Heat & Glo 6000/8000C Modern IFT Series Install Manual

  • Hello! I've reviewed the Installation Manual for Heat & Glo 6000CMOD-IFT and 8000CMOD-IFT fireplaces. These are direct vent gas fireplaces designed for supplemental heating and, importantly, have safety features like a barrier for the hot glass. I'm here to answer your questions about the installation process, clearances, and other details mentioned in the manual.
  • What should I do if I smell gas?
    Who should perform the installation?
    What should I do with this manual?
1
Heat & Glo • 6000CMOD-IFT, 8000CMOD-IFT Installation Manual • 2509-980 Rev. Q • 7/22
Installation Manual
Installation and Appliance Setup
INSTALLER: Leave this manual with party responsible for use and operation.
OWNER: Retain this manual for future reference.
NOTICE: DO NOT discard this manual!
In the Commonwealth of Massachusetts installation must be
performed by a licensed plumber or gas tter.
See Table of Contents for location of additional Commonwealth
of Massachusetts requirements.
DO NOT store or use gasoline or other am-
mable vapors and liquids in the vicinity of this
or any other appliance.
What to do if you smell gas
- DO NOT try to light any appliance.
- DO NOT touch any electrical switch. DO
NOT use any phone in your building.
- Leave the building immediately.
- Immediately call your gas supplier from
a neighbor’s phone. Follow the gas sup-
plier’s instructions.
- If you cannot reach your gas supplier, call
the re department.
Installation and service must be performed
by a qualied installer, service agency, or the
gas supplier.
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly
could result in serious injury, death, or
property damage.
Models:
6000CMOD-IFT
8000CMOD-IFT
This appliance may be installed as an OEM
installation in manufactured home (USA
only) or mobile home and must be installed
in accordance with the manufacturer’s
instructions and the Manufactured Home
Construction and Safety Standard, Title 24
CFR, Part 3280 in the United States, or the
Standard for Installation in Mobile Homes,
CAN/CSA Z240 MH Series, in Canada.
This appliance is only for use with the type(s)
of gas indicated on the rating plate. This
appliance is not convertible for use with other
gases, unless a certied kit is used.
DANGER
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of
burns from the hot viewing glass is provided
with this appliance and must be installed for
the protection of children and other at-risk
individuals.
Heat & Glo • 6000CMOD-IFT, 8000CMOD-IFT Installation Manual • 2509-980 Rev. Q • 7/222
Table of Contents
Installation Standard Work Checklist ....................3
1 Product Specic and Important Safety Information
A. Appliance Certication ............................ 4
B. Glass Specications ..............................4
C. BTU Specications ...............................4
D. High Altitude Installations ..........................4
E. Non-Combustible Materials Specication. . . . . . . . . . . . . . 4
F. Combustible Materials Specication ................. 4
G. Electrical Codes .................................4
H. California ......................................4
I. Requirements for the Commonwealth of Massachusetts . . 5
2 Getting Started
A. Design and Installation Considerations ...............6
B. Good Faith Wall Surface ..........................6
C. Tools and Supplies Needed ........................6
D. Inspect Appliance and Components ..................7
3 Framing and Clearances
A. Appliance/Decorative Front Dimension Diagrams ....... 8
B. Clearances to Combustibles ......................14
C. Constructing the Appliance Chase ..................16
D. Floor Protection ................................16
4 Termination Location and Vent Information
A. Vent Termination Minimum Clearances .............. 17
B. Vent Terminal Clearances ........................18
C. Approved Pipe .................................19
D. Use of Elbows ................................. 20
E. Measuring Standards ............................21
F. Vent Diagrams .................................22
5 Vent Clearances and Framing
A. Pipe Clearances to Combustibles .................. 29
B. Wall Penetration Framing .........................29
C. Ceiling Firestop/Floor Penetration Framing ...........30
D. Install Attic Insulation Shield .......................30
6 Appliance Preparation
A. Vent Collar Preparation ..........................31
B. Installing Optional Heat Management Systems ........32
C. Securing and Leveling the Appliance ................33
D. Installing the Non-combustible Board. . . . . . . . . . . . . . . . 33
7 Venting and Chimneys
A. Assemble Vent Sections (DVP Pipe) ................ 34
B . Assemble Vent Sections (SLP Pipe) ................35
C. Assemble Slip Sections ..........................36
D. Secure the Vent Sections ......................... 37
E. Disassemble Vent Sections ....................... 37
F. Vertical Termination Requirements ..................38
G. Horizontal Termination Requirements ...............39
8 Electrical Information
A. General Information ............................. 41
B. Wiring Requirements ............................42
9 Gas Information
A. Fuel Conversion ................................44
B. Gas Pressure ..................................44
C. Gas Connection ................................44
D. High Altitude Installations .........................44
E. Air Shutter Setting .............................. 45
10 Finishing
A. Facing Material .................................46
B. Mantel and Wall Projections ....................... 47
C. Decorative Fronts ...............................48
11 Appliance Setup
A. Remove Fixed Glass Assembly .................... 51
B. Remove the Shipping Materials ....................51
C. Clean the Appliance .............................51
D. Glass Panel Installation ..........................52
E. Media Placement ...............................53
F. IntelliFire Touch® Control System Setup .............. 54
G. Fixed Glass Assembly ...........................54
H. Install Decorative Front ..........................54
12 Reference Materials
A. Vent Components Diagrams ......................55
B. Accessories ...................................66
= Contains updated information.
