselectcontinuousoperationoftheprocessairfaneventhough
dehumidicationisnotrequired.Forfurtherinformation,seesection5.1.1,Continuousprocessairfanoperation.
5.1.3Two-stagehumiditysensor
NOTE!Whennohumiditysensorisconnected,thedehumidierwillrunatmaximumeffectcontinuously.
Ifatwo-stagehumiditysensorisconnected,thiswillcontrolthereactivationheaterintwostages.The
reactivationpoweriscontrolledonthebasisofthehumiditysensorreadingandthesetpoint.Atwo-stage
humiditysensorisconnectedaccordingtothewiringdiagram.
Tomaintainaircirculation,preselectcontinuousoperationoftheprocessairfaneventhough
dehumidicationisnotrequired.Forfurtherinformation,seesection5.1.1,Continuousprocessairfanoperation.
5.1.4Remotefaultindication
ThePCBdisplaycanbeusedforageneralindicationofthefollowingfaultsonthedehumidier:
Processairfan
Reactivationairfan
Drivemotor
Heater
Auxiliaryequipmentinput
Rotorhasstopped(ifthisoptionisinstalled)
Blockedprocessairlter(ifthisoptionisinstalled)
Blockedreactivationairlter(ifthisoptionisinstalled)
190TGB-1035-H1604Commissioning15
DehumidierML420-MLT1400
5.2Pre-startchecks
W W
W
ARNING! ARNING!
ARNING!
Installation,adjustments,maintenanceandrepairsmustonlybecarriedoutbyqualiedpersonnelwhoare
awareoftherisksinvolvedwhenworkingwithequipmentoperatingwithhighelectricalvoltageandhighmachine
temperatures.
Beforestartingthedehumidierforthersttime,ensurethatthemainspowersupplyisisolatedfromthe
dehumidierandcarry-outthefollowingchecks:
1.CheckthattheModeswitchonthedehumidierisinthe“OFF”position,seesection6.4,Operatorpanel.
2.Checktheairintakeltersfordamageandproperxationandalsocheckthatallareasinsidetheunitare
clean.
3.Visuallyinspectallductingandductconnectionstomakesurethatallconnectionshavebeencorrectly
installedandthattherearenosignsofdamagetothesystem.Alsocheckthatallductsarefreefrom
obstaclesblockingtheairpassage.
4.Removethetoppanelandcheckthatnoneofthemaincontactbreakersintheelectricaloperatorpanel
havebeentripped.Fordetailsrefertothewiringdiagramsprovidedwiththeunit.
5.Checkthattheincomingpowersupplyvoltageiscorrectandthatthecablesarecorrectlyconnected.
6.Checktherotationdirectionofthefanimpellerafterconnectiontothepowersupply.Openthefront
panelofthedehumidierandtakeouttheprocesslter.Startthedehumidierandcheckthatthefan
impellerisrotating.Switchoffthedehumidierandwatchthefanimpellerjustbeforeitstopsrotating.
Checkthatitisrotatingclockwise.
7.Ifanexternalhumiditysensorisused,checkthatthesensoriscorrectlypositionedintheroomandis
correctlyconnectedtotheunit,seesection4.8,Externalhumiditysensor.
8.Settheprocessandreactivationairowdamperstothefullyopenposition.
16Commissioning190TGB-1035-H1604
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56