LG LRUV1008TS0.AWGAIDA Installation guide

Type
Installation guide

This manual is also suitable for

System
Outdoor Unit
INSTALLATION MANUAL
LG
MODELS: LRUV Series
LRUN Series
website http://www.lgservice.com
e-mail http://www.lgeservice.com/techsup.html
IMPORTANT
• Please read this installation manual completely before
installing the product.
• Installation work must be performed in accordance with
the national wiring standards by authorized personnel
only.
• Please retain this installation manual for future reference
after reading it thoroughly.
2 Outdoor Unit
LRUN Series Outdoor Unit Installation Manual
TABLE OF CONTENTS
Safety Precautions.........................3
Installation Process.....................10
Outdoor Units Information..........11
Select the Best Location.............16
Installation Space ........................17
Lifting method..............................21
Installation....................................22
Refrigerant piping installation....26
Electrical Wiring...........................55
Test Run........................................79
Installation Manual 3
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must
be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
Be sure not to do.
Be sure to follow the instruction.
Installation
Have all electric work done by a licensed
electrician according to "Electric Facility
Engineering Standard" and "Interior Wire
Regulations" and the instructions given in
this manual and always use a special circuit.
• If the power source capacity is inadequate or
electric work is performed improperly, electric
shock and fire may result.
Ask the dealer or an authorized technician to
install the air conditioner.
• Improper installation by the user may result in
water leakage, electric shock, or fire.
Always ground the product.
• There is risk of fire or electric shock.
Always intstall a dedicated circuit and breaker.
• Improper wiring or installation may cause fire or
electric shock.
4 Outdoor Unit
Safety Precautions
For re-installation of the installed product,
always contact a dealer or an Authorized
Service Center.
• There is risk of fire, electric shock, explosion, or
injury.
Do not install, remove, or re-install the unit
by yourself (customer).
• There is risk of fire, electric shock, explosion, or
injury.
Do not store or use flammable gas or
combustibles near the air conditioner.
• There is risk of fire or failure of product.
Use the correctly rated breaker or fuse.
• There is risk of fire or electric shock.
Prepare for typhoons and other strong winds
and earthquakes and install the unit at the
specified place.
• Improper installation may cause the unit to top-
ple and result in injury.
Do not install the product on a defective
installation stand.
• It may cause injury, accident, or damage to the
product.
When installing and moving the air condition-
er to another site, do not charge it with a
differnet refrigerant from the refrigerant
specified on the unit.
• If a differnet refrigerant or air is mixed with the
original refrigerant, the refrigerant cycle may
malfunction and the unit may be gamaged.
Do not reconstruct ot change the settings of
the protection devices.
• If the pressure switch, thermal switch, or other
protection device is shorted and operated
forcibly, or parts other than
those specified by LGE are
used, fire or explosion may
result.
Gasolin
Installation Manual 5
Safety Precautions
Ventilate before operating air conditioner
when gas goes out.
• It may cause explosion, fire, and burn.
Securely install the cover of control box and
the panel.
• If the cover and panel are installed securely, dust
or water may enter the outdoor unit and fire or
electric shock may result.
If the air conditioner is installed in a small room, measures must be taken to prevent the
refrigerant concentration from exceeding the safety limit when the refrigerant leaks.
• Consult the dealer regarding the appropriate measures to prevent the safety limit from being exceed-
ed. Should the refrigerant leak and cause the safety limit to be exceeded, harzards due to lack of oxy-
gen in the room could result.
Operation
Do not damage or use an unspecified power
cord.
• There is risk of fire, electric shock, explosion, or
injury.
Use a dedicated outlet for this appliance.
• There is risk of fire or electrical shock.
Be cautious that water could not enter the
product.
• There is risk of fire, electric shock, or product
damage.
Do not touch the power switch with wet
hands.
• There is risk of fire, electric shock, explosion, or
injury.
6 Outdoor Unit
Safety Precautions
When the product is soaked (flooded or
submerged), contact an Authorized Service
Center.
• There is risk of fire or electric shock.
Be cautious not to touch the sharp edges
when installing.
• It may cause injury.
Take care to ensure that nobody could step
on or fall onto the outdoor unit.
• This could result in personal injury and product
damage.
Do not open the inlet grill of the product dur-
ing operation. (Do not touch the electrostatic
filter, if the unit is so equipped.)
• There is risk of physical injury, electric shock, or
product failure.
Installation
Always check for gas (refrigerant) leakage
after installation or repair of product.
• Low refrigerant levels may cause failure of
product.
Do not install the product where the noise or
hot air from the outdoor unit could damage
the neighborhoods.
• It may cause a problem for your neighbors.
Keep level even when installing the product.
• To avoid vibration or water leakage.
Do not install the unit where combustible gas
may leak.
• If the gas leaks and accumulates around the
unit, an explosion may result.
90˚
Gasolin
Installation Manual 7
Safety Precautions
Use power cables of sufficient current
carrying capacity and rating.
Cables that are too small may leak, generate
heat, and cause a fire.
Do not use the product for special purposes,
such as preserving foods, works of art, etc. It
is a consumer air conditioner, not a precision
refrigeration system.
There is risk of damage or loss of property.
Keep the unit away from children. The heat
exchanger is very sharp.