Safety Alert Key:
DANGER! Indicates a hazardous situation which, if not avoided will result in death or serious injury.
WARNING! Indicates a hazardous situation which, if not avoided could result in death or serious injury.
CAUTION! Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE: Used to address practices not related to personal injury.
Note: The term “recommend” or “recommended” does not indicate a requirement. It is a best practice suggested by
Hearth & Home Technologies®.
3
Heat & Glo • 6000CMOD-IFT, 8000CMOD-IFT Installation Manual • 2509-980 Rev. Q • 7/22
Installation Standard Work Checklist
Customer:
Lot/Address:
Model (circle one): 6000CMOD-IFT
8000CMOD-IFT
Date Installed:
Location of Fireplace:
Installer:
Dealer/Distributor Phone #
Serial #:
Comments: Further description of the issues, who is responsible (Installer/ Builder/ Other Trades, etc) and corrective
action needed _____________________________________________________________________________________
_________________________________________________________________________________________________
_________________________________________________________________________________________________
Comments Communicated to party responsible ____________________ by ______________________on ___________
(Builder / Gen. Contractor/) (Installer) (Date)
Appliance Install YES IF NO, WHY?
Veried that the chase is insulated and sealed. (Pg. 16) ___________________________
Required non-combustible board is installed. (Pg. 33) ___________________________
Veried clearances to combustibles. (Pg. 14-15) ___________________________
Fireplace is leveled and secured. (Pg. 33) ___________________________
Venting/Chimney Section 7 (Pg 34-40)
Venting conguration complies to vent diagrams. ___________________________
Venting installed, locked and secured in place with proper clearance. ___________________________
Elbow heat shield installed per requirements. (Pg 23, 29) ___________________________
Firestops installed. ___________________________
Attic insulation shield installed. ___________________________
Exterior wall/Roof ashing installed and sealed. ___________________________
Terminations installed and sealed. ___________________________
Electrical Section 8 (Pg 41-43)
Unswitched power (110-120 VAC) provided to the appliance. ___________________________
Switch wires properly installed. ___________________________
Gas Section 9 (Pg 44-45)
Proper appliance for fuel type. ___________________________
Leak check performed and inlet pressure veried. ___________________________
Veried proper air shutter setting for installation type. ___________________________
Finishing Section 10 (Pg 46-50)
Combustible materials not installed in non-combustible areas. ___________________________
Veried all clearances meet installation manual requirements. ___________________________
Mantels and wall projections comply with installation manual requirements. ___________________________
Appliance Setup Section 11 (Pg 51-54)
All packaging and protective materials removed (inside & outside of appliance). ___________________________
Refractory and media installed correctly. ___________________________
Glass assembly installed and secured. ___________________________
Accessories installed properly. ___________________________
Decorative front properly installed. ___________________________
Manual bag and all of its contents are removed from inside/under
the appliance and given to party responsible for use and operation. ___________________________
Started appliance and veried no gas leaks exist. ___________________________
2509-982D 6/20
= Contains updated information.
Hearth & Home Technologies recommends the following:
• Photographing the installation and copying this checklist for your le.
• That this checklist remain visible at all times on the appliance until the installation is complete.
This standard work checklist is to be used by the installer in conjunction with, not instead of, the instructions contained in this
installation manual.
WARNING! Risk of Fire or Explosion! Failure to install appliance according to these instructions could
lead to a re or explosion.
ATTENTION INSTALLER:
Follow this Standard Work Checklist
Heat & Glo • 6000CMOD-IFT, 8000CMOD-IFT Installation Manual • 2509-980 Rev. Q • 7/224
This product is listed to ANSI standards for “Vented Gas
Fireplace Heaters” and applicable sections of “Gas Burn-
ing Heating Appliances for Manufactured Homes and
Recreational Vehicles”, and “Gas Fired Appliances for
Use at High Altitudes”.
A. Appliance Certication
E. Non-Combustible Materials Specication
Material which will not ignite and burn. Such materials are
those consisting entirely of steel, iron, brick, tile, concrete,
slate, glass or plasters, or any combination thereof.
Materials that are reported as passing ASTM E 136,
Standard Test Method for Behavior of Materials in
a Vertical Tube Furnace at 750 ºC shall be considered
non-combustible materials.
F. Combustible Materials Specication
Materials made of or surfaced with wood, compressed pa-
per, plant bers, plastics, or other material that can ignite
and burn, whether ame proofed or not, or plastered or
unplastered shall be considered combustible materials.
G. Electrical Codes
NOTICE: This appliance must be electrically wired
and grounded in accordance with local codes or, in the
absence of local codes, with National Electric Code
ANSI/NFPA 70-latest edition or the Canadian Electric
Code CSA C22.1.
A 110-120 VAC circuit for this product must be pro-
tected with ground-fault circuit-interrupter protection,
in compliance with the applicable electrical codes,
when it is installed in locations such as in bathrooms
or near sinks.
H. California
NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE.
This appliance is tested and approved as either supplemen-
tal room heat or as a decorative appliance. It should not be
factored as primary heat in residential heating calculations.
NOTICE: This installation must conform with local codes.
In the absence of local codes you must comply with the
National Fuel Gas Code, ANSI Z223.1-latest edition in
the U.S.A. and the CAN/CGA B149 Installation Codes in
Canada.
1 1 Product Specic and Important Safety Information
D. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced,
these rules do not apply. Check with your local gas utility
or authorities having jurisdiction.
When installing above 2000 feet elevation:
In the USA: Reduce input rate 4% for each 1000 feet
above 2000 feet.
• In CANADA: Input ratings are certied without a
reduction of input rate for elevations up to 4500 feet
(1370 m) above sea level. Please consult provincial
and/ or local authorities having jurisdiction for
installations at elevations above 4500 feet (1370 m).
Check with your local gas utility to determine proper
orice size.
MODELS: 6000CMOD-IFT, 8000CMOD-IFT
LABORATORY: Underwriters Laboratories, Inc. (UL)
TYPE: Direct Vent Heater
STANDARD: CSA / ANSI Z21.88:19 • CSA 2.33:19
C. BTU Specications
B. Glass Specications
This appliance is equipped with ceramic glass with an
anti-reective coating. Replace glass only with glass with
identical specications. Please contact your dealer for re-
placement glass.
Models
(U.S. or Canada)
Maximum
Input
BTU/h
Minimum
Input
BTU/h
Orice
Size
(DMS)
6000CMOD-IFT (NG) (0-2000 FT) 34,000 17,500 35
8000CMOD-IFT (NG) (0-2000 FT) 35,500 19,000 33
WARNING: This product and the fuels used to
operate this product (liquid propane or natural
gas), and the products of combustion of such fuels, can
expose you to chemicals including benzene, which is
known to the State of California to cause cancer and
reproductive harm. For more information go to: www.
P65Warnings.ca.gov.
5
Heat & Glo • 6000CMOD-IFT, 8000CMOD-IFT Installation Manual • 2509-980 Rev. Q • 7/22
I. Requirements for the Commonwealth of
Massachusetts
For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7)
feet above nished grade in the area of the venting, in-
cluding but not limited to decks and porches, the following
requirements shall be satised:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gas tter
shall observe that a hard wired carbon monoxide detector
with an alarm and battery back-up is installed on the oor
level where the gas equipment is to be installed. In addi-
tion, the installing plumber or gas tter shall observe that
a battery operated or hard wired carbon monoxide detec-
tor with an alarm is installed on each additional level of
the dwelling, building or structure served by the side wall
horizontal vented gas fueled equipment. It shall be the
responsibility of the property owner to secure the services
of qualied licensed professionals for the installation of
hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fu-
eled equipment is installed in a crawl space or an attic,
the hard wired carbon monoxide detector with alarm and
battery back-up may be installed on the next adjacent
oor level.
In the event that the requirements of this subdivision can
not be met at the time of completion of installation, the
owner shall have a period of thirty (30) days to comply
with the above requirements; provided, however, that dur-
ing said thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accor-
dance with the above provisions shall comply with NFPA
720 and be ANSI/UL 2034 listed and IAS certied.
Signage
A metal or plastic identication plate shall be permanent-
ly mounted to the exterior of the building at a minimum
height of eight (8) feet above grade directly in line with the
exhaust vent terminal for the horizontally vented gas fu-
eled heating appliance or equipment. The sign shall read,
in print size no less than one-half (1/2) in. in size, “GAS
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB-
STRUCTIONS”.
Inspection
The state or local gas inspector of the side wall horizon-
tally vented gas fueled equipment shall not approve the
installation unless, upon inspection, the inspector ob-
serves carbon monoxide detectors and signage installed
in accordance with the provisions of 248 CMR 5.08(2)(a)1
through 4.
Exemptions
The following equipment is exempt from 248 CMR 5.08(2)
(a)1 through 4:
The equipment listed in Chapter 10 entitled “Equipment
Not Required To Be Vented” in the most current edition
of NFPA 54 as adopted by the Board; and
• Product Approved side wall horizontally vented gas fu-
eled equipment installed in a room or structure separate
from the dwelling, building or structure used in whole or
in part for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall
horizontally vented gas equipment provides a venting
system design or venting system components with the
equipment, the instructions provided by the manufacturer
for installation of the equipment and the venting system
shall include:
Detailed instructions for the installation of the venting
system design or the venting system components; and
A complete parts list for the venting system design or
venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall
horizontally vented gas fueled equipment does not pro-
vide the parts for venting the ue gases, but identies
“special venting systems”, the following requirements
shall be satised by the manufacturer:
• The referenced “special venting system” instructions
shall be included with the appliance or equipment in-
stallation instructions; and
• The “special venting systems” shall be Product Ap-
proved by the Board, and the instructions for that sys-
tem shall include a parts list and detailed installation
instructions.
