Johnson Controls Variable Speed ECM Single Piece Multi-Position Air Handlers, AVC SERIES User manual

Category
Split-system air conditioners
Type
User manual
Johnson Controls Ducted Systems 5493974-UIM-B-0419
VARIABLE SPEED ECM
SINGLE PIECE MULTI-POSITION
AIR HANDLERS
MODELS: AVC SERIES
INSTALLATION MANUAL
ISO 9001
Certified Quality
Management System
LIST OF SECTIONS
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
DUCT WORK AND CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . .8
COIL METERING DEVICES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
REFRIGERANT LINE CONNECTION . . . . . . . . . . . . . . . . . . . . . . . .11
CONDENSATE DRAIN CONNECTIONS . . . . . . . . . . . . . . . . . . . . .12
ELECTRIC HEATER INSTALLATION . . . . . . . . . . . . . . . . . . . . . . .13
LINE POWER CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
LOW VOLTAGE CONTROL CONNECTIONS . . . . . . . . . . . . . . . . . 13
REQUIRED CONTROL SET-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
AIRFLOW AND COMFORT SETTING SELECTION . . . . . . . . . . . . 17
UNIT DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
AIR SYSTEM ADJUSTMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
INSTALLATION VERIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
START UP SHEET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
LIST OF FIGURES
Return Air Duct Attachment & Component Location . . . . . . . . . . . . . .2
Pressure Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Dimensions & Duct Connection Dimensions . . . . . . . . . . . . . . . . . . . .3
Typical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Horizontal Pan Adjustment Strap Hole Reference . . . . . . . . . . . . . . . .5
Coil Condensate Deflector Installation . . . . . . . . . . . . . . . . . . . . . . . . .6
Recommended Position of Coil to Install Downflow/Horizontal Right
Condensate Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Installation of Downflow Condensate Diverter Shields . . . . . . . . . . . . .7
60C Horizontal Right Condensate Deflectors . . . . . . . . . . . . . . . . . . .7
60C Horizontal Right Coil Condensate Final Assembly . . . . . . . . . . . .7
Condensate Shield . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Horizontal Suspension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Duct Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Duct Work Transition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Recommended Distributor Adjustment . . . . . . . . . . . . . . . . . . . . . . .10
Piston Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
TXV Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
TXV Bulb and Equalizer line Installations . . . . . . . . . . . . . . . . . . . . . 11
Proper Bulb Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Vertical Temperature Bulb Orientation . . . . . . . . . . . . . . . . . . . . . . . 11
Vapor Line Grommet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Line Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Cooling Models with and without Electric Heat Wiring . . . . . . . . . . . 15
Two-Stage Heat Pump Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Air Handler with Communicating AC or HP . . . . . . . . . . . . . . . . . . . 16
Multi-wire Terminal Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Duct Static Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Drain Traps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Location of Coil Trapped and Plugged Drain Connections . . . . . . . . 26
Wiring Diagram - ECM - Single Phase Heat Kits . . . . . . . . . . . . . . . 27
Wiring Diagram - Three Phase Heat Kits 208-230V . . . . . . . . . . . . . 28
LIST OF TABLES
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Horizontal Pan Strap Settings for Horizontal Left . . . . . . . . . . . . . . . . .5
Low Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Heat Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Comfort Setting Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Physical and Electrical Data - Cooling Only . . . . . . . . . . . . . . . . . . . .18
Electrical Data - Cooling Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Electrical Heat: Minimum Fan Speed . . . . . . . . . . . . . . . . . . . . . . . . 18
KW & MBH Conversions - For Total Power Input Requirement . . . . 19
Electric Heat Performance Data: 208/230-1-60 & 208/230-3-60 . . . 19
Electrical Data For Single Source Power Supply: 208/230-1-60 . . . 20
Electrical Data For Multi-source Power Supply: 208/230-1-60 . . . . . 22
Electrical Data For Single Source Power Supply: 208/230-3-60 . . . 23
Electrical Data For Multi-source Power Supply: 208/230-3-60 . . . . . 24
Air Flow Data (CFM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
SECTION I: GENERAL
The single piece air handler series provides the flexibility for installation
in any position. This unit may be used for upflow, downflow, horizontal
right, or horizontal left applications.
These units may be located in a closet, utility room, attic, crawl space,
or basement. These versatile models may be used for cooling or heat
pump operation with or without electric heat.
Top or side power and control wiring, color coded leads for control
wiring, easy to install drain connections, and electric heaters all
combine to make the installation easy and minimize installation cost.
Electric heat kits are available as field installed accessories. Single
phase kits are available from 2.5 kW to 25 kW. 208-230 volt three
phase kits are available from 10kW to 25kW.
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property
damage.
5493974-UIM-B-0419
2 Johnson Controls Ducted Systems
SAFETY REQUIREMENTS
1. Failure to carefully read and follow all instructions in this manual
can result in air handler malfunction, death, personal injury and/or
property damage.
2. This air handler should be installed in accordance with all national
and local building/safety codes and requirements, local plumbing
or wastewater codes, and other applicable codes.
3. This air handler should be installed only in a location and position
specified in the “Unit Installation” section of this Instruction Man-
ual.
4. The air handler is not to be used for temporary heating of buildings
or structures under construction.
5. Always install the air handler to operate within the air handler’s
intended maximum outlet air temperature.
6. The unit rating plate displays the air handler model number. The
unit dimensions for the supply air plenum are provided in Figure 3
and Table 1 of this Instruction Manual. The plenum must be
installed according to the instructions.
7. Clearance from combustible material is provided under “Clear-
ances” in the “Unit Installation” section.
8. It is necessary to maintain clearances for servicing. Access must be
allowed for electric heaters and blower.
9. The unit rating plate and power supply must be verified to ensure
that the electrical characteristics match.
10. Air handler shall be installed so the electrical components are pro-
tected from water.
11. Installing and servicing heating/cooling equipment can be hazard-
ous due to the electrical components. Only trained and licensed
personnel should install, repair, or service heating/cooling equip-
ment. Unlicensed service personnel can perform basic mainte-
nance functions such as cleaning and replacing the air filters. When
working on heating/cooling equipment, the precautions in the man-
uals and on the labels attached to the unit and other safety precau-
tions must be observed as applicable.
12. These instructions cover minimum requirements and conform to
existing national standards and safety codes. In some instances
these instructions exceed certain local codes and ordinances,
especially those who have not kept up with changing residential
and non-HUD modular home construction practices. These instruc-
tions are required as a minimum for a safe installation.
WARNING
FIRE OR ELECTRICAL HAZARD
Failure to follow the safety warnings exactly could result in serious
injury, death or property damage. A fire or electrical hazard may result
causing property damage, personal injury or loss of life.
WARNING
The air handler area must not be used as a broom closet or for any other
storage purposes, as a fire hazard may be created. Never store items
such as the following on, near or in contact with the furnace.
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum clean-
ers or other cleaning tools.
2. Soap powders, bleaches, waxes or other Cleaning compounds;
plastic items or containers; gasoline, kerosene, cigarette lighter
fluid, dry cleaning fluids or other volatile fluid.
3. Paint thinners and other painting compounds.
4. Paper bags, boxes or other paper products
Never operate the air handler with the blower door removed. To do so
could result in serious personal injury and/or equipment damage.
WARNING
Improper installation, adjustment, alteration, or maintenance may cre-
ate a condition where the operation of the product could cause per-
sonal injury or property damage. Refer to this manual for assistance,
or for additional information, consult a qualified contractor, installer, or
service agency.
CAUTION
This product must be installed in strict compliance with the installation
instructions and any applicable local, state, and national codes
including, but not limited to building, electrical, and mechanical codes.
!
!
!
!
CAUTION
DO NOT lift air handler by the cabinet braces. The cabinet braces are
held in place by the coil channels. The cabinet braces could become
disengaged from the cabinet causing the air handler to fall, potentially
causing injury or damaging property. See Figure 1 for location of cab-
inet braces. Lift the air handler by tightly gripping the casing.
CAUTION
These air handlers should be transported & handled in an upright,
upflow position. Failure to do so may result in unit damage and per-
sonal injury. Configuration conversions should be done at site of
installation.
!
!
FIGURE 1: Return Air Duct Attachment & Component Location
SIDE VIEW
RETURN AIR
DUCT
FRONT VIEW
SECONDARY DRAIN
UPFLOW 3/4” NPT
FILTER DOOR
WHEN ATTACHING DUCTWORK WITH
SCREWS - KEEP SCREWS WITHIN 5/8”
OF SIDESAND BACK OF AIR HANDLER
DUCTWORK MAY
BE FASTENED
CAUTIOUSLY WITH
SCREWSTOTHE
SIDESAND REAR OF UNIT
PRIMARY DRAIN
3/4” NPT
VAPOR
REFRIGERANT
LINE CONNECTION
LIQUID
REFRIGERANT
LINE CONNECTION
HORIZONTAL
DRAIN PAN
VERTICAL
DRAIN PAN
COIL COMPARTMENT
(Access panel removed)
BLOWER
COMPARTMENT
SECONDARY DRAIN
HORIZONTAL FLOW
3/4” NATIONAL PIPE
THREAD (NPT)
A0328-001
CABINET BRACE
CABINET BRACE
5493974-UIM-B-0419
Johnson Controls Ducted Systems 3
INSPECTION
As soon as a coil is received, it should be checked to insure it is still
under pressure per Figure 2. The coil should be inspected for possible
damage during transit. If damage is evident, the extent of the damage
should be noted on the carrier’s freight bill. A separate request for
inspection by the carrier’s agent should be made in writing. The Local
Distributor should be consulted for more information. The drain pan
should be checked for cracks or breakage. Before installation, the unit
should be checked for screws or bolts which may have loosened in
transit. There are no internal shipping or spacer brackets that need to
be removed.