It can cause the injury, such as cutting the finger.
Also the gamaged fin may result in degradation
of capacity.
When installting the unit in a hospital, com-
munication station, or similar place, provide
surfficient protection against noise.
The inverter equipment, private power generator,
high-frequency medical equipment, or radio com-
munication equipment may cause the air condition-
er to operate erroneously, or fail to operate. On the
other hand, the air conditioner may affect such
equipment by creating noise that disturbs medical
treatment or image broadcasting.
Do not install the product where it will be exposed to sea wind (salt spray) directly.
It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins,
could cause product malfunction or inefficient operation.
8 Outdoor Unit
Safety Precautions
Operation
Do not use the air conditioner in special
environments.
Oil, steam, sulfuric smoke, etc. can significantly
reduce the performance of the air conditioner or
damage its parts.
Do not block the inlet or outlet.
It may cause failure of appliance or accident.
Make the connections securely so that the
outside force of the cable is not applied to
the terminals.
Inadequate connection and fastening may gen-
erate heat and cause a fire.
Be sure the installation area does not deteri-
orate with age.
If the base collapses, the air conditioner could
fall with it, causing property damage, product
failure, and personal injury.
Install and insulate the drain hose to ensure that water is drained away properly based on the
installation manual.
A bad connection may cause water leakage.
Be very careful about product transportation.
Only one person should not carry the product if it weighs more
than 20 kg.
Some products use PP bands dor packaging. Do not use any PP
bands for a means of transportation. It is dangerous.
Do not touch the heat exchanger fins. Doing so may cut your fin-
gers.
When transporting the Outdoor Unit, suspending it at the specified
positions on the unit base. Also support the Outdoor Unit at four
points so that it cannot slip sideways.
Installation Manual 9
Safety Precautions
Safely dispose of the packing materials.
Packing materials, such as mails and other metal or
wooden parts, may cause stabs or other injuries.
Tear apart and throw away plastic packaging bags
so that children will not play with them. If children
play with a plastic bag which was
not torn apart, they face the
risk of suffocation.
Turn on the power at least 2 hours before
starting operation.(In case of outdoor
temperature 5°C below)
Starting operation immediately after turning on
the main power switch can result in severe
damage to internal parts. Keep the power switch
turned on during the operational season.
Do not touch any of the refrigerant piping
during and after operation.
It can cause a burn or frostbite.
Do not operate the air conditioner with the
panels and guards removed.
Rotating, hot, or high-voltage parts can cause
injuries.
Do not directly turn off the main power
switch after stopping operation.
Wait at least more than 5 minutes before turning
off the main power switch.
Otherwise it may result in
water leakage or other
problems.
Auto-addressing should be done in condition of
connecting the power of all indoor and outdoour
units. Auto-addressing should also be done in
case of changing the Indoor Unit board(PCB).
Use a firm stool or ladder when cleaning or
maintaining the air conditioner.
Be careful and avoid personal injury.
Do not insert hands or other objects through
the air inlet or outlet while the air conditioner
is plugged in.
There are sharp and moving parts that could
cause personal injury.
10 Outdoor Unit
Installation
Installation Process
The foundation must be level
Outdoor unit foundation work
Avoid short circuits and ensure
sufficient space is allowed for service
Installation of outdoor unit
Refer to automatic addressing flowchart
Automatic addressing of indoor unit
In the final check for 24hours at 2.94 MPa(30.0 kg/cm
2
) there must be no drop in pressure.
All tight test
Multiple core cable must not
be used.(suitable cable should
be selected)
Electrical work
(connection circuits and drive circuits)
Make sure no gaps are left where
the insulating materials are joined
Heat insulation work
Make sure airflow is sufficient
Duct work
Adjust to downward gradient
Drain pipe work
Special attention to dryness,
cleanness and tightness
Refrigerant piping work
Check model name to make
sure the fitting is made correctly
Installation of indoor unit
Take account of gradient
of drain piping
Sleeve and insert work
Make relationship between outdoor, indoor, remote controller, And option connections clear.
(Prepare control circuit diagram)
Preparation of contract drawings
Indicate clearly who is to be responsible for switch settings
Determination of division work
The vacuum pump used must have a capacity of reaching at least 0.5 torr, 3hours
Vacuum drying
Recharge correctly as calculated in this manual. and record the amount of additive refrigerant
Additional charge of refrigerant
Make sure there are no gaps left between the facing materials used on the ceiling
Fit facing panels
Run each indoor unit in turn to make sure the pipe work has been fitted correctly
Test run adjustment
Explain the use of the system as clearly as possible to your customer and make sure all relevant documentation is in order
Transfer to customer with explanation
The above list indicates the order in which the individual work operations are normally carried out but this order
may be varied where local conditions warrants such change.