A copy of all installation instructions for all Product Ap-
proved side wall horizontally vented gas fueled equip-
ment, all venting instructions, all parts lists for venting
instructions, and/or all venting design instructions shall
remain with the appliance or equipment at the completion
of the installation.
See Gas Connection section for additional Common-
wealth of Massachusetts requirements.
Note: The following requirements reference various
Massachusetts and national codes not contained in this
document.
Heat & Glo • 6000CMOD-IFT, 8000CMOD-IFT Installation Manual • 2509-980 Rev. Q • 7/226
2 2 Getting Started
A. Design and Installation Considerations
Heat & Glo direct vent gas appliances are designed to
operate with all combustion air siphoned from outside of
the building and all exhaust gases expelled to the outside.
No additional outside air source is required.
Installation MUST comply with local, regional, state and
national codes and regulations. Consult insurance carrier,
local building inspector, re ocials or authorities having
jurisdiction over restrictions, installation inspection and
permits.
Before installing, determine the following:
• Where the appliance is to be installed.
• The vent system conguration to be used.
• Gas supply piping requirements.
• Provisions for optional heat management system.
• Electrical wiring requirements.
• Framing and nishing details.
Whether optional accessories—devices such as a fan,
wall switch, or remote control—are desired.
C. Tools and Supplies Needed
Before beginning the installation be sure that the following
tools and building supplies are available.
Tape measure Framing material
Pliers Hammer
Phillips screwdriver Manometer
Gloves Framing square
Voltmeter Electric drill and bits (1/4 in.)
Plumb line Safety glasses
Level Reciprocating saw
Flat blade screwdriver
Non-corrosive leak check solution
1/2 - 3/4 in. length, #6 or #8 Self-drilling screws
Caulking material (300 ºF minimum continuous exposure
rating)
One 1/4 in. female connection (for optional fan).
Improper installation, adjustment, alteration, service or
maintenance can cause injury or property damage. For
assistance or additional information, consult a qualied
service technician, service agency or your dealer.
Figure 2.1 Good Faith Wall Surface Temperatures Above Appliance
B. Good Faith Wall Surface
Installation and service of this appliance should be performed by
qualied personnel. Hearth & Home Technologies recommends
HHT Factory Trained or NFI certied professionals.
If installing a television (TV) above the appliance, see
Section 3 of the appliance Owner’s Manual.
MEASUREMENTS FROM
TOP EDGE OF THE OPENING
6 in.
18 in.
24 in.
30 in.
TO CEILING
12 in.
127°F
123°F
132°F
135°F
147°F
APPLIANCE FRONT
FIREPLACE
OPENING
NOTICE: Surface temperatures listed above are taken with
a temperature measuring probe as prescribed by the test
standard used for appliance certication. Temperatures
on walls or mantels taken with an infrared thermometer
may yield increased temperatures of up to 30 °F (17 °C) or
more depending on the thermometer settings and material
characteristics being measured. Use appropriate nishing
materials that are able to withstand these conditions. For
additional nishing guidelines, see Section 10.
7
Heat & Glo • 6000CMOD-IFT, 8000CMOD-IFT Installation Manual • 2509-980 Rev. Q • 7/22
D. Inspect Appliance and Components
Carefully remove the appliance and components from
the packaging.
The vent system components and decorative fronts may
be shipped in separate packages.
Report to your dealer any parts damaged in shipment,
particularly the condition of the glass.
Read all of the instructions before starting the instal-
lation. Follow these instructions carefully during the
installation to ensure maximum safety and benet.
WARNING! Risk of Fire or Explosion! Damaged parts
could impair safe operation. DO NOT install damaged, in-
complete or substitute components. Keep appliance dry.
Hearth & Home Technologies disclaims any responsibility for,
and the warranty will be voided by, the following actions:
Installation and use of any damaged appliance or vent
system component.
Modication of the appliance or vent system.
Installation other than as instructed by Hearth & Home
Technologies.
Improper positioning of the logs/media (as applicable) or
the glass assembly.
Installation and/or use of any component part not approved
by Hearth & Home Technologies.
Any such action may cause a re hazard.
WARNING! Risk of Fire, Explosion or Electric Shock!
DO NOT use this appliance if any part has been under
water. Call a qualied service technician to inspect the
appliance and to replace any part of the control system
and/or gas control which has been under water.
Heat & Glo • 6000CMOD-IFT, 8000CMOD-IFT Installation Manual • 2509-980 Rev. Q • 7/228
3 3 Framing and Clearances
A. Appliance/Decorative Front Dimension Diagrams
Dimensions are actual appliance dimensions. Use for reference only. For framing dimensions and clearances refer to Section 5.