It should be verified that all accessories such as heater kits are
available. Installation of these accessories or field conversion of the unit
should be accomplished before setting the unit in place or connecting
any wiring, duct work or piping.
FIGURE 2: Pressure Check
A0271-001
DEPRESS SCHRADER
CORE TO CHECK FOR
PRESSURE ONE TIME.
NOTE:
Verify that the coil is under
pressure when received.
FIGURE 3: Dimensions & Duct Connection Dimensions
TABLE 1: Dimensions
Models
Dimensions1Wiring Knockouts2Refrigerant
Connections
Line Size
AB CDE FG
Height Width Power Control Liquid Vapor
18B 41 17-1/2 12-7/8 14-1/4 16-1/2
7/8 (1/2)
1-3/8 (1)
1-23/32 (1-1/4) 7/8 (1/2) 3/8
3/4
24B 41 17-1/2 12-7/8 14-1/4 16-1/2
30B 47-1/2 17-1/2 19-1/2 14-1/4 16-1/2
36B 47-1/2 17-1/2 19-1/2 14-1/4 16-1/2
36C 51-1/2 21 22-5/8 17-3/4 20
42C 51-1/2 21 22-5/8 17-3/4 20
7/8
48C 51-1/2 21 22-5/8 17-3/4 20
48D 55-1/2 24-1/2 26-5/8 21-1/4 23-1/2
49C 51-3/4 21 26-5/8 17-3/4 20
60C 55-3/4 21 26-7/8 17-3/4 20
60D 55-1/2 24-1/2 26-5/8 21-1/4 23-1/2
1. All dimensions are in inches.
2. Actual size (Conduit size in parenthesis).
G
A
1-1/2”
7-11/32
C
FILTER ACCESS
DRAIN CONNECTIONS
FOR UPFLOW APPLICATIONS
REFRIGERANT CONNECTIONS
BLOWER
COMPARTMENT
BOTTOM INLET
DIMENSIONS
12-3/16E
D
18-5/8”
TOPOUTLET
DIMENSIONS
SERVICE
DISCONNECT
PANEL
A0329-001
B20-1/2”
21-7/16”
F
COIL
COMPARTMENT
5493974-UIM-B-0419
4 Johnson Controls Ducted Systems
SECTION III: UNIT INSTALLATION
UNIT SIZING
1. The size of the unit should be based on an acceptable heat loss or
gain calculation for the structure. The ACCA – Manual J or other
approved methods may be used. Reference Figure 3 & Table 1.
2. Only connect the air handler to a duct system which has an external
static pressure within the allowable range.
3. Airflow must be within the minimum and maximum limits approved
for electric heat, indoor coils and outdoor units.
4. When an air handler is installed so that supply ducts carry air circu-
lated by the air handler to areas outside the space containing the
air handler, the return air shall also be handled by duct(s) sealed to
the air handler casing and terminating in the space to be cooled/
heated.
5. Refer to the unit rating plate for the air handler model number, and
then see the dimensions page of this instruction for supply air ple-
num dimensions. The plenum must be installed according to the
instructions.
6. The installer must check available supply power and verify that it is
within the normal operating voltage range for the unit. The accept-
able voltage range for these units is as follows:
CLEARANCES
Clearances must be taken into consideration, and provided for as
follows:
1. Refrigerant piping and connections - minimum 12” recommended.
2. Maintenance and servicing access - minimum 36” from front of unit
recommended for blower motor / coil replacement.
3. Condensate drain lines routed to clear filter and panel access.
4. Filter removal - minimum 36” recommended.
5. The duct work connected to this unit is designed for zero clearance
to combustible materials.
6. A combustible floor base accessory is available for downflow appli-
cations of this unit, if required by local code.
LOCATION
Location is usually predetermined. Check with owner’s or dealer’s
installation plans. If location has not been decided, consider the
following in choosing a suitable location:
1. Select a location with adequate structural support, space for service
access, and clearance for air return and supply duct connections.
2. Using hanging brackets to wall mount this single piece air handler
unit is not recommended.
3. Normal operating sound levels may be objectionable if the air han-
dler is placed directly over some rooms such as bedrooms, study,
etc.
4. Select a location that will permit installation of condensate line to an
open drain or outdoors allowing condensate to drain away from
structure.
5. When an indoor coil is installed in an attic or above a finished ceil-
ing, an auxiliary drain pan should be provided under the air handler
as is specified by most local building codes.
6. Proper electrical supply must be available.
7. If unit is located in an area of high humidity (i.e. an unconditioned
garage or attic), nuisance sweating of casing may occur. On these
installations, unit duct connections and other openings should be
properly sealed, and a wrap of 2” fiberglass insulation with vinyl
vapor barrier should be used.
AIR HANDLER CONFIGURATION
These air handler units are supplied ready to be installed in an upflow
or horizontal left position. Refer to Figure 4. If the unit requires either
downflow or horizontal right airflow configurations, the unit must have
the coil assembly repositioned. Refer the Downflow or Horizontal Right
Conversion procedures.
Horizontal Left Conversion
NOTICE
Avoid handling aluminum coil components after handling the copper
line set or other tubing without first cleaning hands.
Entering Air Temperature Limits
Wet Bulb Temp. °F Wet Bulb Temp. °F
Min. Max. Min. Max.
57 72 65 95
Air Handler Voltage Normal Operating 1 Voltage Range
1. Rated in accordance with ARI Standard 110, utilization range “A”.
208V-230V-1-60 187V-253V
NOTICE
The primary and secondary drain line must be trapped to allow proper
drainage of condensate water. The secondary drain line should be
piped to a location that will give the occupant a visual warning that the
primary drain is clogged. If the secondary drain line is not used, it
must be capped.
FIGURE 4: Typical Installation
NOTICE
For horizontal left applications, high airflow can prevent the collected
condensate from draining properly since the direction of the airflow
opposes the direction of the draining condensate. The horizontal pan
must be angled properly in order to ensure proper drainage in high
airflow applications. Ensure that the pan is angled properly by check-
ing that the correct hole is used on the pan straps per TABLE 2. Use
FIGURE 5 to identify the "BACK" and "FRONT" straps since, in some
cases, these settings are not the same.
UPFLOW
HORIZONTAL RIGHT
HORIZONTAL LEFT
HEAT
HEAT
HEAT
DOWNFLOW
HEAT
A0330-001
5493974-UIM-B-0419
Johnson Controls Ducted Systems 5
Downflow or Horizontal Right Conversion
1. Remove coil access panel.
2. Slide coil/drain pan assembly out of air handler. 3. Note the lettered position of the center support bar for the coil/drain
pan. Remove the center support bar by sliding the forward end of
the support bar to the right or left until the lower finger clears the
structure.
FIGURE 5: Horizontal Pan Adjustment Strap Hole Reference
TABLE 2:
Horizontal Pan Strap Settings for Horizontal Left
Model Back Front
AP RFCX-P2 AE RFCX-E2 AVC CM
AP24B
AP30B
AP36B
RFCX24BP
RFCX30BP
RFCX36BP
AE24B
AE30B
AE36B
RFCX24BE
RFCX30BE
RFCX36BE
AVC24B
AVC30B
AVC36B
CM24A
CM24B
CM25B
CM30A
CM30B
CM36A
CM36B
22
AP60C RFCX60CP AE60C RFCX60CE AVC60C CM60C 3 4
AP36C
AP37C
AP42C
AP48C
RFCX36CP
RFCX37CP
RFCX42CP
RFCX48CP
AE42C
AE48C RFCX42CE
RFCX48CE AVC42C
AVC48C CM42C
CM48C 44
– – AE60D RFCX60DE AVC60D CM64D 4 5
AE36C RFCX36CE AVC36C CM37C
CM30C
CM36C 55
–––––CM24C 6 6
AP18B RFCX18BP AE18B RFCX18BE AVC18B CM18B 7 7
AP48D
AP60D RFCX48DP
RFCX60DP AE48D RFCX48DE AVC48D
CM30D
CM36D
CM42D
CM48D
CM60D
88
$
$77$&+0(17+2/()25
+25,=217$/'5$,13$1
+2/(/2&$7,21
180%(56


NOTICE
Convert air handler to the desired orientation prior to installation.
Conversion must be made before brazing the refrigerant connections
to the coil.
NOTICE
The center support bar for the coil/drain pan has a position identifier
embossed into the cabinet structure between the two forward fingers
of the support bar. There are four position identifiers: A, B, C, or D.
The lettered hole location can differ from unit to unit due to the cabi-
net width of the air handler. After removal and re-installation, the cen-
ter support bar must be installed in the same lettered position that it
was originally.
5493974-UIM-B-0419
6 Johnson Controls Ducted Systems
4. Note the numbered position of the coil slide rail located at the upper
right hand side of the indoor coil compartment. Remove slide rail
from air handler cabinet by removing front screw and lowering
bracket down to disengage hook on back of slide rail.
5. Turn air handler cabinet upside down (downflow position).
6. Install coil slide rail by hooking the hook end into holes at the num-
bered position the slide rail was originally in right rear corner post,
and secure rail into right front edge of cabinet with screw in the pre-
drilled hole.
