Ashcroft RXLdp Operating instructions

Type
Operating instructions

Ashcroft RXLdp is a low differential pressure transducer designed for measuring clean, dry air and other noncorrosive gases. It offers both unidirectional and bidirectional pressure ranges and various output signals. With a wide operating temperature range of 0 to 160°F, it is suitable for various applications. Its rugged construction and ability to withstand overpressure up to 15 psi make it reliable for demanding environments. The easy mounting options and simple electrical connections ensure hassle-free installation.

Ashcroft RXLdp is a low differential pressure transducer designed for measuring clean, dry air and other noncorrosive gases. It offers both unidirectional and bidirectional pressure ranges and various output signals. With a wide operating temperature range of 0 to 160°F, it is suitable for various applications. Its rugged construction and ability to withstand overpressure up to 15 psi make it reliable for demanding environments. The easy mounting options and simple electrical connections ensure hassle-free installation.

MODEL RXLdp
INSTRUCTION SHEET
1. GENERAL:
A failure resulting in injury or damage
may be caused by excessive overpres-
sure, excessive vibration or pressure
pulsation, excessive instrument temper-
ature, corrosion of the pressure con-
taining parts, or other misuse. Consult
Ashcroft Inc., Stratford, Connecticut,
USA before installing if there are any
questions or concerns.
2. OVER PRESSURE:
Pressure spikes in excess of the rated
overpressure capability of the transducer
may cause irreversible electrical and/
or mechanical damage to the pressure
measuring and containing elements.
3. STATIC ELECTRICAL CHARGES:
Any electrical device may be suscep-
tible to damage when exposed to static
electrical charges. To avoid damage
to the transducer the operator/installer
should follow proper ESD (electrostatic
discharge) protection procedures before
handling the pressure transducer.
Description
The Ashcroft Model RXLdp is a low
differential pressure transducer to
be used with clean, dry air and other
noncorrosive gases. Both unidirectional
(e.g., 0/1.0 in. W.C.) and bidirectional
(e.g., ±3.0 in. W.C.) pressure ranges
are offered, as well as a wide selection
of output signals. The storage tempera-
ture limits of the RXLdp are from –40
to 180°F. The unit operates between 0
and 160°F and is temperature compen-
sated between 40 and 125°F.
Mounting
The unit should be mounted with #6
or #8 screws using the two mounting
holes provided. Easy access to the zero
adjustment may be a consideration
when mounting. The transducer can be
mounted in any orientation with virtually
no effect on calibration. Any minor zero
pressure offsets that are encountered
can be adjusted using the zero adjust
potentiometer.
WARNING! READ
BEFORE INSTALLATION
m m
© 2011 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614-5145, USA, Tel: 203-378-8281, Fax: 203-385-0499, www.ashcroft.com
All sales subject to standard terms and conditions of sale. I&M 011-10071 (250-3117). Rev. B 11/11
Piping
The two pressure connections are pro-
tected with tubing to avoid debris enter-
ing the unit. It should be left in place until
system tubing is to be connected. The
Ashcroft Model RXLdp can withstand
overpressure or vacuum up to 15 psi
without requiring a recalibration.
Recommended flexible tube sizes should
be as follows:
1/4 barb: < 316˝ ID tube
1/8 barb: < 116˝ ID tube
Power Requirements
Voltage Output:
The Model RXLdp will operate on any
unregulated supply voltage from 12-36
Vdc (24 Vdc typical) and will draw less
than 5mA.
Current Output:
The voltage required for 4-20mA output
is dependent on the loop resistance of
the circuit. The figure below shows the
minimum supply voltage (Vmin) required
for a given Loop Resistance (RL).
B. Current Output
Electrical Connections
1. With pressure connection options
(With Case)
F01 1 8 NPT female
MB2 1 4 barbed
MB8 1 8 barbed
A. Voltage Output
+POWER
SUPPLY
RS
POWER
SUPPLY
OUT
+
+
Load Limitations 4-20mA
OPERATING
REGION
LOOP SUPPLY VOLTAGE (VDC)
010 12 20 30 36 40
1250
1045
1000
750
500
250
0
LOOP RESISTANCE (OHMS)
Vmin = 12 + (.022A x RL)
RL = RS+ RW
RL = Loop Resistance (ohms)
RS = Sense Resistance (ohms)
MODEL RXLdp
INSTRUCTION SHEET
© 2011 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614-5145, USA, Tel: 203-378-8281, Fax: 203-385-0499, www.ashcroft.com
All sales subject to standard terms and conditions of sale. I&M 011-10071 (250-3117). Rev. B 11/11
2.8
3.7
1.6
0.9
3.8
0.6
0.4
2.8
1.1
1.7
Ø 0.14
0.6
2.2
3.3
2.3
Ø 0.20
1.1
General Dimensions (IN INCHES)
B. Current Output
A. Voltage Output
Electrical Connections
2. With pressure connection option MB1
(No Case)
  • Page 1 1
  • Page 2 2

Ashcroft RXLdp Operating instructions

Type
Operating instructions

Ashcroft RXLdp is a low differential pressure transducer designed for measuring clean, dry air and other noncorrosive gases. It offers both unidirectional and bidirectional pressure ranges and various output signals. With a wide operating temperature range of 0 to 160°F, it is suitable for various applications. Its rugged construction and ability to withstand overpressure up to 15 psi make it reliable for demanding environments. The easy mounting options and simple electrical connections ensure hassle-free installation.