Figure 3.1 Appliance Dimensions-6000 Models
A
B
CD
E
FRONT VIEW
TOP VIEW
LEFT SIDE RIGHT SIDE
F
G
H
I
J
K
N
O
GAS LINE
ACCESS
P
Q
HEAT MANAGEMENT SYSTEMS ACCESS
(LEFT & RIGHT SIDES)
R
S
L
ELECTRICAL
ACCESS
M
Location Inches Millimeters
J11-11/16 297
K28-1/2 724
L14-1/4 362
M8-1/2 216
N2-7/8 73
O8-1/2 216
P1 25
Q40-7/8 1038
R14-3/16 360
S15-3/8 391
Location Inches Millimeters
A 41 1041
B36-1/8 918
C33-1/2 851
D34-5/8 879
E2-1/4 57
F 9-11/16 246
G 6 dia 152
H39-7/8 1013
I 21 533
9
Heat & Glo • 6000CMOD-IFT, 8000CMOD-IFT Installation Manual • 2509-980 Rev. Q • 7/22
Figure 3.2 Appliance Dimensions-8000 Models
Location Inches Millimeters
J11-11/16 297
K35-1/2 901
L17-3/4 451
M8-1/2 216
N2-7/8 73
O8-1/2 216
P1 25
Q42-7/8 1089
R14-1/16 357
S17-1/16 433
Location Inches Millimeters
A 48 1219
B43-1/8 1096
C35-1/2 902
D36-5/8 930
E2-3/8 60
F 9-15/16 252
G 6 152
H41-7/8 1064
I 21 533
TOP VIEW
J
K
L
M
N
LEFT SIDE
O
GAS LINE
ACCESS
P
A
B
CD
FRONT VIEW
Q
E
F
G
H
I
RIGHT VIEW
HEAT MANAGEMENT SYSTEMS ACCESS
(LEFT & RIGHT SIDES)
R
S
ELECTRICAL
ACCESS
Heat & Glo • 6000CMOD-IFT, 8000CMOD-IFT Installation Manual • 2509-980 Rev. Q • 7/2210
FOLIO DECORATIVE FRONTS
G
A
B
C D
E
F
A B C D E FG
6000 FOL-36 in. 32-7/16 23-1/8 35-13/16 1-1/2 8-1/4 32-1/8 33-9/16
mm 824 587 910 38 210 816 853
8000 FOL-42 in. 39-7/16 25-5/16 42-13/16 1-1/2 8-1/4 34-1/8 35-11/16
mm 1002 643 1087 38 210 867 907
ARCADIA DECORATIVE FRONTS
Figure 3.3 Decorative Front Dimensions - Folio and Arcadia
G
A
B
CD
E
F
A B C D E FG
6000 ARC-36 in. 32-7/16 20-1/2 37-1/4 1-1/4 7-11/16 32-7/8 34-1/8
mm 824 521 946 32 195 835 867
8000 ARC-42 in. 39-7/16 22-7/16 44-1/4 1-1/4 7-11/16 34-13/16 36-1/16
mm 1002 570 1124 32 195 884 916
11
Heat & Glo • 6000CMOD-IFT, 8000CMOD-IFT Installation Manual • 2509-980 Rev. Q • 7/22
HALSTON DECORATIVE FRONTS
CHATEAU DECORATIVE FRONTS
Figure 3.4 Decorative Front Dimensions - Halston and Chateau
G
A
B
C
D
E
F
G
A
B
CD
E
F
A B C D E FG
6000 HAL-36 in. 32-7/16 21-1/4 37-1/4 1-1/4 7-1/4 32-7/8 34-1/8
mm 824 540 946 32 184 835 867
8000 HAL-42 in. 39-7/16 23-1/8 44-1/4 1-1/4 7-1/4 34-13/16 36-1/16
mm 1002 587 1124 32 184 884 916
A B C D E FG
6000 CHA-36 in. 20-1/2 32-7/16 37-1/4 1-1/2 7-7/8 32-7/8 34-1/8
mm 521 824 946 38 200 835 867
8000 CHA-42 in. 22-7/16 39-7/16 44-1/8 1-1/4 7-7/8 34-13/16 36-1/16
mm 570 1002 1121 32 200 884 916
Heat & Glo • 6000CMOD-IFT, 8000CMOD-IFT Installation Manual • 2509-980 Rev. Q • 7/2212
CHATEAU FORGE DECORATIVE FRONTS
GALLERIA DECORATIVE FRONTS
Figure 3.5 Decorative Front Dimensions - Chateau Forge and Galleria
G
A
B
C D
E
F
A
B
G
D
F
E
C
A B C D E FG
6000 CHAF-36 in. 32-1/4 20-3/4 37 1-3/16 7-9/16 32-7/8 34-1/8
mm 819 527 940 30 192 835 867
8000 CHAF-42 in. 39-1/4 22-5/8 44 1-1/4 7-5/8 34-3/4 36
mm 997 575 1118 32 194 883 914
A B C D E FG
6000 GALLERIA-6 in. 31-9/16 20-7/8 37-1/8 1-1/4 7-1/2 32-7/8 34-1/16
mm 802 530 943 32 191 835 865
8000 GALLERIA-8 in. 38-9/16 22-3/4 44-1/16 1-1/4 7-1/2 34-3/4 36
mm 979 578 1121 32 191 883 914
13
Heat & Glo • 6000CMOD-IFT, 8000CMOD-IFT Installation Manual • 2509-980 Rev. Q • 7/22
G
A
B
C
DE
F
A B C D E FG
6000 CF-36 in. 31-9/16 22-1/8 35-13/16 3-1/2 4-9/16 26-13/16 28-15/16
mm 802 562 910 89 116 681 735
8000 CF-42 in. 38-1/2 24-1/16 42-3/4 3-1/2 4-9/16 28-11/16 30-13/16
mm 978 611 1086 89 116 729 783
Figure 3.6 Decorative Front Dimensions - Clean Face and Iron Age
IRON AGE DECORATIVE FRONTS
A
B
C
G
D
E
F
A B C D E FG
6000 FSI-36 in. 27-3/8 23-1/8 37-3/16 1-1/4 6-3/4 32-7/8 34-1/8
mm 695 587 945 32 172 835 867
8000 FSI-42 in. 34-3/8 25-3/16 44-3/16 1-1/4 6-3/4 34-13/16 36-1/16
mm 873 640 1122 32 172 884 916
CLEAN FACE DECORATIVE FRONTS
Heat & Glo • 6000CMOD-IFT, 8000CMOD-IFT Installation Manual • 2509-980 Rev. Q • 7/2214
B. Clearances to Combustibles
When selecting a location for the appliance it is important
to consider the required clearances to walls. See Figure
3.5.
WARNING! Risk of Fire or Burns! Provide adequate
clearance around air openings and for service access.
Due to high temperatures, the appliance should be lo-
cated out of trac and away from furniture and draperies.
NOTICE: Illustrations reect typical installations and are
FOR DESIGN PURPOSES ONLY. Illustrations/diagrams
are not drawn to scale. Actual installation may vary due to
individual design preference.
Figure 3.5 Appliance Locations
NOTICE: Illustrations reect typical installations and are
FOR DESIGN PURPOSES ONLY. Illustrations/diagrams
are not drawn to scale. Actual installation may vary due to
individual design preference.
A B C D E F
6000 in. 51 42 72 See Section 10.B
Mantel Projections
22 17-3/4
mm 1295 1067 1829 559 451
8000 in. 55-7/8 49 79 See Section 10.B
Mantel Projections
22 19-3/4
mm 1419 1245 2007 559 502
1/2 IN.
ALCOVE
INSTALLATION
TOP VENT
ONE 90º ELBOW
A
BC
B
D
B
E
F
A
NOTE: THE REAR STANDOFF MAY NEED
TO BE REMOVED WHEN VENTING AT 45º
15
Heat & Glo • 6000CMOD-IFT, 8000CMOD-IFT Installation Manual • 2509-980 Rev. Q • 7/22
Figure 3.6 Clearances to Combustibles
* Adjust framing dimensions for interior sheathing (such as sheetrock).
G** For installations with vinyl ooring see section 3.D.
C
B
D
A
F
G
H
I
J
E
* MINIMUM FRAMING DIMENSIONS
Models
A B C D E F G** H I J
Rough
Opening
(Width)
Rough
Opening
(Height)
Rough
Opening
(Depth)
Rough
Opening
(Width)
Clearance
to Ceiling
Combustible
Floor
Combustible
Flooring
Behind
Appliance
Sides of
Appliance
Front of
Appliance
6000 in. 10 40-1/8 22 42 32 0 0 1/2 1/2 36
mm 254 1019 559 1067 813 0 0 13 13 914
8000 in. 10 42-1/8 22 49 32 0 0 1/2 1/2 36
mm 254 1070 559 1245 813 0 0 13 13 914
COMBUSTIBLE FLOORING MAY BE INSTALLED
NEXT TO THE FRONT OF THE APPLIANCE.
Heat & Glo • 6000CMOD-IFT, 8000CMOD-IFT Installation Manual • 2509-980 Rev. Q • 7/2216
C. Constructing the Appliance Chase
A chase is a vertical box-like structure built to enclose the
gas appliance and/or its vent system. In cooler climates
the vent should be enclosed inside the chase.
NOTICE: Treatment of ceiling restops and wall shield
restops and construction of the chase may vary with the
type of building. These instructions are not substitutes
for the requirements of local building codes. Therefore,
you MUST check local building codes to determine the
requirements to these steps.
NOTICE: Where required by code, install only sprinkler
heads with a sprinkler activation temperature classied
as Extra High.
Sprinklers inside of chase: Keep sprinkler head away
from vent and chimney.
Heat Management applications: Maintain 36 inches of
clearance to openings from which heat is discharged
such as heat zone registers, etc. Refer to Section 6.B
for Heat Management options allowed for this appliance.
Chases should be constructed and insulated in the same
manner as the thermal envelope of the home based on
the code requirements for that climate zone to prevent air
leakage and draft problems. The chase is an extension of
the building thermal envelope.
To further prevent drafts and air leakage, the wall shield
and ceiling restops should be caulked with caulk with
a minimum of 300 ºF continuous exposure rating to
seal gaps. Gas line holes and other openings should
be caulked with caulk with a minimum of 300 ºF continu-
ous exposure rating or stued with unfaced insulation. If the
appliance is being installed on a cement surface, a layer of
plywood may be placed underneath to prevent conducting
cold up into the room.
NOTICE: Install appliance on hard metal or wood surfaces
extending full width and depth. DO NOT install directly
on carpeting, vinyl, tile or any combustible material other
than wood.
WARNING! Risk of Fire! Maintain specied air space
clearances to appliance and vent pipe:
Insulation and other materials must be secured to prevent
accidental contact.
• The chase must be properly blocked to prevent blown
insulation or other combustibles from entering and
making contact with replace or chimney.
• Failure to maintain airspace may cause overheating and
a re.
12 IN. MIN.
APPLIANCE WIDTH MIN.
12 IN. MIN.
VINYL
Figure 3.7 Vinyl Flooring Recommendations
Vinyl Flooring
Vinyl ooring is sensitive to heat. To avoid damage to
the vinyl ooring, a 12 inch minimum x 12 inch minimum
hearth is recommended when using vinyl ooring up
to the wall. See Figure 3.7. If no hearth is used, it is
recommended to provide a minimum of 30 inches of
clearance in front of the appliance to the vinyl ooring OR
the bottom of the appliance should be raised a minimum
of 24 inches o of the oor to allow the vinyl ooring to be
installed up to the wall.
D. Floor Protection
Hearth and Home Technologies does not recommend
adhesive based vinyl ooring products due to thermal
expansion during operation. Floating style ooring can be
used, but will reach temperatures up to 110 °F (based on
ambient temperature of 70 °F). Consult the manufacturer’s
ooring specications to ensure compatibility.
NOTICE: Clearances that do not meet the minimum
guidelines could result in damage or buckling to the vinyl
ooring and is done at the installer’s risk.
17
Heat & Glo • 6000CMOD-IFT, 8000CMOD-IFT Installation Manual • 2509-980 Rev. Q • 7/22
A. Vent Termination Minimum Clearances
Roof Pitch H (Min.) Ft.
Flat to 6/12...........................................................1.0*
Over 6/12 to 7/12 .................................................1.25*
Over 7/12 to 8/12 .................................................1.5*
Over 8/12 to 9/12 .................................................2.0*
Over 9/12 to 10/12 ...............................................2.5*
Over 10/12 to 11/12 .............................................3.25
Over 11/12 to 12/12 .............................................4.0
Over 12/12 to 14/12 .............................................5.0
Over 14/12 to 16/12 .............................................6.0
Over 16/12 to 18/12 .............................................7.0
Over 18/12 to 20/12 .............................................7.5
Over 20/12 to 21/12 .............................................8.0
Figure 4.1 Minimum Height From Roof to Lowest Discharge
Opening
HORIZONTAL
OVERHANG
VERTICAL
WALL
GAS DIRECT VENT
TERMINATION CAP
12
X
ROOF PITCH
IS X/ 12
LOWEST
DISCHARGE
OPENING
2 FT.
MIN.
20 INCHES MIN.
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
4 4 Termination Location and Vent Information
Fire Risk.
Maintain vent clearance to combustibles as
specied.
DO NOT pack air space with insulation or other
materials.
Failure to keep insulation or other materials away
from vent pipe could cause overheating and re.
WARNING
Figure 4.2 Staggered Termination Caps
Gas, Wood or Fuel Oil
Termination Cap
B
Gas
Termination
Cap **
A *
*If using decorative cap cover(s), this distance may need to be
increased. Refer to the installation instructions supplied with the
decorative cap cover.
**
A B
6 in. (minimum) up to 20 in.
152 mm/508 mm
18 in. minimum
457 mm
20 in. and over 0 in. minimum
In a staggered installation with both gas and wood or fuel oil
terminations, the wood or fuel oil termination cap must be
higher than the gas termination cap.
* H minimum may vary depending on regional snowfall.
Refer to local codes.
CAUTION! Risk of Burns! Termination caps are HOT,
consider proximity to doors, trac areas or where people
may pass or gather (sidewalk, deck, patio, etc.). Listed
cap shields available. Contact your dealer.
Local codes or regulations may require different
clearances.
Hearth & Home Technologies assumes no responsibility
for the improper performance of the appliance when the
venting system does not meet these requirements.
Vinyl protection kits are suggested for use with vinyl siding.
Measure horizontal and vertical termination cap clearances
as noted in Figure 4.3.
Figure 4.3
CLEARANCE
= 6 IN.
H
V
V
H=Measure Horizontal Distances from H
V=Measure Vertical Distances from V
H
Heat & Glo • 6000CMOD-IFT, 8000CMOD-IFT Installation Manual • 2509-980 Rev. Q • 7/2218
Figure 4.4 Minimum Clearances for Termination
C
JB
D
B
F
B
A
E
V
V
V
V
V
V
M
H or i
V
G
X
VH
A
VV
H
X= AIR SUPPLY INLET
V= VENT TERMINAL
= AREA WHERE TERMINAL IS NOT PERMITTED
Electrical
Service
V
K
VK
V
L
C
V
B. Vent Terminal Clearances
U.S.A. CANADA
AClearance above grade,veranda, porch, deck, or balcony 12 in. (305 mm) 12 in. (305 mm)
BClearance to window or door that may be opened, or to permanently closed window
U.S.A.: = 9 in. min. (229 mm min.) CANADA: = 12 in. min. ( 305 mm min.)
C
clearance below unventilated sot 18 in. (457 mm) 18 in. (457 mm)
clearance below ventilated sot 18 in. (457 mm) 18 in. (457 mm)
clearance below any vinyl sots and electrical service 30 in. (762 mm) 30 in. (762 mm)
D clearance to outside corner 6 in. (152 mm) 6 in. (152 mm)
E clearance to inside corner 6 in. (152 mm) 6 in. (152 mm)
Fnot to be installed above a gas meter/regulator assembly within 3 feet horizontally from
the center-line of the regulator 3 ft (914 mm) 3 ft (914 mm)
G clearance to gas service regulator vent outlet 3 ft (914 mm) 3 ft (914 mm)
Hclearance to non-mechanical air supply inlet to building or the combustion air inlet to
any other appliance termination (mechanical or non-mechanical)
9 in. min.
(229 mm min.)
12 in. min.
(305 mm min.)
I
clearance to a mechanical (powered) air supply inlet
***(All mechanical air intakes within 10 feet of a horizontal termination cap must be
a minimum of 3 feet below termination.)
3 ft (914 mm)*** 6 ft (1.8 m)
J
On public property: clearance above paved sidewalk or a paved driveway. 7 ft (2.1 m) 7 ft (2.1 m)**
**(A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings
and serves both dwellings.)
K
clearance from sides of electrical service 6 in. (152 mm) 6 in. (152 mm)
Location of the vent termination must not interfere with access to the electrical service.
L
clearance above electrical service 12 in. (305 mm) 12 in. (305 mm)
Location of the vent termination must not interfere with access to the electrical service.
M
clearance under veranda, porch, deck, balcony or overhang
*(Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of
two sides beneath the oor.)
18 in. (457 mm) 12 in. (305 mm)*
vinyl or composite overhang 42 in. (1067 mm) 42 in. (1067 mm)
U.S.A. Installations: In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.
Canadian Installations: In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
19
Heat & Glo • 6000CMOD-IFT, 8000CMOD-IFT Installation Manual • 2509-980 Rev. Q • 7/22
C. Approved Pipe
This appliance is approved for use with Hearth & Home
Technologies DVP or SLP venting systems. Refer to Sec-
tion 12.A for vent component information and dimensions.
Only use listed decorative termination caps/shrouds with
Hearth & Home Technologies approved venting systems.
DO NOT mix pipe, ttings or joining methods from dier-
ent manufacturers.
The pipe is tested to be run inside an enclosed wall.
There is no requirement for inspection openings at each
joint within the wall.
WARNING! Risk of Fire or Asphyxiation. This appli-
ance requires a separate vent. DO NOT vent to a pipe
serving a separate solid fuel burning appliance.
Heat & Glo • 6000CMOD-IFT, 8000CMOD-IFT Installation Manual • 2509-980 Rev. Q • 7/2220
D. Use of Elbows
Diagonal runs have both vertical and horizontal vent as-
pects when calculating the eects. Use the rise for the
vertical aspect and the run for the horizontal aspect. See
Figure 4.5.
Two 45º elbows may be used in place of one 90º elbow.
On 45º runs, one foot of diagonal is equal to 8-1/2 in. (216
mm) horizontal run and 8-1/2 in. (216 mm) vertical run. A
length of straight pipe is allowed between two 45º elbows.
See Figure 4.5.
Figure 4.6 shows the vertical and horizontal osets for
DVP or SLP elbows.
Figure 4.5
HORIZONTAL
VERTICAL
RUN
RISE
EFFECTIVE
LENGTH
Y
X
X
X
DVP
Pipe
Eective Length Rise/Run
Inches Millimeters Inches Millimeters
DVP4 4 102 2-3/4 70
DVP6 6 152 4-1/4 108
DVP12 12 305 8-1/2 216
DVP24 24 610 17 432
DVP36 36 914 25-1/2 648
DVP48 48 1219 34 864
DVP6A 3 to 6 76 to 152 2-1/8-4-1/4 54-108
DVP12A 3 to 12 76 to 305 2-1/8-8-1/2 54-216
Vent Type X
Inches Millimeters
DVP 16-1/4 413
SLP 11-1/4 286
Figure 4.6 Vertical and Horizontal Oset for DVP and SLP Elbows
SLP
Pipe
Eective Length Rise/Run
Inches Millimeters Inches Millimeters
SLP4 4 102 2-3/4 70
SLP6 6 152 4-1/4 108
SLP12 12 305 8-1/2 216
SLP24 24 610 17 432
SLP36 36 914 25-1/2 648
SLP48 48 1219 34 864
SLP6A 3 to 6 76 to 152 2-1/8-4-1/4 54-108
SLP12A 3 to 12 76 to 305 2-1/8-8-1/2 54-216
Vent
Type
X Y
Inches Millimeters Inches Millimeters
DVP 6-5/8 168 16-1/2 419
SLP 5-1/4 133 11-3/8 289
/