7. Install center support bar for the coil/drain pan onto the lettered
position that it was originally mounted.
8. For horizontal right applications, install front and back coil conden-
sate deflectors (condensate deflectors shipped as loose parts with
the unit). Locate 4 screws securing coil delta plates to coil drain
pan. Loosen the screws. Slide each coil condensate deflector
between the drain pan and the coil delta plate. Tighten screws to
securely anchor coil condensate deflectors. Refer to Figure 6.
9. Slide the coil back into the cabinet. Be sure to engage the side coil
slide into the slide rail on the air handler cabinet.
10. Install coil access panel. Conversion is now complete.
Handling Coil Assemblies when Removed from Casing
When the coil assembly is removed from its casing, it must be handled
in such a manner that does not compromise the foam gasket that seals
the attachment point of the horizontal drain pan and primary drain pan.
DO NOT position the coil so that the coil weight rests on the horizontal
drain pan. By doing so, the horizontal drain pan straps could deform or
become damaged which will not allow the pan to be positioned/angled
correctly when the unit is horizontally installed, and if the foam gasket
that seals the attachment point becomes compromised by the move-
ment of the horizontal drain pan, condensate may leak at this point and
cause damage to the unit/property.
Positioning the Unit in Horizontal Applications
Set unit so that it is sloped 1/4” towards the drain plug.
AVC60C Downflow or Horizontal Right
The AVC60C model contains a unique coil assembly in that additional
pieces are required to be installed in horizontal right and downflow
applications to reduce the potential for condensate blow-off. The large
cooling capacity and high volumetric airflow (1800 CFM and above)
required for these coils put them more at risk of condensate blow-off.
The installation of additional shields should mitigate condensate man-
agement issues while allowing the coil to perform adequately for proper
cooling/heating.
When installing any of the shield provisions, it is advised to position the
coil such that the primary drain pan opening can be easily accessed to
attach the shields. See Figure 7.
NOTICE
The position identifier for the coil slide rail is embossed into the back
corner vertical angle of the cabinet structure. There are four position
identifiers: 1, 2, 3, or 4. The numbered attachment location can differ
from unit to unit due to the cabinet height of the air handler. After
removal and re-installation, the coil slide rail must be installed in the
same numbered position that it was originally.
NOTICE
The rear of the center support bar are longer than the fingers on the
forward end of the support bar.
NOTICE
When installing a coil condensate deflector, make sure that each
notch in the coil condensate deflector slides around the anchor screw
with the bottom of the notch fully set against the screw.
Ensure that the coil condensate deflector is installed with the flange
bending away from the coil delta plate.
NOTICE
Some models contain condensate deflectors that are not symmetrical
and must be installed in the correct orientation. If this air handling unit
is a **60C model, refer to the horizontal right conversion section on
the next page.
FIGURE 6: Coil Condensate Deflector Installation
IMPORTANT: DO NOT position the loose coil so that it rests on the
horizontal drain pan. The weight of the coil will deform the horizontal
pan straps, and the movement of the horizontal pan could potentially
compromise the foam gasket that seals the horizontal drain pan to the
primary drain pan. This could lead to water leaking at this attachment
point and damaging the insulation/cabinet/property.
INSTALL COIL BLOW
OFF WING ON FRONT
AND BACK OF COIL
COIL
DELTA PLATE
DRAIN PAN
SCREWS
(2 per blow off wing)
BLOW OFF WING
A0417-001
CONDENSATE
DEFLECTOR
(2 per deflector)
INSTALL COIL CONDENSATE
DEFLECTOR ON FRONT
AND BACK OF COIL
A0417-002
5493974-UIM-B-0419
Johnson Controls Ducted Systems 7
AVC60C Horizontal Right
1. Attach the additional condensate deflectors that were included in
the loose parts kit to the coil assembly by loosening the screws that
secure the front and rear delta plates to the primary drain pan. DO
NOT remove the screws completely. Loosen them enough so that
you can insert the deflectors between the drain pan and the delta
plate.
2. Insert the deflectors between the primary drain pan and the delta
plates. Make sure that the slots in the deflectors nest firmly against
the loosened screws between the primary drain pan and delta
plates.
3. Tighten the screws that secure the delta plates to the primary drain
pan. The interactive fit of the delta plate, primary drain pan, and
screws will hold the shields firmly in place during operation. Figure
10 shows the final assembly.
FIGURE 7: Recommended Position of Coil to Install Downflow/
Horizontal Right Condensate Components
FIGURE 8: Installation of Downflow Condensate Diverter Shields
IMPORTANT: FOR 60C (21.0”) COIL ASSEMBLIES: While the
shields may appear similar, they are actually different in that there is a
front and rear shield. Due to their asymmetry, these shields will not fit
correctly if they are oriented incorrectly. See Figure 9 for details.
A1076-001
A1074-001
Condensate Shield
- Downflow Only
(Field Installed)
Condensate Shield
(Factory Installed)
FIGURE 9: 60C Horizontal Right Condensate Deflectors
FIGURE 10: 60C Horizontal Right Coil Condensate Final Assembly
A1075-001
Front Deflector Rear Deflector
Drip Leg
(Orient Towards Bottom Coil Slab)
A1077-001
Condensate Deectors
5493974-UIM-B-0419
8 Johnson Controls Ducted Systems
Upflow or Downflow Applications (All Models)
AVC60C Downflow Conversion
1. Rotate equipment cabinet so that the bottom of the primary (plastic)
drain pan can be accessed.
2. Locate the downflow condensate shield (as shown in Figure 11)
and foam gasket strip shipped in the loose parts kit included with
the coil.
3. Install the condensate shield to the primary drain pan (as shown in
Figure 8). There should be an identical condensate shield that was
factory installed on the opposite side of the primary drain pan.
4. Apply the foam gasket strip to the condensate shield evenly so that
it covers the condensate shield and primary drain pan.
Horizontal Left Applications (All Models)
Air handling units are supplied ready to be installed in a horizontal left
position. A horizontal drain pan is factory installed. If horizontal right
application, refer to the horizontal right conversion before proceeding.
See sections on “Refrigerant Line Connections” and “Condensate Drain
Connections” for further installation instruction.
SECTION IV: DUCT WORK AND
CONNECTIONS
Air supply and return may be handled in one of several ways best
suited to the installation. Upflow, horizontal or downflow applications
may be used.
The vast majority of problems encountered with heating and cooling
systems can be linked to improperly designed or installed duct systems.
It is therefore highly important to the success of an installation that the
duct system be properly designed and installed.
When installing a central air return grille in or near the living space, it is
advisable to design the duct work so that the grille is not in direct line
with the opening in the unit. One or two elbows and acoustical duct liner
assures a quieter system. Operation where return air duct is short or
where sound may be a problem, acoustical duct liner should be used
inside the duct. Use flexible duct connectors to minimize the
transmission of vibration/noise into the conditioned space.
Insulation of duct work is a must where it runs through an unheated
space during the heating season or through an uncooled space during
the cooling season. The use of a vapor barrier is recommended to
prevent absorption of moisture from the surrounding air into the
insulation.
The supply air duct should be properly sized by use of a transition to
match unit opening. All ducts should be suspended using flexible
hangers and never fastened directly to the structure.
Duct work should be fabricated and installed in accordance with local
and/or national codes. This includes the standards of the National Fire
Protection Association for Installation of Air-Conditioning and
Ventilating Systems, NFPA No. 90B. Duct systems should be designed
in accordance with the Air Conditioning Contractors of America (ACCA)
– Manual D.
Use flexible duct collars to minimize the transmission of vibration/noise
into the conditioned space. If electric heat is used, non-flammable
material must be used.
All ducts should be suspended using flexible hangers and never
fastened directly to the structure.
HORIZONTAL SUSPENSION
These air handlers may be suspended in horizontal applications. It is
recommended to use angle steel support brackets with minimum 3/8”
threaded rods, supporting the unit from the bottom. Attach the threaded
rods at the locations shown in the Figure 12, leaving enough clearance
between door and rod so that doors maybe easily removed for service.
NOTICE
For maximum performance, if an air handling unit is being installed in
Upflow or Downflow orientation, it is recommended that the horizontal
drain be removed from the assembly. This can be achieved by remov-
ing the horizontal drain pan support straps, cutting the foam gasket
that seals the attachment point of the horizontal drain pan and pri-
mary drain pan, and removing the entire horizontal drain pan assem-
bly.
FIGURE 11: Condensate Shield
NOTICE
For horizontal left applications, high airflow can prevent the collected
condensate from draining properly since the direction of the airflow
opposes the direction of the draining condensate. The horizontal pan
must be angled properly in order to ensure proper drainage in high
airflow applications. Ensure that the pan is angled properly by check-
ing that the correct hole is used on the pan straps per TABLE 2. Use
FIGURE 5 to identify the FRONT and REAR straps since, in some
cases, these settings are not the same.
A1073-001
WARNING
Do not bring in return air from a location which could introduce haz-
ardous substances into the airflow.
Use 1/2” screws to connect duct work to cabinet. If pilot holes are
drilled, drill only through field duct and unit flange.
CAUTION
This unit is not designed for non-ducted (freeblow) applications. Do
not operate without duct work attached to unit.
Equipment should never be operated without filters.
CAUTION
DO NOT lift air handler by the cabinet brace. The cabinet brace is
held in place by the coil channel. The cabinet brace could become
disengaged from the cabinet causing the air handler to fall, potentially
causing injury or damaging property. See Figure 1 for location of cab-
inet braces.
NOTICE
When assembling the support structure, make sure to size to provide
clearance for access door removal.
!
!
!
5493974-UIM-B-0419
Johnson Controls Ducted Systems 9
DUCT FLANGES
Three duct flanges are provided to assist in positioning and attaching
duct work to the air handler. These flanges are included in the unit parts
bag. With the screws from the parts bag, install one of the duct flanges.
Duct flanges have holes on both legs with one leg longer than the other.
The longer leg can be used to mate against the air handler so that
different thicknesses of duct board can be made flush with the outer
surface of the air handler. Repeat the procedure for the other two
flanges. Refer to Figure 13. If the flanges are not used, they may be
discarded.
UNIT CONNECTIONS
There are several ways to handle the supply and return air duct
connections. The location and sizing of the connections depends on the
situation and the method best suited to the installation. Upflow,
horizontal or downflow applications may be used.
The supply air duct should be properly sized by use of a transition to
match unit opening. Refer to Table 1 for air handler unit inlet and outlet
dimensions.
Duct work that is not designed to match the supply air opening can
cause turbulence inside the plenum. This turbulence can change the air
flow patterns across the electric heater limit switches. If the factory
suggested transition cannot be fabricated, it is recommended that a
block off plate (approximately 8" high and running the full width of the
plenum) be attached to the supply opening. Refer to Figure 14 as a
visual aid. The use of this block off plate will enable better air circulation
across the limit switches.
AIR FILTERS
Return air filters are required and must be field supplied. Filtration can
be accomplished external to the unit or the integral filter rack may be
used. A 1" filter access rack has been built into the unit. Remove filter
access cover shown. Install proper size filter. Standard 1" size
permanent or throw away filter may be used, or permanent washable
filters are available using model numbers: 1PF0601, 602 or 603. See
Table 7 for filter size.
.
SECTION V: COIL METERING DEVICES
A piston or a TXV is to be installed in the field. There is an installation
manual that comes with the TXV kit. It is recommended to install the
piston or TXV kit prior to installation of coil and brazing of line set. Until
brazing is completed and cooled, the TXV sensing bulb must not be
installed.
The outdoor technical guide for outdoor units should be consulted for
required piston or TXV on the indoor coil. The piston and the Schrader
core are supplied with the outdoor unit. When the piston is used instead
of the TXV, the Schrader core is installed in the suction line equalizer
connection port and is capped with the supplied plastic cap. The
Schrader core must not be installed if the TXV is installed, because the
TXV equalizer line attaches to the equalizer connection port.
Dimension in Inches
Air Handler Cabinet Size X H
17-1/2 Width-Short H 21 41
17-1/2 Width-Long H 21 47-1/2
21 Width-Short H 21-1/2 51-1/2
21 Width-Long H 21-1/2 55-3/4
24-1/2 Width 21-1/2 55-1/2
FIGURE 12: Horizontal Suspension
FIGURE 13: Duct Attachment
SUSPENSION SUPPORT LOCATIONS FOR HORIZONTAL APPLICATIONS
X
H
2” 1-1/2”
MIN. 1-1/2” x 1-1/2”
Angle Recommended
length 26” minimum
with 2” clearance
on both sides
of Air Handler
MIN. 3/8”
THREADED ROD
X
H
1-1/2”
1-1/2”
MIN. 1-1/2” x 1-1/2”
Angle Recommended
length 26” minimum
with 2” clearance on
both sides of
Air Handler
MIN. 3/8”
THREADED ROD
A0331-001
A0445-001
DUCT FLANGES
(Shipped in bag with unit)
FIGURE 14: Duct Work Transition
CAUTION
Use 1/2” screws to connect duct work to unit. Longer screws will
pierce the drain pan and cause leakage. If pilot holes are drilled, drill
only though field duct and unit bottom duct flange.
CAUTION
Equipment should never be operated without filters.
A0332-001
RECOMMENDED
TRANSITION SUGGESTED LOCATION
OF BLOCK OFF PLATE
!
!
5493974-UIM-B-0419
10 Johnson Controls Ducted Systems
PISTON INSTALLATION
Install Schrader Valve Core and Piston as follows:
1. After holding charge is completely discharged, remove black plastic
cap from equalizer connection port on the vertical part of the vapor
line.
2. Distributor position must be adjusted to allow the preformed liquid
line assembly to properly line up with the hole in the tubing access
panel. Raise the distributor body approximately 2” toward the top of
the coil or what would be the top of the coil if coil was in the upflow
position. See Figure 15. Adjust as necessary.
3. Install Schrader valve core supplied with the outdoor unit into the
equalizer fitting connection port using a valve core tool.
4. Loosen and remove the liquid line connection nut and the sealing
disc from the distributor assembly. Note that the fitting has right
hand threads.
5. Slide the nut over the liquid line to be installed, and discard the seal
disc.
6. Install required size piston into the distributor. Refer to supplied
Tabular Data Sheet for specific piston size and indoor coil match
up. See Figure 16.
7. Verify that the Teflon washer is still in place in the distributor open-
ing. See Figure 16.
8. After piston is installed, install the liquid line to the top of the piston/
distributor assembly. Hand tighten, and turn an additional 1/4 turn
to seal. Do not over tighten fittings.
9. Replace black plastic cap on unused equalizer fitting connection
port.
10. After line set is installed, leak test the system.
THERMOSTATIC EXPANSION VALVE (TXV) INSTAL-
LATION
The following are basic steps for installation. For detailed instructions,
refer to the Installation Instructions accompanying the TXV kit. Install
TXV kit as follows:
1. Relieve the holding charge by depressing Schrader core on the
suction manifold stub out.
2. After holding charge is completely discharged, loosen and remove
the Schrader core.
3. Place a backup wrench on distributor, loosen and remove brass
distributor nut. Retain brass nut for use on liquid line. Keep Teflon
washer in place and discard clear disk.
4. Install the thermal expansion valve to the distributor assembly with
supplied fittings. Ensure Teflon washer is seated in distributor.
Hand tighten and turn an additional 1/4 turn to seal. Do not over-
tighten fittings. See Figure 17.
5. Slide the nut removed in step 3 over the supplied liquid line. Place
supplied Teflon washer from TXV kit in place on TXV, and install liq-
uid line to the top of the thermal expansion valve. Adjust assembly
so liquid line aligns with hole in access panel. See Figure 18. Hand
tighten the liquid line, and apply an additional 1/4 turn to seal.
CAUTION
COIL UNDER PRESSURE.
Verify that pressure has been released by depressing schrader valve
core.
The coil requires a metering device to be added.
See outdoor unit documentation for correct TXV or piston to be used.
NOTICE
To prevent moisture and contaminates from entering the system, the
coil should not be open to atmosphere for extended periods of time. If
the coil cannot be brazed into the refrigeration system during a rou-
tine installation period, the ends should be temporarily closed or
plugged. For a short term delay, use masking tape over the ends of
the copper tubing to close the tube from the air. For a longer term
delay, use plugs or caps. There is no need to purge the coil if this pro-
cedure is followed.
WARNING
Failure to install Schrader Valve Core in the vapor line equalizer con-
nection port for piston applications could result in total refrigerant loss
of the system!
FIGURE 15: Recommended Distributor Adjustment
!
!
$
FIGURE 16: Piston Installation
CAUTION
Do not overtorque. Do not use slip joint pliers. This will distort the alu-
minum distributor and the brass fitting (potentially causing leaks).
CAUTION
Outdoor unit model numbers ending with an “H” have a factory
installed hard start kit which is required when a TXV is installed. Out-
door unit model numbers with no “H” ending do not require a hard
start kit unless local regulations dictate it.
IMPORTANT: Refer to the Technical Guide for the unit to determine
the proper TXV kit to be used on this product.
CAUTION
Do not over-torque. Do not use slip joint pliers. This will distort the
aluminum distributor and the brass fitting (potentially causing leaks).
A0305-001
DISTRIBUTOR
PISTON
LIQUID LINE SWIVEL COUPLING
(This fitting is a right-handed thread.
Turn counter-clockwise to remove.)
TEFLON WASHER
!
!
!
5493974-UIM-B-0419
Johnson Controls Ducted Systems 11
6. Install the TXV equalizer line onto the vapor line by hand tightening
the 1/4” SAE coupling nut to the equalizer fitting, and apply an addi-
tional 1/3 turn to seal. See Figure 18.
7. Pass the temperature sensing bulb tube for the TXV through the
tube opening in the split grommet of the access panel.
8. Install the TXV bulb to the vapor line near the cabinet, using the
bulb clamp(s) furnished with the TXV assembly. Ensure the bulb is
making maximum contact. See Figures 18 & 19, and accomplish
the following:
a. If possible, install the temperature bulb on a horizontal run of
the vapor line. Ensure that the bulb is installed at a 10 o’clock
or 2 o’clock position.
b. If bulb installation is made on a vertical run, ensure that the
bulb is a minimum of 8 inches (20.3 cm) away from elbow
coming out of the coil. Position the bulb with the tail of the
bulb at the top, so that the bulb acts as a reservoir. See Fig-
ure 20.
c. Insulate the bulb using thermal insulation provided to protect
it from the effect of the surrounding ambient temperature.
Cover completely to insulate.
9. After line set is installed, leak test the system.
SECTION VI: REFRIGERANT LINE
CONNECTION
FIGURE 17: TXV Installation
WARNING
Schrader valve core MUST NOT be installed with TXV installation.
Poor system performance or system failure could result.
CAUTION
In all cases, mount the TXV temperature sensing bulb after vapor line
is brazed and sufficiently cooled.
Failure to use suction line split grommet may result in TXV failure.
FIGURE 18: TXV Bulb and Equalizer line Installations
TXV / DISTRIBUTOR COUPLING
LIQUID LINE / TXV COUPLING
TEFLON WASHER
TXV
TEFLON WASHER
DISTRIBUTOR
A0281-002
!
!
TXV BULB
(Wrap with
insulation.)
VAPOR LINE
LIQUID LINE
TVX
EQUALIZER
LINE
THERMAL EXPANSION
VALVE (TXV)
DISTRIBUTOR
BODY
A0279-002
FIGURE 19: Proper Bulb Location
FIGURE 20: Vertical Temperature Bulb Orientation
CAUTION
Coil is under inert gas pressure. Relieve pressure from coil by
depressing Schrader core at end of suction manifold stub out.
CAUTION
Dry nitrogen should always be supplied through the tubing while it is
being brazed, because the temperature required is high enough to
cause oxidation of the copper unless an inert atmosphere is provided.
The flow of dry nitrogen should continue until the joint has cooled.
Always use a pressure regulator and safety valve to insure that only
low pressure dry nitrogen is introduced into the tubing. Only a small
flow is necessary to displace air and prevent oxidation.
TXV BULB
(Cover completely
with insulation.)
VAPOR LINE
OF LINE SET
A0269-002
CLAMP
A
DETAIL A
TXV SENSING BULB
(Pass through split hole
in grommet.)
VAPOR
LINE
NUT
NUT
Bulb at
10 o’clock
position.
Bulb at
2 o’clock
position.
SCREW
SCREW
CLAMP
VAPOR LINE
OF LINE SET
A0378-002
CLAMP
TXV
TEMPERATURE
BULB
TAIL END UP
8” (20.3 cm)
NOTE:
Ensure bulb is on opposite
side of tubing bend plane.
!
!
5493974-UIM-B-0419
12 Johnson Controls Ducted Systems
Connect lines as follows:
1. Suction and liquid line connections are made outside the cabinet.
Leave the tubing connection panel attached to the cabinet. Coil
access panel should be removed for brazing. The lines are
expanded to receive the field line set tubes for most outdoor unit
matches.
2. Remove grommets where tubes exit the cabinet to prevent burning
them during brazing. In some units, the vapor line grommet may be
shipped as a loose part with the unit. Refer to Figure 21.
3. Cut the end of the suction tube using a tube cutter. Place the tube
cutter as close as possible to the end of the tube to allow as much
depth as possible for the connection and brazing of the suction line.
To ensure suction line fits into connection, deburr the stub out
(including inner pressure protrusion from cutting).
4. If coil does not have a factory installed TXV, install the required size
piston or TXV kit. See coil metering devices section for detailed
instructions.
5. If the coil does have a factory installed TXV, remove the liquid line
copper cap which is soft soldered onto the outside of the 3/8” stub
protruding from front of the coil cabinet tubing panel as follows:
a. Screw a sheet metal screw into the center of the cap.
b. Apply a small amount of heat to the cap while pulling on the
screw using slip joint pliers.
6. Insert liquid and suction lines into the coil connections at the coil
cabinet tubing panel.
7. Wrap a water soaked rag around the coil connection tubes inside
the cabinet to avoid transferring excess heat to the coil or TXV.
8. Purge refrigerant lines with dry nitrogen.
9. Braze the suction and liquid lines, and allow the joints to cool.
10. Route the TXV sensing bulb through suction line opening.
11. Secure sensing bulb and equalizer line capillary tubes with nylon
cable ties to prevent leaks from tubes rubbing.
12. If piston is used, install Schrader core into suction header, and rein-
stall cap.
13. Re-attach the grommets to the lines carefully to prevent air leak-
age. In some units, the vapor line grommet may be shipped as a
loose part with the unit. Refer to Figure 21.
14. Attach the coil access panel to the cabinet.
15. Refer to Outdoor unit Installation Manual, and accomplish evacua-
tion, leak check and charging instructions. Check all field brazed
joints and metering device connections.
16. Ensure lines are sound isolated by using appropriate hangers or
strapping.
SECTION VII: CONDENSATE DRAIN
CONNECTIONS
All drain lines should be trapped a minimum of three inches, should be
pitched away from unit drain pan and should be no smaller than the coil
drain connection.
Route the drain line so that it does not interfere with accessibility to the
coil, air handling system or filter and will not be exposed to freezing
temperatures. See Figures 29 & 30 for drain connection locations.
If the coil is provided with a secondary drain it should be piped to a
location that will give the occupant a visual warning that the primary
drain is clogged. If a secondary drain is not used it must be plugged.
Instruct the owner that the indoor coil drain pan should be inspected
and cleaned regularly to prevent odors and assure proper drainage. If a
secondary drain is not used it must be plugged. See Figures 29 & 30.
Coils should be installed level or pitched slightly toward the drain end.
Suggested pitch should not exceed 1/4 inch per foot of coil.
The drain pan connections are designed to ASTM Standard D 2466
Schedule 40. Use 3/4” PVC or steel threaded pipe. Since the drains are
not subject to any pressure it is not necessary to use Schedule 40 pipe
for drain lines.
NOTICE
Avoid handling aluminum coil components after handling the copper
line set or other tubing without first cleaning hands.
NOTICE
Route the refrigerant lines to the coil in a manner that will not obstruct
service access to the coil, air handling system, furnace flue or filter.
NOTICE
All indoor coil connections are copper-to-copper and should be
brazed with a phosphorous-copper alloy material such as Silfos-5 or
equivalent. DO NOT use soft solder.
FIGURE 21: Vapor Line Grommet
CAUTION
DO NOT use TeflonTM tape, pipe thread compound, or other
sealants. The use of a sealant may cause damage and premature
failure of the drain pan.
Threaded drain connection should be hand-tightened, plus no more
than 1 turn.
Avoid Double Trapping of a single drain line.
CAUTION
When the unit is installed in an attic or above a finished ceiling, an
auxiliary drain pan should be provided under the coil as specified by
most local building codes. When this exterior secondary drain pan is
used that drain should be piped to a location that will give the occu-
pant a visual warning that the primary drain is clogged.
$
*5200(7
)RU9DSRU/LQH
!
!
5493974-UIM-B-0419
Johnson Controls Ducted Systems 13
SECTION VIII: ELECTRIC HEATER
INSTALLATION
If the air handler requires electric heat, install the electric heat kit
according to the installation instructions included with the kit. After
installing the kit, mark the air handler nameplate to designate the heater
kit that was installed. If no heater is installed, mark the name plate
appropriately to indicate that no heat kit is installed.
Use only 6HK Revision C or later heater kits, as listed on air handler
name plate and in these instructions. Use data from Tables 9 & 16 for
information on required minimum motor speed tap to be used for
heating operation and maximum over-current protection device
required as listed for combination of air handler and heater kit.
For Upflow, Downflow and Horizontal left-hand applications, the kits can
be installed without modification.
Field modification is required for Horizontal right-hand airflow applica-
tion only. Follow instructions with heater for modification.
SECTION IX: LINE POWER CONNECTIONS
Power may be brought into the unit through the supply air end of the
unit (top left when unit is vertical) or the left side panel. Use the hole
appropriate to the unit’s orientation in each installation to bring conduit
from the disconnect. The power lead conduit should be terminated at
the electrical control box. To determine proper wire sizing, refer to
Tables 7 - 10 and the latest edition of the National Electric Code or in
Canada the Canadian electrical Code and local codes to determine
correct wire sizing. To minimize air leakage, seal the wiring entry point
at the outside of the unit.
All electrical connections to air handlers must be made with copper
conductors. Direct connection of aluminum wiring to air handlers is
not approved.
If aluminum conductors are present, all applicable local and national
codes must be followed when converting from aluminum to copper
conductors prior to connection to the air handler.
If wire other than uncoated (non-plated), 75° C ambient, copper wire is
used, consult applicable tables of the National Electric Code (ANSI/
NFPA 70). The chosen conductor and connections all must meet or
exceed the amperage rating of the overcurrent protector (service
disconnect or fuse) in the circuit.
Additionally, existing aluminum wire within the structure must be sized
correctly for the application according to National Electric Code and
local codes. Caution must be used when sizing aluminum rather than
copper conductors, as aluminum conductors are rated for less current
than copper conductors of the same size.
SECTION X: LOW VOLTAGE CONTROL
CONNECTIONS
The 24 volt power supply is provided by an internally wired low voltage
transformer which is standard on all models, However, if the unit is con-
nected to a 208 volt power supply, the low voltage transformer must be
rewired to the 208 volt tap. See the unit wiring label.
Remove desired knockout and pierce foil faced insulation to allow wir-
ing to pass through. Use as small of a hole as possible to minimize air
leakage.
Install a 7/8” plastic bushing in the selected hole and keep low voltage
wiring as short as possible.
To further minimize air leakage, seal the wiring entry point at the out-
side of the unit.
The field wiring is to be connected with wire connectors to the wires
provided. Refer to Figures 24 & 25.
NOTICE
In some horizontal applications, the service disconnects on the elec-
tric heat kits must be rotated 180° so the up position of the discon-
nect is the ON position. This service disconnect orientation change is
required by UL1995, Article 26.19 (in reference to all circuit break-
ers).
FIGURE 22: Line Power Connections
),(/'32:(5:,5,1*
9
&20321(17&2'(6
*1'*5281'/8*
6'6(59,&(',6&211(&7
&.7&,5&8,7
&1:,5(&211(&725187
*1'
12(/(&75,&+($7
32:(5
6833/< &1
&1
*1'
-803(5%$5
6,1*/(6285&(32:(5

08/7,6285&(32:(5

08/7,6285&(32:(5
:,7+-803(5%$5

7(50,1$/%/2&.25
6(59,&(',6&211(&7
32:(5
6833/< 32:(5
6833/<
6,1*/(6285&(32:(5
&,5&8,7621N:N:
&,5&8,7621N:
7(50,1$/%/2&.25
6(59,&(',6&211(&7
&.7
&.7
32:(5
6833/<
6'
6'
6'
6'
6'
32:(5
6833/<
*1'
*1'
*1'
*1'
32:(5
6833/<
/
/
/
/
/
/
&.7
/
/
/
/
6'
6'
6'
/
/
/
/
/
/
/
/
/
08/7,6285&(32:(5
&.7
&.7
&,5&8,7621N:N:
&,5&8,7621N:
3+$6((/(&75,&+($7237,216
3+$6((/(&75,&+($732:(5237,216
$
NOTICE
All wiring must comply with local and national electrical code require-
ments. Read and heed all unit caution labels.
NOTICE
It is possible to vary the amount of electric heat turned on during the
defrost cycle of a heat pump. Standard wiring will only bring on the
first stage of electric heat during defrost. See Table 5 for additional
information on heat during defrost cycle.
5493974-UIM-B-0419
14 Johnson Controls Ducted Systems
Humidity Switch Input
The air handler control is designed to work with a humidity control that
closes when the humidity is below the set-point. The control is open
when the humidity is above the set-point. This humidity control may be
referred to as a humidistat or a dehumidistat.
The humidity switch controls de-humidification operation of the control
during cooling operation. The humidity switch should be connected to
HUM wire of the control. See Figures 23 & 24.
FIGURE 23: Control Board
LEAVING AIR TEMP
SENSOR TERMINALS
FLOAT SWITCH
INPUT
HUMIDIFIER
OUTPUT
CFM
INDICATOR
STATUS
INDICATOR BLOWER
SPEED
JUMPERS
HUMIDISTAT
JUMPER
AC/HP JUMPER
MODEL
ID PLUG
FUSE
COMM
PORT
SERVICE
TOOL
PORT
A0405-001
ELECTRONIC
AIR CLEANER
EAC
NOTICE
All wiring must comply with local and national electrical code require-
ments. Read and heed all unit caution labels.
It is possible to vary the amount of electric heat turned on during the
defrost cycle of a heat pump. Standard wiring will only bring on the
first stage of electric heat during defrost. See Heat Output and Limit
Connections and Table 5 for additional information on heat during
defrost cycle.
TABLE 3:
Low Voltage Connections
Wire Colors Signals Comment
R Red 24 VAC power (fused)
G Green Continuous Fan operation Fan Speed, 63% of high cool speed.
Y/Y2 Yellow Second or full stage compressor operation
Y1 Yellow & Black First stage compressor operation Not used with outdoor units having one stage compressors.
W2 Brown Second stage heat operation
W1 White First stage heat operation
O Orange Reversing valve operation
EAC Field Supplied Wiring Electric Air Cleaner Located on P2 connector. There is 24VAC output during indoor blower
operation to energize a pilot duty relay for an electronic air cleaner.
X/L Field Supplied Wiring Connection point for heat pump fault indi-
cator This terminal is a connection point only and does not affect air handler control operation.
HUM Purple Humidity switch input
C (COM) Blue 24 VAC common
The field wiring is to be connected at the pigtails supplied with the control board harness.
5493974-UIM-B-0419
Johnson Controls Ducted Systems 15
*Optional dehumidification humidistat switch contacts open on humidity rise.
NOTES:
1. “Y/Y2” Thermostat wire must be connected for full CFM and applications requiring 60 second blower off delay for SEER enhancement.
2. Move HUM STAT jumper on air handler control board to YES position if humidistat is used.
3. For heat pump applications - set AC/HP jumper on air handler control board to the HP position.
.
* Optional dehumidification humidistat switch contacts open on humidity rise.
NOTES:
1. “Y/Y2” Thermostat wire must be connected for full CFM and applications requiring 60 second blower off delay for SEER enhancement.
2. Remove humidistat jumper on air handler control board.
3. For heat pump applications - set AC/HP jumper on air handler control board to the HP position.
CONTROL WIRING USING COMMUNICATING
CONTROLS
The Communicating System consists of several intelligent communicat-
ing components including the Communicating Thermostat Control
(touch-screen wall thermostat), variable speed air handler, air condi-
tioner (15 and 18 SEER premium air conditioners) or heat pump (13, 15
and 18 SEER premium heat pumps), which continually communicate
with each other via a four-wire connection called the A-R-C-B bus.
Commands, operating conditions, and other data are passed continu-
ally between components over the A-R-C-B bus. See Figure 26. The
result is a new level of comfort, versatility, and simplicity.
In order to use this air handler in full communications (COMM) mode, it
MUST be installed with the matching touch-screen Communicating
Control (wall thermostat) and an outdoor air conditioner or heat pump
with a fully communicating control.
This air handler may also be used along with the touch-screen Commu-
nicating Control and a non-communicating outdoor air conditioner
through the addition of a communicating AC Control board to the out-
door unit. This system allows full communication between the air han-
dler, outdoor unit, and touch-screen Communication Control.
Use the wiring diagram below to connect the air handler control, touch-
screen Communicating Control (wall thermostat) and communicating
outdoor unit. Be sure that all of the “A+” terminals are connected
together, all of the “B-” terminals are connected together, all of the “C”
terminals are connected together and all of the “R” terminals are con-
nected together. See Figure 26 & 27. When using a fully communicating
system, removal of the low voltage signal connector at P3 is recom-
mended (C, G, R, etc.). The four small screw terminals in the terminal
block on the end of the air handler control should be used.
FIGURE 24: Cooling Models with and without Electric Heat Wiring
$LU+DQGOHU&RQWURO:LULQJ
7\SLFDO$&&RROLQJRQO\$SSOLFDWLRQV
7+(50267$7
321$,5
+$1'/(5
%2$5' 67$*(
$,5&21',7,21,1*
55
*
<
:
:
&
*
:
:
<
&
<<
<
2
+80
&
&20
+80,',67$7
$
7+(50267$7 67$*(
$,5&21',7,21,1*
55
*
<
:
:
&
*
:
:
<
&
<<
<
2
+80
$LU+DQGOHU&RQWURO:LULQJ
7\SLFDO$&ZLWK(OHFWULF+HDW$SSOLFDWLRQV
+80,',67$7
321$,5
+$1'/(5
%2$5'
&
&20
321$,5
+$1'/(5
%2$5'
+80 ($& (/(&75,&$,5
&/($1(55(/$<
67$*(
$,5&21',7,21,1*
$FFHVVRU\
&RQWURO:LULQJ
9+80,',),(5
+80,',67$7
FIGURE 25: Two-Stage Heat Pump Wiring
&21752/:,5,1*$LU+DQGOHU83*+36\VWHPV
7ZR6WDJH+3ZLWK<RUN*XDUG9,%RDUG
&RQYHQWLRQDO$SSOLFDWLRQ1RW+RW+HDW3XPS
7+(50267$7
$,5+$1'/(5
%2$5'
67$*(6&52//
+($73803
55 5
**
<
(
::
2 2
2
;/ ;/ ;/
&&
<<
< <
<287
<
:287
:287
%6
:
:
+80
&20
+80,',67$7
<
$
5493974-UIM-B-0419
16 Johnson Controls Ducted Systems
FLOAT SWITCH INPUT
An optional switch may be connected to the FLT terminals on the con-
trol board. This feature is only functional when used with the Communi-
cating Control. It is intended for use with a water overflow switch.
LEAVING AIR TEMP SENSOR INPUT
A plenum air temperature sensor (thermistor) can be connected to the
LAS terminals on the control board. The Communicating Control can
the monitor the temperature of the supply air in the plenum.
SECTION XI: REQUIRED CONTROL
SET-UP
1. Consult system wiring diagram to determine proper thermostat wir-
ing for your system.
2. If using a communicating control and a humidistat is installed,
change HUM STAT jumper from NO to YES.
3. Set the MODE jumper to A/C (Air Conditioner) or HP (Heat Pump)
position depending on the outdoor unit included with the system.
4. Set airflow and comfort setting jumper to proper positions.
FUNCTIONALITY AND OPERATION
Jumper Positions
Hum Stat Jumper
The HUM STAT jumper configures the control to monitor the humidity
switch input. With the jumper in the NO position, the control will ignore
the HUM input. With the jumper in the YES position, the control will
monitor the HUM input to control the blower speed for de-humidification
during cooling operation.
If the jumper is not present, the control will operate as if the jumper is in
the NO position.
AC/HP Jumper
The AC/HP jumper configures the control to operate properly with an air
conditioner (AC position) or heat pump (HP position). With the jumper in
the AC position, the control will treat any “Y” call as a cooling call. With
the jumper in the HP position, the O input signal is received from the
room thermostat. This allows the control to recognize whether in the
heating or cooling mode and energizes the 24 VAC HUM output when
blower is on and a first stage heating call is present.
If the jumper is not present, the control will operate as if the jumper is in
the HP position.
Airflow and Comfort Setting Jumpers
See separate section.
Status and Fault Codes
The control includes an LED that displays status and fault codes. These
codes are shown in Table 4. The control will display the fault codes until
power is removed from the control or the fault condition is no longer
present.
CAUTION
If any field-supplied wiring is to be connected to the control board,
such as will be the case if the Communicating Control is used or if a
humidistat, float switch or leaving air temperature switch are used,
the additional wires MUST be routed through the hole at the lower left
of the control box. DO NOT add any additional holes to the control
box. After attaching the additional wires to the board, the remaining
hole around the wires must be plugged with the sealant putty supplied
or with a suitable waterproof sealant. FAILURE TO SEAL THIS HOLE
MAY ALLOW WATER TO ENTER THE CONTROL BOX AND DAM-
AGE THE CONTROL BOARD.
FIGURE 26: Air Handler with Communicating AC or HP
IMPORTANT: Do not place more than one wire under any single
communication terminal screw (there are four communication termi-
nal screws). If more than one wire must be connected to a terminal
screw, attach only the terminal end of a one wire pigtail no longer than
6“, and use a wire connector to connect the other end of the pigtail to
the other wires. Failure to do this will result in nuisance communica-
tion error faults. See Figure 27.
FIGURE 27: Multi-wire Terminal Connection
!
A+
R
C
B-
A+
R
C
B-
A+
R
C
B-
R
G
Y/Y2
Y1
W2
W1
O
HUM
COM
TOUCH SCREEN
COMMUNICATING
CONTROL
AIR HANDLER
COMMUNICATING
CONTROL
AC/HEAT PUMP
COMMUNICATING
CONTROL
EAC
A0409-001
OUTDOOR UNIT
INDOOR UNIT
WIRE
CONNECTOR
THERMOSTAT
TERMINAL
SCREW
NOTE:
Ensure only one wire under
terminal screw.
To connect more than one wire:
A+
R
C
B-
AIR HANDLER
COMMUNICATING
CONTROL BOARD
1. Connect only terminal end of
” wire pigtail.
2. Use wire connector to connect
other end of pigtail
to other wires.
A0237-001
IMPORTANT: The following steps must be taken at the time of instal-
lation to insure proper system operation.
TABLE 4:
Fault Codes
Fault or Status Condition LED1 (RED)
Flash Code
Status
No power to control OFF
Internal control fault ON
2 sec on 2 sec off heartbeat Normal
0.1 sec on, 0.1 sec off Test mode
Call for heat and cool at the same time 7
Model Plug Not inserted 8
Internal fault self-corrected, attempting normal operation 9
5493974-UIM-B-0419
Johnson Controls Ducted Systems 17
HUM OUT Output
The HUM OUT output can be used to drive an external relay or solenoid
(24 VAC coil) to control a humidifier. The output is energized when the
control has a thermostat call for heating (heat pump or electric heat).
Heat Output
The control is connected to the heater relays using pins 4,5, and 6 of
connector P1. The relay outputs are 24 VAC.
The control energizes the heat relays as shown in Table 5.
Depending on the heat kit installed in the air handler, the control pro-
vides the flexibility to configure the amount of heat delivered with the
first stage heating call. As an example, when the control’s W1 input is
connected to the room thermostat’s first stage heat signal, a call for first
stage heat will energize one heating element (HT1). If the control’s W2
input is connected to the room thermostat’s first stage heat signal, a call
for first stage heat will energize one heating element (HT2). With either
configuration, the control will energize two heating elements (HT1, and
HT2) when it receives a first and second stage heat input from the ther-
mostat.
Wiring Related Faults
If the control receives a simultaneous call for heating and cooling (fault
code 7), the control will perform both heating and cooling operations.
SECTION XII: AIRFLOW AND COMFORT
SETTING SELECTION
AIRFLOW SELECTION
When not using communicating functionality, the airflow and comfort
setting selection jumpers must be set properly at the time of installation
for proper system operation. Place jumpers in the proper locations
based on the information shown in Table 16 & Figure 18.
Inputs to air handler control board are passed to the motor which deter-
mines the target CFM to be delivered. The following inputs will produce
the CFM per the appropriate table and selected tap settings.
These variable speed air handlers are designed to deliver constant air-
flow (CFM) regardless of the external static pressure (ESP) in the
ductwork. Therefore, if too many supply registers are closed, a filter
becomes clogged, or there is a restriction in the ductwork, the motor will
automatically operate at a higher speed to compensate for the higher
ESP. This may result in a higher operating sound level and motor dam-
age.
To Set Cooling Airflow:
Refer to the outdoor unit technical guide for the recommended airflow
with the matching indoor coil. Refer to Table 16 for the possible high
speed cooling and heat pump airflow selections.
Find the recommended system airflow in Table 16 for the installed air
handler model and outdoor unit.
Select the COOL airflow needed from Table 15. Set the COOL and
ADJUST Jumpers on the control as indicated in Table 16.
To Set Heat Pump Airflow:
The heat pump airflow setting is the same as the cooling airflow setting.
No additional airflow setting is required. However, you must set the AC/
HP jumper to the HP position for proper system operation (See Figure
23).
To Set Electric W1 Heat Airflow:
The blower speed required for 1st stage electric heat is different than
cooling. Refer to Table 16 for the possible CFM selections. Refer to
Table 8 for the minimum required airflow for the electric heater installed.
Find the desired airflow in Table 16 for low heat. Set the HEAT jumper
on the control as indicated in Table 16.
To Set W2 Electric Heat Airflow:
Airflow for any W2 input, which is for second stage of electric heat, is
the indicated CFM for high heat tap selection on Table 16.
Blower Ramp-Up /Ramp-Down:
To minimize the sound made by the blower when it speeds up or slows
down, the blower will slowly ramp up or down from one speed to
another. Changes in blower speed during A/C or heat pump heating can
take up to 30 seconds. Changes in blower speed during electric resis-
tance heating can take up to 15 seconds.
COMFORT SETTINGS
Normal
The normal setting provides a ramp-up from zero airflow to full capacity
and a ramp-down from full capacity back to zero airflow.
Humid
The humid setting is best-suited for installations where the humidity is
frequently very high during cooling season, such as in the southern part
of the country. On a call for cooling, the blower will ramp up to 50% of
full capacity and will stay there for two minutes, then will ramp up to
82% of full capacity and will stay there for five minutes, and then will
ramp up to full capacity, where it will stay until the wall thermostat is sat-
isfied.
Dry
The dry setting is best suited to parts of the country where excessive
humidity is not generally a problem, where the summer months are usu-
ally dry. On a call for cooling the motor will ramp up to full capacity and
will stay there until the thermostat is satisfied. At the end of the cooling
cycle, the blower will ramp down to 50% of full capacity where it will stay
for 60 seconds. Then it will ramp down to zero.
Temperate
The temperate setting is best suited for most of the country, where nei-
ther excessive humidity nor extremely dry conditions are the norm. On
a call for cooling, the motor will ramp up to 63% of full capacity and will
stay there for 90 seconds, then will ramp up to full capacity. At the end
of the cooling cycle, the motor will ramp down to 63% of full capacity
and will stay there for 30 seconds, then will ramp down to zero.
TABLE 5:
Heat Relays
Input Heat Relay Output
W1 HT1
W2 HT2
W1 and W2 HT1 and HT2
NOTICE
Incorrect airflow and comfort settings may result in decreased system
efficiency and performance.
CAUTION
DO NOT change the ADJUST tap position on the control as this will
change your cooling airflow previously selected.
TABLE 6:
Comfort Setting Selection
DELAY TAP COMFORT SETTING
A Normal
B Humid
C Dry
D Temperate
!
5493974-UIM-B-0419
18 Johnson Controls Ducted Systems
SECTION XIII: UNIT DATA
TABLE 7:
Physical and Electrical Data - Cooling Only
Models 18B 24B 30B 36B 36C 42C
Blower - Diameter x Width 10 x 8 10 x 8 10 x 8 10 x 8 11 x 10 11 x 10
Motor HP 1/3 HP 1/3 HP 1/3 HP 1/2 HP 1/2 HP 1/2 HP
Nominal RPM 1050 1050 1050 1050 1050 1050
Voltage 208/230 208/230 208/230 208/230 208/230 208/230
Full Load Amps @230V 2.9 2.9 2.9 4.5 4.5 4.5
Filter1Type DISPOSABLE OR PERMANENT
Size 16 x 20 x 1 16 x 20 x 1 16 x 20 x 1 16 x 20 x 1 20 x 20 x 1 20 x 20 x 1
Permanent Type Kit 1PF0601 1PF0601 1PF0601 1PF0601 1PF0602 1PF0602
Shipping Operating Weight (lbs.) 91/85 93/87 119/113 119/113 120/114 144/136
Models 48C 48D 49C 60C 60D
Blower - Diameter x Width 11 x 10 11 x 10 11x10 11 x 10 11 x 10
Motor HP 3/4 HP 3/4 HP 3/4 HP 3/4 HP 3/4 HP
Nominal RPM 1050 1050 1050 1050 1050
Voltage 208/230 208/230 208/230 208/230 208/230
Full Load Amps @230V 7.0 7.0 7.0 7.0 7.0
Filter1Type DISPOSABLE OR PERMANENT
Size 20 x 20 x 1 22 x 20 x 1 20x20 x1 20 x 20 x 1 22 x 20 x 1
Permanent Type Kit 1PF0602 1PF0603 1PF0602 1PF0602 1PF0603
Shipping Operating Weight (lbs.) 158/150 163/153 158/150 156/146 180/170
1. Field supplied.
TABLE 8:
Electrical Data - Cooling Only
Models Motor FLA1
1.FLA = Full Load Amps
Minimum Circuit Ampacity MOP2
2.MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. Refer to the latest edition of the
National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing.
208V 230V 208V 230V
18B/24B/30B 3.0 2.9 3.8 3.6 15
36B/36C/42C 5.0 4.5 6.3 5.6 15
48C/48D/49C/60C/60D 7.3 7.0 9.1 8.8 15
TABLE 9:
Electrical Heat: Minimum Fan Speed
Heater Kit
Models1,2,3
Nom.
kW
@240V
Air Handler Models
18B 24B 30B 36B 36C 42C 48C 48D 49C 60C 60D
6HK(0,1)6500206 2.4kW Med Lo (D)Med Lo (D)Med Lo (D)Med Lo (D)Med Lo (D)Med Lo (D)Med Lo (D)Med Lo (D)Med Lo (D)Med Lo (D)Med Lo (D)
6HK(0,1)6500506 4.8kW Med Lo (D) Med (C) Med (C) Med Lo (D) Med (C) Med Lo (D)Med Lo (D)Med Lo (D)Med Lo (D)Med Lo (D)Med Lo (D)
6HK(0,1)6500806 7.7kW Med (C) Med Hi (B) Med Hi (B)Med Lo (D)Med Hi (B) Med (C) Med Lo (D)Med Lo (D)Med Lo (D)Med Lo (D)Med Lo (D)
6HK(0,1)6501006
6HK36501025 9.6kW Med (C) Med Hi (B) Med Hi (B)Med Lo (D)Med Hi (B) Med (C) Med Lo (D)Med Lo (D)Med Lo (D)Med Lo (D)Med Lo (D)
6HK(1,2)6501306 12.5kW Med Hi (B) Med Hi (B) Med (C) Med Hi (B) Med (C) Med Lo (D)Med Lo (D)Med Lo (D)Med Lo (D)Med Lo (D)
6HK(1,2)6501506
6HK36501525 14.4kW Med Hi (B) Med Hi (B) Med Hi (B) Hi (A) Med (C) Med (C) Med (C) Med Lo (D)Med Lo (D)
6HK(1,2)6501806
6HK36501825 17.3kW Med Hi (B) Med Hi (B) Hi (A) Med (C) Med Hi (B) Med (C) Med (C) Med (C)
6HK(1,2)6502006
6HK46502025 19.2kW Med Hi (B) Hi (A) Hi (A) Med Hi (B) Hi (A) Med Hi (B) Med Hi (B)Med Hi (B)
6HK(1,2)6502506
6HK46502525 24kW –––––––Hi (A)––Med Hi (B)
1.(0,1) - 0 = no service disconnect OR 1 = with service disconnect.
2.(1,2) - 1 = with service disconnect, no breaker jumper bar OR 2 = with service disconnect & breaker jumper bar.
3.6HK3 = 3-Phase with terminal block connectors only, 6HK4 = 3-Phase with service disconnect.
5493974-UIM-B-0419
Johnson Controls Ducted Systems 19
TABLE 10:
KW & MBH Conversions - For Total Power Input Requirement
For a power distribution voltage that is different than the provided nominal voltage, multiply the kW and MBH data from the table by the conversion
factor in the following table.
DISTRIBUTION POWER NOMINAL VOLTAGE CONVERSION FACTOR
208V 240V 0.75
220V 240V 0.84
230V 240V 0.92
TABLE 11:
Electric Heat Performance Data: 208/230-1-60 & 208/230-3-60
Heater
Models1,2,3 Nominal kW
@240V
Total Heat4kW Staging
kW MBH W1 Only W1 + W2
208V 230V 208V 230V 208V 230V 208V 230V
1PH
6HK(0,1)6500206 2.4 1.8 2.2 6.2 7.5 1.8 2.2 1.8 2.2
6HK(0,1)6500506 4.8 3.6 4.4 12.3 15 3.6 4.4 3.6 4.4
6HK(0,1)6500806 7.7 5.8 7.1 19.7 24.1 5.8 7.1 5.8 7.1
6HK(0,1)6501006 9.6 7.2 8.8 24.6 30.1 7.2 8.8 7.2 8.8
6HK(1,2)6501306 12.5 9.4 11.5 32 39.2 3.1 3.8 9.4 11.5
6HK(1,2)6501506 14.4 10.8 13.2 36.9 45.1 3.6 4.4 10.8 13.2
6HK(1,2)6501806 17.3 13 15.9 44.3 54.2 6.5 7.9 13 15.9
6HK(1,2)6502006 19.2 14.4 17.6 49.2 60.2 7.2 8.8 14.4 17.6
6HK(1,2)6502506 24 18 22 61.5 75.2 7.2 8.8 18 22
3PH
6HK36501025 9.6 7.2 8.8 24.6 30.1 7.2 8.8 7.2 8.8
6HK36501525 14.4 10.8 13.2 36.9 45.1 10.8 13.2 10.8 13.2
6HK36501825 17.3 13 15.9 44.3 54.2 13 15.9 13 15.9
6HK46502025 19.2 14.4 17.6 49.2 60.2 7.2 8.8 14.4 17.6
6HK46502525 24 18 22 61.5 75.2 9 11 18 22
1.(0,1) - 0 = no service disconnect OR 1 = with service disconnect.
2.(1,2) - 1 = with service disconnect, no breaker jumper bar OR 2 = with service disconnect & breaker jumper bar.
3.6HK3 = 3-Phase with terminal block connectors only, 6HK4 = 3-Phase with service disconnect.
4.For different power distributions, see conversion table above.
5493974-UIM-B-0419
20 Johnson Controls Ducted Systems
TABLE 12:
Electrical Data For Single Source Power Supply: 208/230-1-60
Air Handler Models Heater Models1,2 Heater
Amps
@240V
Field Wiring
Min. Circuit Ampacity MOP.3
208V 230V 208V 230V
18B
6HK(0,1)6500206 10 14.6 15.6 15 20
6HK(0,1)6500506 20 25.4 27.5 30 30
6HK(0,1)6500806 32 38.6 42.2 40 45
6HK(0,1)6501006 40 47.0 51.5 50 60
24B
6HK(0,1)6500206 10 14.6 15.6 15 20
6HK(0,1)6500506 20 25.4 27.5 30 30
6HK(0,1)6500806 32 38.6 42.2 40 45
6HK(0,1)6501006 40 47.0 51.5 50 60
6HK(1,2)6501306 52 60.2 66.1 70 70
30B
6HK(0,1)6500206 10 14.6 15.6 15 20
6HK(0,1)6500506 20 25.4 27.5 30 30
6HK(0,1)6500806 32 38.6 42.2 40 45
6HK(0,1)6501006 40 47.0 51.5 50 60
6HK(1,2)6501306 52 60.2 66.1 70 70
6HK(1,2)6501506 60 68.7 75.4 70 80
36B
6HK(0,1)6500206 10 17.1 17.6 20 20
6HK(0,1)6500506 20 27.9 29.5 30 30
6HK(0,1)6500806 32 41.1 44.2 45 45
6HK(0,1)6501006 40 49.5 53.5 50 60
6HK(1,2)6501306 52 62.7 68.1 70 70
6HK(1,2)6501506 60 71.2 77.4 80 80
6HK(1,2)6501806 72 84.4 92.0 90 100
6HK(1,2)6502006 80 92.8 101.3 100 110
36C
6HK(0,1)6500206 10 17.1 17.6 20 20
6HK(0,1)6500506 20 27.9 29.5 30 30
6HK(0,1)6500806 32 41.1 44.2 45 45
6HK(0,1)6501006 40 49.5 53.5 50 60
6HK(1,2)6501306 52 62.7 68.1 70 70
6HK(1,2)6501506 60 71.2 77.4 80 80
6HK(1,2)6501806 72 84.4 92.0 90 100
6HK(1,2)6502006 80 92.8 101.3 100 110
42C
6HK(0,1)6500206 10 17.1 17.6 20 20
6HK(0,1)6500506 20 27.9 29.5 30 30
6HK(0,1)6500806 32 41.1 44.2 45 45
6HK(0,1)6501006 40 49.5 53.5 50 60
6HK(1,2)6501306 52 62.7 68.1 70 70
6HK(1,2)6501506 60 71.2 77.4 80 80
6HK(1,2)6501806 72 84.4 92.0 90 100
6HK(1,2)6502006 80 92.8 101.3 100 110
48C
6HK(0,1)6500206 10 19.9 20.7 25 25
6HK(0,1)6500506 20 30.8 32.7 35 35
6HK(0,1)6500806 32 44.0 47.3 45 50
6HK(0,1)6501006 40 52.4 56.6 60 60
6HK(1,2)6501306 52 65.6 71.3 70 80
6HK(1,2)6501506 60 74.0 80.5 80 90
6HK(1,2)6501806 72 87.3 95.2 90 100
6HK(1,2)6502006 80 95.7 104.4 100 110
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26