Installation Manual 11
Outdoor Units Information
Outdoor Units Information
CAUTION: A ratio of the connectable Indoor Units with the Outdoor Unit : within 50 ~ 130%
Power Supply: Outdoor Unit (3Ø, 380 ~ 415V, 50Hz)
Cooling Only
Unit
System(HP)
Model
Product Charge kg
CF(Correction Factor) kg
Max. Connectable No. of Indoor Units
Net Weight kg(lbs)
Dimensions (W x H x D)
mm(inch)
Pipe Connections
Liquid Pipes(mm(inch))
Gas Pipes(mm(inch))
1 Outdoor Unit(Half size)
1 Outdoor Unit
568101214
LRUV508T0 LRUV608T0 LRUV808T0 LRUV1008T0 LRUV1208T0 LRUV1408T0
5 5 10 10 10 10
1 1 -1 -1 -1 -1
6 8 16 16 16 16
150(330.7) 150(330.7) 300(661.4) 300(661.4) 300(661.4) 300(661.4)
806 x 1520 x 730 806 x 1520 x 730 1280 x 1520 x 730 1280 x 1520 x 730 1280 x 1520 x 730 1280 x 1520 x 730
(31.7 x 59.84 x 28.74) (31.7 x 59.84 x 28.74) (50.40 x 59.84 x 28.74) (50.40 x 59.84 x 28.74) (50.40 x 59.84 x 28.74) (50.40 x 59.84 x 28.74)
Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2)
Ø19.05(3/4) Ø19.05(3/4) Ø28.58(9/8) Ø28.58(9/8) Ø28.58(9/8) Ø28.58(9/8)
Unit
System(HP)
Model
Product Charge kg
CF(Correction Factor) kg
Max. Connectable No. of Indoor Units
Net Weight kg(lbs)
Dimensions (W x H x D)
mm(inch)
Pipe Connections
Liquid Pipes(mm(inch))
Gas Pipes(mm(inch))
2 Outdoor Units
3 Outdoor Units
16 18 20 22 24 26
LRUV1608TS0 LRUV1808TS0 LRUV2008TS0 LRUV2208TS0 LRUV2408TS0 LRUV2608TR0
LRUV808TS0 LRUV1008TS0 LRUV1008TS0 LRUV1208TS0 LRUV1208TS0 LRUV1008TR0
LRUC808TS0 LRUC808TS0 LRUC1008TS0 LRUC1008TS0 LRUC1208TS0 LRUC808TR0
LRUC808TR0
10 x 2 10 x 2 10 x 2 10 x 2 10 x 2 10 x 3
-2 -2 -2 -2 -2 0
20 20 20 22 24 32
300(661.4) x 2 300(661.4) x 2 300(661.4) x 2 300(661.4) x 2 300(661.4) x 2 300(661.4) x 3
(1280 x 1520 x 730) x 2 (1280 x 1520 x 730) x 2 (1280 x 1520 x 730) x 2 (1280 x 1520 x 730) x 2 (1280 x 1520 x 730) x 2 (1280 x 1520 x 730) x 3
((50.40 x 59.84 x 28.74) x 2) ((50.40 x 59.84 x 28.74) x 2) ((50.40 x 59.84 x 28.74) x 2) ((50.40 x 59.84 x 28.74) x 2) ((50.40 x 59.84 x 28.74) x 2) ((50.40 x 59.84 x 28.74) x 3)
Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø22.2(7/8)
Ø38.1(1
1
/2) Ø38.1(1
1
/2) Ø38.1(1
1
/2) Ø38.1(1
1
/2) Ø38.1(1
1
/2) Ø44.5(1
3
/4)
Unit
System(HP)
Model
Product Charge kg
CF(Correction Factor) kg
Max. Connectable No. of Indoor Units
Net Weight kg(lbs)
Dimensions (W x H x D)
mm(inch)
Pipe Connections
Liquid Pipes(mm(inch))
Gas Pipes(mm(inch))
3 Outdoor Units
28 30 32 34 36 38 40
LRUV2808TR0 LRUV3008TR0 LRUV3208TR0 LRUV3408TR0 LRUV3608TR0 LRUV3808TR0 LRUV4008TR0
LRUV808TR0 LRUV1008TR0 LRUV1208TR0 LRUV1408TR0 LRUV1208TR0 LRUV1408TR0 LRUV1608TR0
LRUC1008TR0 LRUC1008TR0 LRUC1008TR0 LRUC1008TR0 LRUC1208TR0 LRUC1208TR0 LRUC1208TR0
LRUC1008TR0 LRUC1008TR0 LRUC1008TR0 LRUC1008TR0 LRUC1208TR0 LRUC1208TR0 LRUC1208TR0
10 x 3 10 x 3 10 x 3 10 x 3 10 x 3 10 x 3 10 x 3
0001122
32 32 32 34 36 38 40
300(661.4) x 3 300(661.4) x 3 300(661.4) x 3 300(661.4) x 3 300(661.4) x 3 300(661.4) x 3 300(661.4) x 3
(1280 x 1520 x 730) x 3 (1280 x 1520 x 730) x 3 (1280 x 1520 x 730) x 3 (1280 x 1520 x 730) x 3 (1280 x 1520 x 730) x 3 (1280 x 1520 x 730) x 3 (1280 x 1520 x 730) x 3
((50.40 x 59.84 x 28.74) x 3) ((50.40 x 59.84 x 28.74) x 3) ((50.40 x 59.84 x 28.74) x 3) ((50.40 x 59.84 x 28.74) x 3) ((50.40 x 59.84 x 28.74) x 3) ((50.40 x 59.84 x 28.74) x 3) ((50.40 x 59.84 x 28.74) x 3)
Ø22.2(7/8) Ø22.2(7/8) Ø22.2(7/8) Ø22.2(7/8) Ø22.2(7/8) Ø22.2(7/8) Ø22.2(7/8)
Ø44.5(1
3
/4) Ø44.5(1
3
/4) Ø44.5(1
3
/4) Ø44.5(1
3
/4) Ø44.5(1
3
/4) Ø44.5(1
3
/4) Ø44.5(1
3
/4)
12 Outdoor Unit
Outdoor Units Information
Heat Pump
Unit
System(HP)
Model
Product Charge kg
CF(Correction Factor) kg
Max. Connectable No. of Indoor Units
Net Weight kg(lbs)
Dimensions (W x H x D)
mm(inch)
Pipe Connections
Liquid Pipes(mm(inch))
Gas Pipes(mm(inch))
1 Outdoor Unit(Half size)
1 Outdoor Unit
568101214
LRUN508T0 LRUN608T0 LRUN808T0 LRUN1008T0 LRUN1208T0 LRUN1408T0
5 5 10 10 10 10
1 1 -1 -1 -1 -1
6 8 16 16 16 16
150(330.7) 150(330.7) 300(661.4) 300(661.4) 300(661.4) 300(661.4)
806 x 1520 x 730 806 x 1520 x 730 1280 x 1520 x 730 1280 x 1520 x 730 1280 x 1520 x 730 1280 x 1520 x 730
(
31.7 x 59.84 x 28.74) (31.7 x 59.84 x 28.74) (50.40 x 59.84 x 28.74) (50.40 x 59.84 x 28.74) (50.40 x 59.84 x 28.74) (50.40 x 59.84 x 28.74)
Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2)
Ø19.05(3/4) Ø19.05(3/4) Ø28.58(9/8) Ø28.58(9/8) Ø28.58(9/8) Ø28.58(9/8)
Unit
System(HP)
Model
Product Charge kg
CF(Correction Factor) kg
Max. Connectable No. of Indoor Units
Net Weight kg(lbs)
Dimensions (W x H x D)
mm(inch)
Pipe Connections
Liquid Pipes(mm(inch))
Gas Pipes(mm(inch))
2 Outdoor Units
3 Outdoor Units
16 18 20 22 24 26
LRUN1608TS0 LRUN1808TS0 LRUN2008TS0 LRUN2208TS0 LRUN2408TS0 LRUN2608TR0
LRUN808TS0 LRUN1008TS0 LRUN1008TS0 LRUN1208TS0 LRUN1208TS0 LRUN1008TR0
LRUH808TS0 LRUH808TS0 LRUH1008TS0 LRUH1008TS0 LRUH1208TS0 LRUH808TR0
LRUH808TR0
10 x 2 10 x 2 10 x 2 10 x 2 10 x 2 10 x 3
-2 -2 -2 -2 -2 0
20 20 20 22 24 32
300(661.4) x 2 300(661.4) x 2 300(661.4) x 2 300(661.4) x 2 300(661.4) x 2 300(661.4) x 3
(1280 x 1520 x 730) x 2 (1280 x 1520 x 730) x 2 (1280 x 1520 x 730) x 2 (1280 x 1520 x 730) x 2 (1280 x 1520 x 730) x 2 (1280 x 1520 x 730) x 3
((50.40 x 59.84 x 28.74) x 2) ((50.40 x 59.84 x 28.74) x 2) ((50.40 x 59.84 x 28.74) x 2) ((50.40 x 59.84 x 28.74) x 2) ((50.40 x 59.84 x 28.74) x 2) ((50.40 x 59.84 x 28.74) x 3)
Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø22.2(7/8)
Ø38.1(1
1
/2) Ø38.1(1
1
/2) Ø38.1(1
1
/2) Ø38.1(1
1
/2) Ø38.1(1
1
/2) Ø44.5(1
3
/4)
Unit
System(HP)
Model
Product Charge kg
CF(Correction Factor) kg
Max. Connectable No. of Indoor Units
Net Weight kg(lbs)
Dimensions (W x H x D)
mm(inch)
Pipe Connections
Liquid Pipes(mm(inch))
Gas Pipes(mm(inch))
3 Outdoor Units
28 30 32 34 36 38 40
LRUN2808TR0 LRUN3008TR0 LRUN3208TR0 LRUN3408TR0 LRUN3608TR0 LRUN3808TR0 LRUN4008TR0
LRUN808TR0 LRUN1008TR0 LRUN1208TR0 LRUN1408TR0 LRUN1208TR0 LRUN1408TR0 LRUN1608TR0
LRUH1008TR0 LRUH1008TR0 LRUH1008TR0 LRUH1008TR0 LRUH1208TR0 LRUH1208TR0 LRUH1208TR0
LRUH1008TR0 LRUH1008TR0 LRUH1008TR0 LRUH1008TR0 LRUH1208TR0 LRUH1208TR0 LRUH1208TR0
10 x 3 10 x 3 10 x 3 10 x 3 10 x 3 10 x 3 10 x 3
0001122
32 32 32 34 36 38 40
300(661.4) x 3 300(661.4) x 3 300(661.4) x 3 300(661.4) x 3 300(661.4) x 3 300(661.4) x 3 300(661.4) x 3
(1280 x 1520 x 730) x 3 (1280 x 1520 x 730) x 3 (1280 x 1520 x 730) x 3 (1280 x 1520 x 730) x 3 (1280 x 1520 x 730) x 3 (1280 x 1520 x 730) x 3 (1280 x 1520 x 730) x 3
((50.40 x 59.84 x 28.74) x 3) ((50.40 x 59.84 x 28.74) x 3) ((50.40 x 59.84 x 28.74) x 3) ((50.40 x 59.84 x 28.74) x 3) ((50.40 x 59.84 x 28.74) x 3) ((50.40 x 59.84 x 28.74) x 3) ((50.40 x 59.84 x 28.74) x 3)
Ø22.2(7/8) Ø22.2(7/8) Ø22.2(7/8) Ø22.2(7/8) Ø22.2(7/8) Ø22.2(7/8) Ø22.2(7/8)
Ø44.5(1
3
/4) Ø44.5(1
3
/4) Ø44.5(1
3
/4) Ø44.5(1
3
/4) Ø44.5(1
3
/4) Ø44.5(1
3
/4) Ø44.5(1
3
/4)
Installation Manual 13
Outdoor Units Information
Power Supply: Outdoor Unit (3Ø, 380V, 60Hz)
Cooling Only
Unit
System(HP)
Model
Product Charge kg
CF(Correction Factor) kg
Max. Connectable No. of Indoor Units
Net Weight kg(lbs)
Dimensions (W x H x D)
mm(inch)
Pipe Connections
Liquid Pipes(mm(inch))
Gas Pipes(mm(inch))
1 Outdoor Unit(Half size)
1 Outdoor Unit
568101214
LRUV509T0 LRUV609T0 LRUV809T0 LRUV1009T0 LRUV1209T0 LRUV1409T0
5 5 10 10 10 10
1 1 -1 -1 -1 -1
6 8 16 16 16 16
150(330.7) 150(330.7) 300(661.4) 300(661.4) 300(661.4) 300(661.4)
806 x 1520 x 730 806 x 1520 x 730 1280 x 1520 x 730 1280 x 1520 x 730 1280 x 1520 x 730 1280 x 1520 x 730
(31.7 x 59.84 x 28.74) (31.7 x 59.84 x 28.74) (50.40 x 59.84 x 28.74) (50.40 x 59.84 x 28.74) (50.40 x 59.84 x 28.74) (50.40 x 59.84 x 28.74)
Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2)
Ø19.05(3/4) Ø19.05(3/4) Ø28.58(9/8) Ø28.58(9/8) Ø28.58(9/8) Ø28.58(9/8)
Unit
System(HP)
Model
Product Charge kg
CF(Correction Factor) kg
Max. Connectable No. of Indoor Units
Net Weight kg(lbs)
Dimensions (W x H x D)
mm(inch)
Pipe Connections
Liquid Pipes(mm(inch))
Gas Pipes(mm(inch))
2 Outdoor Units
16 18 20 22 24 26
LRUV1609TS0 LRUV1809TS0 LRUV2009TS0 LRUV2209TS0 LRUV2409TS0 LRUV2609TS0
LRUV809TS0 LRUV1009TS0 LRUV1009TS0 LRUV1209TS0 LRUV1209TS0 LRUV1409TS0
LRUC809TS0 LRUC809TS0 LRUC1009TS0 LRUC1009TS0 LRUC1209TS0 LRUC1209TS0
10 x 2 10 x 2 10 x 2 10 x 2 10 x 2 10 x 2
-2 -2 -2 -2 -2 -1
20 20 20 22 24 26
300(661.4) x 2 300(661.4) x 2 300(661.4) x 2 300(661.4) x 2 300(661.4) x 2 300(661.4) x 2
(1280 x 1520 x 730) x 2 (1280 x 1520 x 730) x 2 (1280 x 1520 x 730) x 2 (1280 x 1520 x 730) x 2 (1280 x 1520 x 730) x 2 (1280 x 1520 x 730) x 2)
((50.40 x 59.84 x 28.74) x 2) ((50.40 x 59.84 x 28.74) x 2) ((50.40 x 59.84 x 28.74) x 2) ((50.40 x 59.84 x 28.74) x 2) ((50.40 x 59.84 x 28.74) x 2) ((50.40 x 59.84 x 28.74) x 2)
Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4)
Ø38.1(1
1
/2) Ø38.1(1
1
/2) Ø38.1(1
1
/2) Ø38.1(1
1
/2) Ø38.1(1
1
/2) Ø38.1(1
1
/2)
Unit
System(HP)
Model
Product Charge kg
CF(Correction Factor) kg
Max. Connectable No. of Indoor Units
Net Weight kg(lbs)
Dimensions (W x H x D)
mm(inch)
Pipe Connections
Liquid Pipes(mm(inch))
Gas Pipes(mm(inch))
3 Outdoor Units
28 30 32 34 36 38 40
LRUV2809TR0 LRUV3009TR0 LRUV3209TR0 LRUV3409TR0 LRUV3609TR0 LRUV3809TR0 LRUV4008TR0
LRUV809TR0 LRUV1009TR0 LRUV1209TR0 LRUV1409TR0 LRUV1209TR0 LRUV1409TR0 LRUV1609TR0
LRUC1009TR0 LRUC1009TR0 LRUC1009TR0 LRUC1009TR0 LRUC1209TR0 LRUC1209TR0 LRUC1209TR0
LRUC1009TR0 LRUC1009TR0 LRUC1009TR0 LRUC1009TR0 LRUC1209TR0 LRUC1209TR0 LRUC1209TR0
10 x 3 10 x 3 10 x 3 10 x 3 10 x 3 10 x 3 10 x 3
0001122
32 32 32 34 36 38 40
300(661.4) x 3 300(661.4) x 3 300(661.4) x 3 300(661.4) x 3 300(661.4) x 3 300(661.4) x 3 300(661.4) x 3
(1280 x 1520 x 730) x 3 (1280 x 1520 x 730) x 3 (1280 x 1520 x 730) x 3 (1280 x 1520 x 730) x 3 (1280 x 1520 x 730) x 3 (1280 x 1520 x 730) x 3 (1280 x 1520 x 730) x 3
((50.40 x 59.84 x 28.74) x 3) ((50.40 x 59.84 x 28.74) x 3) ((50.40 x 59.84 x 28.74) x 3) ((50.40 x 59.84 x 28.74) x 3) ((50.40 x 59.84 x 28.74) x 3) ((50.40 x 59.84 x 28.74) x 3) ((50.40 x 59.84 x 28.74) x 3)
Ø22.2(7/8) Ø22.2(7/8) Ø22.2(7/8) Ø22.2(7/8) Ø22.2(7/8) Ø22.2(7/8) Ø22.2(7/8)
Ø
44.5(1
3
/4)
Ø
44.5(1
3
/4)
Ø
44.5(1
3
/4)
Ø
44.5(1
3
/4)
Ø
44.5(1
3
/4)
Ø
44.5(1
3
/4)
Ø
44.5(1
3
/4)
14 Outdoor Unit
Outdoor Units Information
Heat Pump
Unit
System(HP)
Model
Product Charge kg
CF(Correction Factor) kg
Max. Connectable No. of Indoor Units
Net Weight kg(lbs)
Dimensions (W x H x D)
mm(inch)
Pipe Connections
Liquid Pipes(mm(inch))
Gas Pipes(mm(inch))
1 Outdoor Unit(Half size)
1 Outdoor Unit
568101214
LRUN509T0 LRUN609T0 LRUN809T0 LRUN1009T0 LRUN1209T0 LRUN1409T0
5 5 10 10 10 10
1 1 -1 -1 -1 -1
6 8 16 16 16 16
150(330.7) 150(330.7) 300(661.4) 300(661.4) 300(661.4) 300(661.4)
806 x 1520 x 730 806 x 1520 x 730 1280 x 1520 x 730 1280 x 1520 x 730 1280 x 1520 x 730 1280 x 1520 x 730
(31.7 x 59.84 x 28.74) (31.7 x 59.84 x 28.74) (50.40 x 59.84 x 28.74) (50.40 x 59.84 x 28.74) (50.40 x 59.84 x 28.74) (50.40 x 59.84 x 28.74
Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2)
Ø19.05(3/4) Ø19.05(3/4) Ø28.58(9/8) Ø28.58(9/8) Ø28.58(9/8) Ø28.58(9/8)
Unit
System(HP)
Model
Product Charge kg
CF(Correction Factor) kg
Max. Connectable No. of Indoor Units
Net Weight kg(lbs)
Dimensions (W x H x D)
mm(inch)
Pipe Connections
Liquid Pipes(mm(inch))
Gas Pipes(mm(inch))
2 Outdoor Units
16 18 20 22 24 26
LRUN1609TS0 LRUN1809TS0 LRUN2009TS0 LRUN2209TS0 LRUN2409TS0 LRUN2609TS0
LRUN809TS0 LRUN1009TS0 LRUN1009TS0 LRUN1209TS0 LRUN1209TS0 LRUN1409TS0
LRUH809TS0 LRUH809TS0 LRUH1009TS0 LRUH1009TS0 LRUH1209TS0 LRUH1209TS0
10 x 2 10 x 2 10 x 2 10 x 2 10 x 2 10 x 2
-2 -2 -2 -2 -2 -1
20 20 20 22 24 26
300(661.4) x 2 300(661.4) x 2 300(661.4) x 2 300(661.4) x 2 300(661.4) x 2 300(661.4) x 2
(1280 x 1520 x 730) x 2 (1280 x 1520 x 730) x 2 (1280 x 1520 x 730) x 2 (1280 x 1520 x 730)) x 2 (1280 x 1520 x 730) x 2 (1280 x 1520 x 730) x 2
((50.40 x 59.84 x 28.74) x 2) ((50.40 x 59.84 x 28.74) x 2) ((50.40 x 59.84 x 28.74) x 2) ((50.40 x 59.84 x 28.74) x 2) ((50.40 x 59.84 x 28.74) x 2) ((50.40 x 59.84 x 28.74) x 2)
Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4)
Ø38.1(1
1
/
2) Ø38.1(1
1
/
2) Ø38.1(1
1
/
2) Ø38.1(1
1
/
2) Ø38.1(1
1
/
2) Ø38.1(1
1
/
2)
Unit
System(HP)
Model
Product Charge kg
CF(Correction Factor) kg
Max. Connectable No. of Indoor Units
Net Weight kg(lbs)
Dimensions (W x H x D)
mm(inch)
Pipe Connections
Liquid Pipes(mm(inch))
Gas Pipes(mm(inch))
3 Outdoor Units
28 30 32 34 36 38 40
LRUN2809TR0 LRUN3009TR0 LRUN3209TR0 LRUN3409TR0 LRUN3609TR0 LRUN3809TR0 LRUN4009TR0
LRUN809TR0 LRUN1009TR0 LRUN1209TR0 LRUN1409TR0 LRUN1209TR0 LRUN1409TR0 LRUN1609TR0
LRUH1009TR0 LRUH1009TR0 LRUH1009TR0 LRUH1009TR0 LRUH1209TR0 LRUH1209TR0 LRUH1209TR0
LRUH1009TR0 LRUH1009TR0 LRUH1009TR0 LRUH1009TR0 LRUH1209TR0 LRUH1209TR0 LRUH1209TR0
10 x 3 10 x 3 10 x 3 10 x 3 10 x 3 10 x 3 10 x 3
0001122
32 32 32 34 36 38 40
300(661.4) x 3 300(661.4) x 3 300(661.4) x 3 300(661.4) x 3 300(661.4) x 3 300(661.4) x 3 300(661.4) x 3
(1280 x 1520 x 730) x 3 (1280 x 1520 x 730) x 3 (1280 x 1520 x 730) x 3 (1280 x 1520 x 730) x 3 (1280 x 1520 x 730) x 3 (1280 x 1520 x 730) x 3 (1280 x 1520 x 730) x 3
((50.40 x 59.84 x 28.74) x 3) ((50.40 x 59.84 x 28.74) x 3) ((50.40 x 59.84 x 28.74) x 3) ((50.40 x 59.84 x 28.74) x 3) ((50.40 x 59.84 x 28.74) x 3) ((50.40 x 59.84 x 28.74) x 3) ((50.40 x 59.84 x 28.74) x 3)
Ø22.2(7/8) Ø22.2(7/8) Ø22.2(7/8) Ø22.2(7/8) Ø22.2(7/8) Ø22.2(7/8) Ø22.2(7/8)
Ø
44.5(1
3
/4)
Ø
44.5(1
3
/4)
Ø
44.5(1
3
/4)
Ø
44.5(1
3
/4)
Ø
44.5(1
3
/4)
Ø
44.5(1
3
/4)
Ø
44.5(1
3
/4)
Installation Manual 15
Outdoor Units Information
Power Supply: Outdoor Unit (3Ø, 220V, 60Hz)
Cooling Only
Heat Pump
Unit
System(HP)
Model
Product Charge kg
CF(Correction Factor) kg
Max. Connectable No. of Indoor Units
Net Weight kg(lbs)
Dimensions (W x H x D)
mm(inch)
Pipe Connections
Liquid Pipes(mm(inch))
Gas Pipes(mm(inch))
1 Outdoor Unit(Half size)
1 Outdoor Unit
2 Outdoor Units 3 Outdoor Units
5 6 8 10122030
LRUV50BT0 LRUV60BT0 LRUV80BT0 LRUV100BT0 LRUV120BT0 LRUV200BTS0 LRUV300BTR0
LRUV100BTS0 LRUV100BTR0
LRUC100BTS0 LRUC100BTR0
LRUC100BTR0
5 5 10 10 10 10 x 2 10 x 3
1 1 -1 -1 -1 -2 0
6 8 16 16 16 20 32
150(330.7) 150(330.7) 300(661.4) 300(661.4) 300(661.4) 300(661.4) x 2 300(661.4) x 3
806 x 1520 x 730 806 x 1520 x 730 1280 x 1520 x 730 1280 x 1520 x 730 1280 x 1520 x 730
(1280 x 1520 x 730) x 2 (1280 x 1520 x 730) x 3
(31.7 x 59.84 x 28.74) (31.7 x 59.84 x 28.74) (50.40 x 59.84 x 28.74) (50.40 x 59.84 x 28.74) (50.40 x 59.84 x 28.74)
((50.40 x 59.84 x 28.74) x 2) ((50.40 x 59.84 x 28.74) x 3)
Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) Ø19.05(3/4) Ø22.2(7/8)
Ø19.05(3/4) Ø19.05(3/4) Ø28.58(9/8) Ø28.58(9/8) Ø28.58(9/8) Ø38.1(1
1
/2) Ø44.5(1
3
/4)
Unit
System(HP)
Model
Product Charge kg
CF(Correction Factor) kg
Max. Connectable No. of Indoor Units
Net Weight kg(lbs)
Dimensions (W x H x D)
mm(inch)
Pipe Connections
Liquid Pipes(mm(inch))
Gas Pipes(mm(inch))
1 Outdoor Unit(Half size)
1 Outdoor Unit
2 Outdoor Units 3 Outdoor Units
5 6 8 10122030
LRUN50BT0 LRUN60BT0 LRUN80BT0 LRUN100BT0 LRUN120BT0 LRUN200BTS0 LRUN300BTR0
LRUN100BTS0 LRUN100BTR0
LRUH100BTS0 LRUH100BTR0
LRUH100BTR0
5 5 10 10 10 10 x 2 10 x 3
1 1 -1 -1 -1 -2 0
6 8 16 16 16 20 32
150(330.7) 150(330.7) 300(661.4) 300(661.4) 300(661.4) 300(661.4) x 2 300(661.4) x 3
806 x 1520 x 730 806 x 1520 x 730 1280 x 1520 x 730 1280 x 1520 x 730 1280 x 1520 x 730 (1280 x 1520 x 730) x 2 (1280 x 1520 x 730) x 3
(31.7 x 59.84 x 28.74) (31.7 x 59.84 x 28.74) (50.40 x 59.84 x 28.74) (50.40 x 59.84 x 28.74) (50.40 x 59.84 x 28.74)
((50.40 x 59.84 x 28.74) x 2) ((50.40 x 59.84 x 28.74) x 3)
Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) Ø19.05(3/4) Ø22.2(7/8)
Ø19.05(3/4) Ø19.05(3/4) Ø28.58(9/8) Ø28.58(9/8) Ø28.58(9/8) Ø38.1(1
1
/
2) Ø44.5(1
3
/
4)
16 Outdoor Unit
Select the Best Location
Select the Best Location
Select space for installing Outdoor Unit, which will meet the following conditions:
No direct thermal radiation from other heat sources
No possibility of annoying the neighbors by noise from unit
No exposition to strong wind
With strength which bears weight of unit
Note that drain flows out of unit when heating
With space for air passage and service work shown below
Because of the possibility of fire, do not install unit to the space where generation, inflow, stagnation, and leak
of combustible gas is expected.
Avoid unit installation in a place where acidic solution and spray (sulfur) are often used.
Do not use unit under any special environment where oil, steam and sulfuric gas exist.
Installation restriction on Outdoor Unit when cooling operation is performed when the outdoor air temperature
is -5°C or lower
It is recommended to fence round the Outdoor Unit in order to prevent any person or animal from accessing
the Outdoor Unit.
If installation site is area of heavy snowfall, then the following directions should be observed.
- Make the foundation as high as possible.
- Fit a snow protection hood.
Installation Manual 17
Installation Space
Installation Space
Individual Installation
Basic space required
A space of at least 250 mm is necessary at the back for inlet air. Taking servicing, etc. from the rear into
account, a space of about 900 mm should be provided, the same as at the front.
When inlet air enters from right and left sides of unit
250 mm or more
900 mm or more (Control box is of a open/close type)
Top discharge (open in principle)
Front inlet (open in principle)
Rear inlet (open in principle)
A
B
C
D
E
C
ED
A
B
Control Box
Front Side
Rear Side
A
B
Control Box
Front Side
Rear Side
A
B
Control Box
Front Side
Rear Side
A
B
C
900 mm or more
(Control box is of a open/close type)
250 mm or more
150 mm from the wall
C
A
B
C
A
B
Front Side
Rear Side
C
A
B
C
Front Side
Rear Side
C
A
B
C
Front Side
Rear Side
C
A
B
C
A
B
Control Box
Front Side
Rear Side
Front Side
Rear Side
< Side view > < Top view >
< Side view > < Top view >
CAUTION
Wall height(H) must not
exceed height of the
product. If the wall height
is higher than the whole
height of product by (h),
Add (h) to
, .
18 Outdoor Unit
Installation Space
E
D
F
A
B
C
A
B
C
A
B
C
45° or more
200 mm or more
250 mm or more
A
B
C
1000 mm or more
Air outlet guide (Procured at the site)
250 mm or more
D
E
F
A
B
C
< Front view >
< Side view >
When unit is surrounded by walls
900 mm or more (Control box is of a open/close type)
250 mm or more
A
B
A
B
B
B
Front Side
Rear Side
A
B
B
B
Front Side
Rear Side
A
B
B
B
Front Side
Rear Side
Front Side
Rear Side
A
B
B
B
When there is an obstruction above the unit
Installation Manual 19
Installation Space
Collective / Continuous installation
Space required for collective installation and continuous installation:When installing several units, leave
the space between each block as shown below considering passage for air and people.
(Be opened)
900mm or more (control box is of a open/close type)
250 mm or more
A
B
C
Front Side
Rear Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
20 Outdoor Unit
Season wind and cautions in winter
Sufficient measures are required at a snow area or severe cold area in winter so that product can be operated
well.
Get ready for seasonal wind or snow in winter even in other area.
Install a suction and discharge duct so that snow or rain does not enter into when the product operates at out-
door temperature of less than 10°C.
Install the outdoor so that it does not directly touch with the suction hole at the area with much snow since the
inside of the Indoor Unit may be frozen because the air suction hole of the Outdoor Unit is clogged due to snow-
fall and then attach the hood to prevent effect of snowfall.
Install the Outdoor Unit at the higher installation console by 50cm than the expected average snowfall (annual
average snowfall) at the area with much snowfall since the inside of the Indoor Unit may be frozen because the
air suction hole of the Outdoor Unit is clogged due to snowfall.
Where snow accumulated on the upper part of the Outdoor Unit by more than 10cm, always remove snow for
operation.
1. The H of frame height must be more than 2 times the snowfall and its width shall not exceed the width of the
product. (If width of the frame is wider than that of the product, snow may accumulate)
2. Don't install the suction hole and discharge hole of the Outdoor Unit facing to the seasonal wind.
Lifting Method
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87

LG LRUV1008TS0.AWGAIDA Installation guide

Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI