Grunbeck GENO-OSMO-X Operating instructions

Type
Operating instructions
Operation manual
Reverse osmosis system GENO-OSMO-X
with GENO-tronic operating element
and GENO-OSMO-X controller
starting from software version V1.11
Edition: April 2018
Order no. 124 750 927-inter
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
1
Table of contents
AGENERAL ............................................................................................................................................................................................ 4
1
|
P
REFACE
..................................................................................................................................................................................................... 4
2
|
H
OW TO USE THIS OPERATION MANUAL
............................................................................................................................................................ 4
3
|
G
ENERAL SAFETY INFORMATION
..................................................................................................................................................................... 5
3.1Symbols and notes .............................................................................................................................................................................. 5
3.2Operating personnel ............................................................................................................................................................................ 5
3.3Appropriate application ........................................................................................................................................................................ 5
3.4Protection from water damage ............................................................................................................................................................. 6
3.5Indication of specific dangers ............................................................................................................................................................... 6
4
|
S
HIPPING AND STORAGE
................................................................................................................................................................................ 6
5
|
D
ISPOSAL OF USED PARTS AND MATERIALS
...................................................................................................................................................... 6
BBASIC INFORMATION ........................................................................................................................................................................ 7
1
|
L
AWS
,
REGULATIONS
,
STANDARDS
.................................................................................................................................................................. 7
2
|
W
ATER
........................................................................................................................................................................................................ 7
3
|
F
UNCTIONAL PRINCIPLE OF REVERSE OSMOSIS
................................................................................................................................................. 8
CPRODUCT DESCRIPTION .................................................................................................................................................................. 9
1
|
T
YPE DESIGNATION PLATE
.............................................................................................................................................................................. 9
2
|
F
UNCTIONAL DESCRIPTION
........................................................................................................................................................................... 10
3
|
T
ECHNICAL SPECIFICATIONS
......................................................................................................................................................................... 15
4
|
A
PPROPRIATE APPLICATION
......................................................................................................................................................................... 16
4.1System idle time ................................................................................................................................................................................. 16
5
|
A
PPLICATION LIMITS
.................................................................................................................................................................................... 17
6
|
S
COPE OF SUPPLY
...................................................................................................................................................................................... 18
6.1Standard equipment ........................................................................................................................................................................... 18
6.2Optional accessories .......................................................................................................................................................................... 19
6.3Consumables ..................................................................................................................................................................................... 22
6.4Wearing parts .................................................................................................................................................................................... 23
DINSTALLATION ................................................................................................................................................................................. 24
1
|
G
ENERAL
I
NSTALLATION
I
NSTRUCTIONS
........................................................................................................................................................ 24
1.1Preliminary work ................................................................................................................................................................................ 24
2
|
W
ATER INSTALLATION
.................................................................................................................................................................................. 24
3
|
H
OW TO CONNECT THE SYSTEM
.................................................................................................................................................................... 25
4
|
E
LECTRICAL INSTALLATION
........................................................................................................................................................................... 26
4.1Circuit diagram of power distribution .................................................................................................................................................. 26
4.2Connections within the GENO-OSMO-X control unit and the GENO-tronic operating element: ........................................................ 28
4.3Connections within the GENO-OSMO-X reverse osmosis system .................................................................................................... 29
4.4Connections to other subsystems - system output ............................................................................................................................. 30
4.5Connections to other subsystems – Residual hardness monitoring system NX1CQ1 for pre-treatment by water softener ................. 30
4.6Connections to other subsystems – Dosing pump RO1 P2 for antiscalant pre-treatment ....................................................................... 31
4.7Connections within the OSMO-X reverse osmosis system – AVRO pre-treatment RO1B5 ................................................................ 31
4.9Subsystems water softener and/or pressure booster interconnected via RS485 data line – Connection of terminating resistors ...... 32
4.10 Connections to other subsystems – Pre-treatment by water softener ................................................................................................. 32
4.11Connections to other sub-systems – Pressure booster installed downstream .................................................................................... 32
4.12Connections to other subsystems – Optional signals or accessories ................................................................................................. 33
ESTART-UP ......................................................................................................................................................................................... 34
1
|
H
OW TO FLUSH THE SYSTEM
........................................................................................................................................................................ 34
1.1How to flush off the preservation agent .............................................................................................................................................. 34
FOPERATION ...................................................................................................................................................................................... 36
1
|
I
NTRODUCTION
........................................................................................................................................................................................... 36
2
|
S
CREEN LAYOUT OF THE
GENO-
TRONIC OPERATING ELEMENT
........................................................................................................................ 36
2.1Home screen ..................................................................................................................................................................................... 36
2.2Info level of GENO-OSMO-X.............................................................................................................................................................. 37
2.3Change, save, reject parameters ....................................................................................................................................................... 38
2.4Acknowledgement of errors/signals ................................................................................................................................................... 39
2.5Screen saver ...................................................................................................................................................................................... 40
3
|
S
YSTEM RANGE
.......................................................................................................................................................................................... 40
3.1System menu I ................................................................................................................................................................................... 40
3.2Data logging on an SD card ............................................................................................................................................................... 42
3.2System menu II .................................................................................................................................................................................. 45
3.3Software version ................................................................................................................................................................................ 45
4
|
S
UB
-
SYSTEM
GENO-OSMO-X
REVERSE OSMOSIS SYSTEM
........................................................................................................................... 45
4.1 User programming level ..................................................................................................................................................................... 46
4.2Installer level (Code 113) ................................................................................................................................................................... 48
4.3Customer service level ....................................................................................................................................................................... 54
4.4Extended customer service level I ...................................................................................................................................................... 54
4.5Extended customer service level II ..................................................................................................................................................... 54
4.6Counter readings, error memory ........................................................................................................................................................ 55
4.7Key operation ..................................................................................................................................................................................... 56
4.8Reset of counter readings .................................................................................................................................................................. 56
4.9Memory of operating parameters ....................................................................................................................................................... 56
5
|
P
ERMEATE TANK
......................................................................................................................................................................................... 57
6
|
P
RE
-
TREATMENT BY MEANS OF ANTISCALANT DOSING
..................................................................................................................................... 58
6.1Operator menu ................................................................................................................................................................................... 59
6.2Customer Service level ...................................................................................................................................................................... 5 9
GTROUBLESHOOTING ....................................................................................................................................................................... 60
1
|
B
ASIC INFORMATION
.................................................................................................................................................................................... 60
2
|
H
OW TO REMEDY WARNINGS
........................................................................................................................................................................ 61
3
|
T
ROUBLESHOOTING
.................................................................................................................................................................................... 64
HMAINTENANCE ................................................................................................................................................................................. 7 0
1
|
B
ASIC INFORMATION
.................................................................................................................................................................................... 70
2
|
I
NSPECTION
(
FUNCTIONAL CHECK
) ................................................................................................................................................................ 70
3
|
M
AINTENANCE
............................................................................................................................................................................................ 7 1
4
|
O
PERATION LOG
......................................................................................................................................................................................... 72
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
2
Publisher's information
All rights reserved.
Copyright by Grünbeck Wasseraufbereitung GmbH
Printed in Germany
Effective with the date of edition indicated on the cover sheet.
-We reserve the right to modifications, especially with regard to
technical progress-
Reprints, translations into foreign languages, electronic storage
or copying of this operation manual only with explicit written ap-
proval of Grünbeck Wasseraufbereitung GmbH.
Any type of duplication not authorised by Grünbeck Wasserauf-
bereitung is a copyright violation and subject to legal action.
Responsible for contents:
Grünbeck Wasseraufbereitung GmbH
Josef-Grünbeck-Str. 1, 89420 Hoechstaedt/Germany
Phone +49 9074 41-0 Fax +49 9074 41-100
www.gruenbeck.de service@gruenbeck.de
Print: Grünbeck Wasseraufbereitung GmbH
Josef-Grünbeck-Str. 1, 89420 Hoechstaedt/Germany
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
3
EU Declaration of Conformity
This is to certify that the system designated below meets the safety and health requirements of
the applicable European guidelines in terms of its design, construction and execution.
If the system is modified in a way not approved by us, this certificate is void.
Manufacturer: Grünbeck Wasseraufbereitung GmbH
Josef-Grünbeck-Str. 1
89420 Hoechstaedt/Germany
Responsible for documenta-
tion:
Markus Pöpperl
System designation: Reverse osmosis system GENO-OSMO-X
System size: 200, 400, 800, 1200, 1600, 2200, 3000
Serial number: refer to type designation plate
Applicable guidelines: Machinery Directive (2006/42/EC)
EMC Directive (2014/30/EU)
Applied harmonised standards,
in particular:
DIN EN ISO 12100: 2011-03
DIN EN 61000-6-2: 2006-03
DIN EN 61000-6-3: 2011-09
Applied national standards
and technical
specifications,
in particular:
City, date and signature: Hoechstaedt, 30.04.2018 p.p.
M. Pöpperl
Dipl.-Ing. (FH)
Function of signatory: Head of Department for Technical Product Design
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
4
A General
1 | Preface
Thank you for opting for a Grünbeck product. Backed by decades
of experience in the area of water treatment, we provide solutions
for all kind of processes.
All Grünbeck systems and devices are made of high-quality mate-
rials. This ensures reliable operation over many years, provided
you treat your water treatment systems with the required care.
This operation manual assists you with important information.
Therefore, please read the entire operation manual before in-
stalling, operating or maintaining the system.
Customer satisfaction is our prime objective and providing cus-
tomers with qualified advice is crucial. If you have any questions
concerning this device, possible extensions or general water and
waste water treatment, our field staff, as well as the experts at
our headquarters in Hoechstaedt, are available to help you.
Advice and assistance For advice and assistance please contact your local representa-
tive (see www.gruenbeck.de) or get in touch with our service
centre which can be reached during office hours:
Phone: +49 9074 41-333
Fax: +49 9074 41-120
Email: service@gruenbeck.de
We can connect you with the appropriate expert more quickly if
you provide the required system data.
2 | How to use this operation manual
This operation manual is intended for the operators of our sys-
tems. It is divided into several chapters and a letter is assigned to
each of them in alphabetical order. In order to find the specific in-
formation you are looking for, check for the corresponding chapter
on page 3.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
5
3 | General safety information
3.1 Symbols and notes Important information in this operation manual is characterised
by symbols. Please pay particular attention to this information to
ensure the hazard-free, safe and efficient handling of the sys-
tem.
Danger! Failure to adhere to this information will cause serious
or life-threatening injuries, extreme damage to property or inad-
missible contamination of the drinking water.
Warning! Failure to adhere to this information may cause inju-
ries, damage to property or contamination of the drinking water.
Attention! Failure to adhere to this information may result in
damage to the system or other objects.
Note: This symbol characterises information and tips to make
your work easier.
Tasks with this symbol may only be performed by Grünbeck's
technical service/authorised service company or by persons ex-
pressly authorised by Grünbeck.
Tasks with this symbol may only be performed by qualified elec-
trical experts according to the VDE guidelines or according to
the guidelines of a similar local institution.
Tasks with this symbol may only be performed by water compa-
nies or approved installation companies. In Germany, the instal-
lation company must be registered in a water company installa-
tion directory as per §12(2) AVBWasserV (German Ordinance on
General Conditions for the Supply of Water).
3.2 Operating personnel Only persons who have read and understood this operation
manual are permitted to work with the system. The safety guide-
lines are to be strictly adhered to.
3.3 Appropriate application The system may only be used for the purpose outlined in the
product description (chapter C). The guidelines in this operation
manual as well as the applicable local guidelines concerning the
drinking water protection, accident prevention and occupational
safety must be adhered to.
In addition, appropriate application also implies that the system
may only be operated when it is in proper working order.
Any malfunctions must be repaired at once.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
6
3.4 Protection from water
damage
Warning! In order to properly protect the installation site against
water damage:
a sufficient floor drain system must be available or
a safety device (see chapter C Accessories) must be in-
stalled.
Warning! In case of a power failure, floor drains with a dis-
charge to a lifting system will be out of operation.
3.5 Indication of
specific dangers
Danger due to electrical energy! Do not touch electrical parts
with wet hands! Disconnect the system from mains before start-
ing work on electrical parts of the system. Have qualified experts
replace damaged cables immediately.
Danger due to mechanical energy! System parts may be subject
to overpressure. Danger of injury and damage to property due to
escaping water and unexpected movement of system parts.
Check pressure pipes regularly. Depressurise the system before
starting repair or maintenance work on the system.
Hazardous to health due to contaminated drinking water! The
system may only be installed by a specialist company. The oper-
ation manual must be strictly adhered to! Ensure that there is
sufficient flow. The pertinent guidelines must be followed for
starting-up after extended periods of standstill. Inspections and
maintenance must be performed at the intervals specified!
Note: By concluding a maintenance contract, you ensure that all
of the required tasks are performed on time. You may perform
the interim inspections yourself.
4 | Shipping and storage
Attention! The system may be damaged by frost or high tem-
peratures. In order to avoid damage of this kind:
Protect from frost during transportation and storage!
Do not install or store system next to objects which radiate a lot
of heat.
The system may only be transported and stored in its original
packing. Ensure that it is handled with care and placed the right
side up (as indicated on the packing).
5 | Disposal of used parts and materials
Used parts and materials are to be disposed of, or made availa-
ble for recycling purposes, according to the applicable local
guidelines.
If a material is subject to specific regulations, adhere to the in-
structions indicated on the packing.
If in doubt, contact your local waste disposal authority or the
manufacturer for more information.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
7
B Basic information
1 | Laws, regulations, standards
In the interest of good health, rules cannot be ignored when it
comes to the processing of drinking water. This operation man-
ual takes into consideration the current regulations and stipu-
lates information that you will need for the safe operation of your
water treatment system.
Among other things, the regulations stipulate that
only approved companies are permitted to make major modi-
fications to water supply facilities
and that tests, inspections and maintenance on installed de-
vices are to be performed at regular intervals.
2 | Water
Due to dynamic substance and water cycles, harmful elements,
which are only partly and only slowly biodegradable are increas-
ingly released into nature. Over time, these elements therefore
accumulate in ground and surface water. Removing them again
from natural water bodies represents a particular challenge.
Grünbeck rises to this challenge and aims at generating unpol-
luted drinking and process water.
The water works provide us with pure drinking water that is suit-
able for consumption. However, if the water is to be used for
technical purposes, further treatment is frequently required.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
8
3 | Functional principle of reverse osmosis
Principle:
Pre-treated feed
water
Concentrate:
Permeate
Fig. B-1: Functional principle
Osmosis Osmotic pressure Reversed osmosis
Solution of high
concentration
Solution of low
concentration
Solution of high
concentration
Solution of low
concentration
Solution of high
concentration
(concentrate)
Solution of low
concentration
(permeate)
Fig. B-2: Reverse osmosis principle
In the osmosis process, watery solutions of different concentra-
tions are separated by a semi-permeable membrane. In keeping
with the law of nature, the concentrations try to equalise. On the
side of the higher original concentration, the so-called "osmotic"
pressure is generated.
In case of reverse osmosis, this osmotic pressure is countered
by a higher pressure. The consequence: the process proceeds
in the reverse direction. A particular advantage of the reverse
osmosis technology compared to other water treatment pro-
cesses is the fact that - apart from the removal of dissolved salts
- bacteria, germs and dissolved organic substances are also re-
duced.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
9
C Product description
1 | Type designation
plate
Please specify the data shown on the type designation plate of
your GENO-OSMO-X reverse osmosis system in order to speed
up the processing of enquiries or orders. Please copy the indi-
cated information to the table below in order to have it handy
whenever necessary.
Reverse osmosis system
GENO-OSMO-X:
Serial number:
Order no.:
Fig. C-1: Type designation plate of the reverse osmosis system GENO-OSMO-X
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
10
2 | Functional description
Feed water
Concentrate to drain
Permeate
Fig. C-2: System design of the reverse osmosis system GENO-OSMO-X
1
2
3
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
11
Feed water inlet
BL1
Connection 1“ or 1¼ (male thread), flat sealing, for feed water
connection by others on site
Note: Provide connection by means of water meter screw con-
nection.
Solenoid valve
for feed water
RO1V1
During the permeate production, this valve is always open. Fol-
lowing the system stop (tank full), the valve remains open for
the programmed flushing volume of the membrane(s).
Fine filter
RO1F1
Pre-filtration of the feed water incl. pressure reducer (pre-set)
4.0 bar and integrated pressure gauge for feed water pressure.
Flow sensor
feed
RO1CF2
Via pulse signal to the control unit.
Feed = Concentrate recirculation + Permeate + Concentrate to
drain.
Pressure switch for
minimum pressure
RO1CP1
To prevent the high-pressure pump from running dry. Switches
time-delayed after opening the solenoid valve for feed water.
Flow sensor
feed water
RO1CF1
Via pulse signal to the control unit.
Feed water = Permeate + Concentrate to drain.
Adjusting valve concen-
trate to drain with drive
RO1V3
To automatically adjust the volume flow concentrate to drain (re-
covery). During the permeate production, this portion of the wa-
ter flow permanently flows to the drain. The volume flow is sub-
ject to the system size. In case of tank "full" as well as in case of
a system failure, the valve always opens the entire cross section
in combination with the solenoid valve for feed water.
Pressure reducer
concentrate
RO1H4
To improve the regulation accuracy of the adjusting valves (set
to 6 bar)
Adjusting valve
concentrate recirculation
with drive
RO1V2
For automatic adjustment of the volume flow concentrate recir-
culation. The volume flow is subject to the system size.
Sampling valve
concentrate
RO1H1
Allows manual quality determination via sampling valve.
Connection concentrate
to drain
BL2
1“ male thread, flat sealing
Note: Provide for connection via water meter screw connection.
Permeate connection
BL3
1“ male thread, flat sealing
Note: Provide for connection via water meter screw connection.
High-pressure pump
RO1P1
Centrifugal pump system (frequency-controlled) that generates
the operating pressure required for the membrane. Pump oper-
ates upon permeate demand from the level control located in the
permeate tank. By means of the frequency converter, the
pump's revolution speed is adapted in a way that the nominal
permeate capacity is achieved.
1
2
3
4
5
6
7
8
9
10
11
12
13
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
12
Pressure switch
maximum pressure
RO1CP3
Prevents the system's operating pressure from exceeding
16 bar.
Membrane
RO1B1
Reverse osmosis membrane to generate the permeate.
Flow sensor permeate
RO1CF3
Via pulse signal at the control unit.
Sampling valve
permeate
RO1H5
Allows manual quality determination via sampling valve.
Conductivity
measurement
RO1CQ1
Conductivity sensor according to the 2-electrode principle (tem-
perature-compensated (RO1CT1)) for the continuous measure-
ment of the permeate conductivity. The measuring results are in-
dicated in the control unit.
Fig. C-3: Reverse osmosis system GENO-OSMO-X hydro module
for feed water
14
15
16
17
18
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
13
Fig. C-4: Reverse osmosis system GENO
-
OSMO-X hydro module
for concentrate
Fig. C-5: Reverse osmosis system GENO
-
OSMO-X hydro module for permeate
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
14
Fig. C-6: Reverse osmosis system GENO-OSMO-X 3000 with fine filter,
hydraulic connections, membrane and high-pressure pump
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
15
3 | Technical specifications
Table C-1: Technical specifications Reverse osmosis system GENO-OSMO-X
200 400 800 1200 1600 2200 3000
Connection data
Nominal connection diameter (male thread)
of feed water inlet 1“ 1“ 1“ 1“ 1“ 1 ¼“ 1 ¼“
Nominal connection diameter (male thread)
of permeate outlet 1“ 1“ 1“ 1“ 1“ 1“ 1“
Nominal connection diameter (male thread)
of concentrate outlet 1“ 1“ 1“ 1“ 1“ 1“ 1“
Min. drain connection
Without optional AVRO DN 50 DN 50 DN 50 DN 50 DN 50 DN 50 DN 50
With optional AVRO DN 50 DN 50 DN 50 DN 100 DN 100 - -
Power supply [V/Hz] 3/N/PE, 400 V/50...60 Hz
Min. power outlet provided on site 5.5 kW / C 20 A / 2.5 mm²
Protection/protection class IP 54/
Power input in case of unpressurised delivery of the permeate into a tank at a switching frequency of the frequency
converter of 8 kHz and an inlet pressure of 4 bar in the feed water
Recovery of 80 % [kW] 0.53 0.87 0.94 1.40 1.74 2.10 2.30
Recovery of 50 % [kW] 0.53 0.88 0.94 1.30 1.60 - -
Power input if the permeate is delivered directly to the consumers with a supply pressure of 3.8 bar at a switching
frequency of the frequency converter of 8 kHz and an inlet pressure of 4 bar in the feed water.
Recovery of 80 % [kW] 0.86 1.44 1.60 2.00 2.31 2.30 2.80
Recovery of 50 % [kW] 0.81 1.20 1.41 1.90 2.11 - -
Performance data
Permeate capacity at a
Feed water temperature of 10 °C [l/h] 170 340 680 1020 1360 1870 2550
Feed water temperature of 15 °C [l/h] 200 400 800 1200 1600 2200 3000
Feed water temperature of 15 °C [m³/d] 4.8 9.6 19.2 28.8 38.4 52.8 72.0
Min. inlet flow pressure of feed water [bar] 2.5
Min. outlet pressure of permeate [bar] 0.5
Nominal pressure PN 16
Salt rejection 95 – 99 %
Total salt concentration in the feed wa-
ter as NaCl, max.
[ppm] 1000
Recovery min./max. [%] 50-80 (adjustable) 65-80 (adjustable)
Volume flow concentrate to drain at a
recovery of 80%. (at 15°C) [l/h] 50 100 200 300 400 550 750
Feed water volume flow (15 °C)
drain at a recovery of 80%. [l/h] 250 500 1000 1500 2000 2750 3750
Filling volumes and consumption data
Number of modules (size 4") [pcs.] ½ 1 2 3 4 6 8
Dimensions and weights
System width [mm] 900 900 1035 1035 1170 1170 1170
System height [mm] 1700 1700 1700 1700 1700 1700 1700
System depth [mm] 675 675 675 675 675 675 675
Room height/installation height, min. [mm] 1800 1800 1800 1800 1800 1800 1800
Operating weight, approx. [kg] 100 115 145 170 195 240 290
General
Feed water temperature, min./max. [°C] 10/30
1)
Ambient temperature, min./max. [°C] 5/35
Order no. 750 200 750 210 750 220 750 230 750 240 750 250 750 260
1)
For temperatures of feed water > 20 °C a separate configuration of the system is required.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
16
4 | Appropriate application
The reserve osmosis system is designed for the demineralisa-
tion of drinking water according to the German Drinking Water
Ordinance (TrinkwV). The generated water is primarily used for
industrial applications.
A corresponding pre-treatment is required and the application
limits (paragraph 5) must be adhered to.
Note: In case of water that does not comply with the stipulations
of the German Drinking Water Ordinance (TrinkwV), a water
analysis is required beforehand.
The continuous permeate capacity is subject to the temperature
and was defined at 15°C. The permeate capacity decreases by
up to 3 % per degree centigrade of the feed water temperature .
Note: This reverse osmosis system adjusts the permeate capac-
ity automatically subject to the temperature. The recovery (con-
centrate to drain) as well as the concentrate recirculation are
adapted to the modified permeate capacity.
The system is adjusted to the permeate requirements to be ex-
pected at the installation site, it is not suitable for major deviations.
The system may only be operated if all components are installed
properly. Safety devices and equipment must NEVER be re-
moved, bridged or tampered with.
Appropriate application of the device also implies that the infor-
mation contained in this operation manual and all safety guide-
lines applying at the installation site be observed. Furthermore,
the maintenance and inspection intervals have to be observed.
4.1 System idle time
If the system is out of operation for more than 14 days, it must
be preserved by Grünbeck's technical customer service/author-
ised service company. The maximum time, the system can re-
main in the preserved condition is 6 months.
In case the down time is longer, the system must be preserved
again in regular intervals by Grünbeck's technical customer ser-
vice/authorised service company. Prior to resuming operation,
the preserving agent must be flushed from the system.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
17
5 | Application limits
For the application of the reverse osmosis system, the limit val-
ues stipulated in the German Drinking Water Ordinance repre-
sent the upper limits for the admissible substances contained in
the water.
Total hardness < 0.1 °dH1)
(0.18 °f; 0.018 mmol/l)
Free chlorine not detectable
Iron < 0.10 mg/l
Manganese < 0.05 mg/l
Silicate < 15 mg/l
Chlorine dioxide not detectable
Turbidity < 1 FTU
Colloid index (SDI) < 3
pH range 3-9
1) Different application limits for the total hardness do apply for
the optional pre-treatment AVRO resp. antiscalant.
Note: The permeate originating from the reverse osmosis sys-
tem is not potable but requires additional treatment (blending,
hardening) if it is to be used as drinking water.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
18
6 | Scope of supply
6.1 Standard equipment Control unit with 4.3" graphics touch panel to indicate the op-
erating state and system values. Voltage-free contacts to re-
lay advance warnings and safety shut-downs. Digital input for
priority permeate production in times when electricity tariffs
are low (smart metering). Fully automatic monitoring and con-
trol of the system parameters permeate flow, monitoring of
the permeate conductivity by means of limit value default set-
tings in the control unit, recovery, concentrate recirculation
and pump frequency (subject to the water temperature). Re-
cording of measured data on integrated SD card. Possibility
to interconnect systems installed upstream or downstream
(water softener, dosing system, permeate tank, pressure
booster) and to operate them by remote control.
Power distribution with mains switch and automatic circuit
breakers as feeding point for power supply provided by oth-
ers on site.
High-pressure centrifugal pump made of stainless steel
1.4401 to supply the reverse osmosis membrane(s).
Ultra-low pressure reverse osmosis membrane(s), installed in
pressure pipe made of high-strength PE.
Three-part hydro module made of red bronze, chemically
nickel-plated, featuring pressure gauges, adjusting resp. so-
lenoid valves and sampling valves. Flow sensors integrated
in the hydro module, volume measurement of the system
flows permeate, concentrate and concentrate recirculation.
The permeate hydro module features a conductivity measur-
ing cell (temperature-compensated).
Pipework between pump and reverse osmosis membrane
made of high-pressure resistant PE pipes and PP compres-
sion fittings.
High-quality system rack made of anodised aluminium to
house all system components.
A ventilation device to be mounted onto the concentrate pipe
provided by others on site.
Fine filter incl. pressure reducer, completely preassembled in
system inlet.
Installation and operation manual.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76

Grunbeck GENO-OSMO-X Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI