Danfoss Termix Compact 28 VX-FI Operating instructions

Type
Operating instructions

Danfoss Termix Compact 28 VX-FI is a heat exchanger unit for the production of heating in large buildings. It can be used for connection to indirect district heating in places where the district heating plant requires a hydraulic break on the plant side. It is also suitable for conversion to district heating when the secondary heating system is suitable to being connected to direct district heating or when a particularly effective security against leakage in the heating system is required. It is possible to connect a hot-water tank.

The substation is fitted with an efficient plate heat exchanger, which ensures the most favorable heat extraction and achieves optimum comfort and operating economy.

Danfoss Termix Compact 28 VX-FI is a heat exchanger unit for the production of heating in large buildings. It can be used for connection to indirect district heating in places where the district heating plant requires a hydraulic break on the plant side. It is also suitable for conversion to district heating when the secondary heating system is suitable to being connected to direct district heating or when a particularly effective security against leakage in the heating system is required. It is possible to connect a hot-water tank.

The substation is fitted with an efficient plate heat exchanger, which ensures the most favorable heat extraction and achieves optimum comfort and operating economy.

OperatingGuide
TermixCompact28VX-FI
1.0TableofContents
1.0TableofContents.............................................1
........................................................................2
2.0Functionaldescription......................................3
3.0Safetynotes.....................................................4
3.1SafetyNotesgeneral............................................4
4.0Mounting........................................................5
4.1MountingtheCompactstation..................................5
4.2Start-up..............................................................12
4.3Electricalconnections.............................................13
5.0Design.............................................................14
5.1Design...............................................................14
5.2Schematicdiagram................................................15
6.0Controls..........................................................17
6.1Heatingcircuit......................................................17
6.2Other.................................................................20
6.3Maintenance........................................................22
7.0Troubleshooting..............................................23
7.1Troubleshootingingeneral......................................23
7.2TroubleshootingHE...............................................23
7.3Disposal.............................................................24
8.0Declaration......................................................27
8.1Declarationofconformity........................................27
DanfossDistrictEnergy
VI.LZ.M1.02/LUK42363
DEN-GT
1
OperatingGuideTermixCompact28VX-FI
2
DEN-GT
VI.LZ.M1.02/LUK42363
DanfossDistrictEnergy
OperatingGuideTermixCompact28VX-FI
2.0Functionaldescription
Districtheatingsubstationforindirectheating.
Spaceheating
TheTermixCompact28VX-FIisaheatexchangerunitforthe
productionofheatinginlargebuildingssuchassportscentres,
schools,blocksofatsetc.Itcanbeusedforconnectiontoindirect
districtheatinginplaceswherethedistrictheatingplantrequiresa
hydraulicbreakontheplantside.Itisalsosuitableforconversion
todistrictheatingwhenthesecondaryheatingsystemissuitable
tobeingconnectedtodirectdistrictheatingorwhenaparticularly
effectivesecurityagainstleakageintheheatingsystemisrequired.
Itispossibletoconnectahot-watertank.
Efcientheatexchanger
Thesubstationisttedwithanefcientplateheatexchanger,
whichensuresthemostfavourableheatextractionandachieves
optimumcomfortandoperatingeconomy.
Severalvariants
TermixCompact28VX-FIisbuiltwithaheatexchangerforspace
heating,owcontroller,pump,electronicregulationoftheheating
circuitaswellasadirectoutletforahotwatertank.Theelectronic
controllerisfactorypre-set.Electricalcomponentsarepre-wired,
andtheunitisequippedwithaplugfor230Va.c.
Itisrecommendedthatdynamicbalancingvalvesareinstalledin
thebuildingsrisersintheheatsupplyandontheheatingsystems
returnlineimmediatelybeforetheunit.
TermixCompact28VX-FIisproducedinstandardconstructions:
VXwithheatexchangerforindirectheating.
VXwithheatexchangerforindirectheatingandintegrated
tankregulation.
Flexiblesolution
Pipeconnectioncanbemadefromeitherthetoporbottom,which
makesthissolutionhighlyexible.Atthesametime,bothspace
andtimearesavedwheninstalling.
Minimalheatloss
Completeinsulationoftheunitensuresminimalheatloss.
Reliableandeasytoinstall
TermixCompact28VX-FIisoperationallyreliable.Aqualityproduct
manufacturedinDenmark,whichiseasytoinstallandquickly
commissioned.
DanfossDistrictEnergy
VI.LZ.M1.02/LUK42363
DEN-GT
3
OperatingGuideTermixCompact28VX-FI
3.0Safetynotes
3.1SafetyNotesgeneral
Thefollowinginstructionsrefertothestandarddesignof
substation.Specialversionsofsubstationsareavailableon
request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation
andstart-upofthesubstation.Themanufactureracceptsno
liabilityfordamageorfaultsthatresultfromnon-compliancewith
theoperatingmanual.Pleasereadandfollowalltheinstructions
carefullytopreventaccidents,injuryanddamagetoproperty.
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleasecomplywiththeinstructionsissuedbythesystem
manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass.
Themaximumchloridecompoundsoftheowmediumshouldnot
behigherthan150mg/l.
Theriskofequipmentcorrosionincreasesconsiderablyifthe
recommendedlevelofpermissiblechloridecompoundsis
exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary
sourceofenergy.However,alsootherenergysourcescanbeused
wheretheoperatingconditionsallowitandalwaysarecomparable
todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse
installationinafrost-freeroom,wherethetemperaturedoesnot
exceed50°Candthehumiditydoesnotexceed60%.Donotcover
orwallupthesubstationorinanyotherwayblocktheentrance
tothestation.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin
compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat
thesubstationcanbeseparatedfromallenergysources(also
powersupply).
Emergency
Incaseofdangeroraccidents-re,leaksorotherdangerous
circumstances-interruptallenergysourcestothestationif
possible,andseekexperthelp.
Incaseofdiscolouredorbad-smellingdomestichotwater,closeall
shut-offvalvesonthesubstation,informtheoperatingpersonnel
andcallforexperthelpimmediately.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto
installationshouldbeinconditionswhicharedryandheated.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallationspermissiblesystempressureand
temperature.
Themaximumtemperatureoftheowmediuminthesubstationis
110°C.
Themaximumoperatingpressureofthesubstationis16bar.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases
considerablyiftherecommendedpermissibleoperatingparameters
areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves,
however,alwaysinaccordancewithlocalregulations.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns.
Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen
position.Thesurfacesofthesubstationcangethot,whichcancause
skinburns.Theballvalvesondistrictheatingsupplyandreturnshould
beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation
hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallangeconnections,screwjoints
andelectricalclampandscrewconnectionsmustbecheckedand
tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen
addedtothesystemandthesystemhasbeenputintooperation,
re-tightenALLconnections.
4
DEN-GT
VI.LZ.M1.02/LUK42363
DanfossDistrictEnergy
OperatingGuideTermixCompact28VX-FI
4.0Mounting
4.1MountingtheCompactstation
Installationmustbeincompliancewithlocalstandardsand
regulations.
Districtheating(DH)-Inthefollowingsections,DHreferstothe
heatsourcewhichsuppliesthesubstations.Avarietyofenergy
sources,suchasoil,gasorsolarpower,couldbeusedasthe
primarysupplytoDanfosssubstations.Forthesakeofsimplicity,
DHcanbetakentomeantheprimarysupply.
Connections:
1.Districtheating(DH)supply
2.Districtheating(DH)return
3.Heating(HE)supply
4.Heating(HE)return
5.Tankowline(TFL)
6.Tankreturnline(TRL)
Connectionsizes:
DH+HE:
G1”(int.thread)
TFL+TRL:
G¾”(int.thread)
Dimensions(mm):
Withinsulation:
H890xW905xD400
Weight(approx.):60kg
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote
themarkingsonthestation.
DanfossDistrictEnergy
VI.LZ.M1.02/LUK42363
DEN-GT
5
OperatingGuideTermixCompact28VX-FI
Removethefront.
Removeotherblocks.
Attachthemountingrailtothewall.
Liftthestation.
6
DEN-GT
VI.LZ.M1.02/LUK42363
DanfossDistrictEnergy
OperatingGuideTermixCompact28VX-FI
Mountthestationonthemountingrail.
Attachthestationtothewallintheholesonthemountingplate.
Installthesafetyvalve.
Installballvalves.
MountblockA(CifitistheMagnapump)ontheleft-handsideof
thepump.AttachblockEtoblockA/C,andattachittothepipe
abovethepumpbyclickingitinplace.
DanfossDistrictEnergy
VI.LZ.M1.02/LUK42363
DEN-GT
7
OperatingGuideTermixCompact28VX-FI
MountblockB(DifitistheMagnapump)ontheright-handsideof
thepump.
MountblockF(GforVM2valve).Theblockishingedandcanbe
drawnaroundthevalve.AttachtheblocktoblockB/DandE.
MountblockJandHaroundthevalveforthetankcontrol.
Mountthefrontcover.
8
DEN-GT
VI.LZ.M1.02/LUK42363
DanfossDistrictEnergy
OperatingGuideTermixCompact28VX-FI
4.1.1InstallingtheCompactstation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting
andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes
andlabelsareplacedcorrectly.Ifyouwishtomountthestation
differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided
inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe
cleanedandrinsed.
Tightening
Duetovibrationduringtransport,allsubstationconnectionsmust
becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha
plug.Shouldtheplugsrequireremoval,thismustonlybedoneby
anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbettedaccording
toschematicdiagram.Pleasenotethatthestrainermaybe
suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe
madeusingthreaded,angedorweldedconnections.
Keyholeformounting.
DanfossDistrictEnergy
VI.LZ.M1.02/LUK42363
DEN-GT
9
OperatingGuideTermixCompact28VX-FI
4.1.2Pipeconnectionsup
Removethetopblock.
Removethepipeplugsatthetopofthestation.
RemoveU-clamps.
Removepipes.Anglesandteesareturnedsothatpipescanbe
installedfromabove.
Installthepipes.Districtheatingsupplypipestobeinterchanged.
10
DEN-GT
VI.LZ.M1.02/LUK42363
DanfossDistrictEnergy
OperatingGuideTermixCompact28VX-FI
FitU-clamps.
Fitthepipeplugsatthebottomofthestation.
Fitthetopblock.
DanfossDistrictEnergy
VI.LZ.M1.02/LUK42363
DEN-GT
11
OperatingGuideTermixCompact28VX-FI
4.2Start-up
Start-up,Indirectheating
Filling:
1:Firstll
Whencarryingoutrstll,theheatexchangermustbeslowlylled
withwateruntilitreachesworkingpressure.
2:Pressuregauge
TheHEpressuregaugeindicatesthepressureoftheHEsystem.This
instructionmustbefollowedstrictly,toavoiddangeroussituations.
3:Supplyhose
AballvalvewithplugisinstalledintheHEreturnline.Tollthe
system,theballvalvemustrstbeclosed,theplugremovedand
asupplyhoseconnected.Onre-openingtheballvalve,system
llcancommence.
4:Pre-pressure
Whenllingthesystemwithwater,thepressuregaugeshouldbe
observedclosely.Theexpansionvesselissuppliedpre-pressurised
to0.5bar.Thepre-pressurerequiredateachsubstationwill
dependonsystemhead(thedistancebetweenthelowestand
highestpointinthesystem),forexample:
5:Fillingstop
Fillingmuststopwhenthepressuregaugeshowsapressure
approximately1-2barhigherthanthepre-pressuresetting.The
ballvalveisthenclosed,thehoseremovedandtheplugputback
in.
Start-up:
1:Pumpspeed
Setthepumptohighestspeedbeforestart-up.
2:Startpump
Startthepumpandheatthroughthesystem.
3:Openshut-offvalves
Theshut-offvalvesshouldthenbeopenedandtheunitobserved
asitentersservice.Visualcheckingshouldconrmtemperatures,
pressures,acceptablethermalexpansionandabsenceofleakage.
Iftheheatexchangeroperatesinaccordancewithdesign,itcanbe
puttoregularuse.
4:Ventsystem
Switchoffthepumpandventtheinstallationaftertheradiators
havebeenwarmedup.
5:Adjustpumpspeed
Setthepumptothelowestspeedconsistentwithcomfortand
electricityconsumption.
Normallythechange-overswitchissetinthemidposition(default).
Howeverforsystemswithunderoorheatingorsinglepipeloop
systems,itmaybenecessarytoturnthechange-overswitch
upwards.
Higherpumpspeedsareonlyusediftheheatingrequirement
increases.
Re-tightenconnections
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen
putintooperation,re-tightenALLconnections.
Pump
Thepumpmustbeswitchedoffduringsystemll.
Height(m)Pressure(bar)
050,5
5101,0
1015
1,5
15202,0
12
DEN-GT
VI.LZ.M1.02/LUK42363
DanfossDistrictEnergy
OperatingGuideTermixCompact28VX-FI
Underoorheating:
Pumpstopfunction
Ifthesubstationisusedinconnectionwithunderoorheating,the
circulationpumpmustbeconnectedtothepumpstopfunctionin
theunderoorheatingcontroller.Thepumpmustbestoppedif
allunderoorheatingcircuitsareclosed.
Warranty
Ifthisisnotpossible,thenowmustbecontinuedthroughthe
by-pass.Failingthis,thepumpwillbeatriskofseizureandany
remainingwarrantywillbewithdrawn.
Summeroperation:
Switchoffpump
Insummerthecirculationpumpmustbeswitchedoffandthe
shut-offvalvetoHEsupplyclosed.
Runningpumpbi-weekly
Itisrecommendedtostartupthecirculationpump(for2minutes)
onceamonthduringsummer;theshut-offvalveoftheHEsupply
mustbeshut.
Electroniccontroller
Mostelectroniccontrollerswillstartupthepumpautomatically
(pleasenotemanufacturer´sinstructions).
4.3Electricalconnections
Beforemakingelectricalconnections,pleasenotethe
following:
Safetynotes
Pleasereadtherelevantpartsofthesafetynotes.
230V
Thesubstationmustbeconnectedto230VACandearth.
Potentialbonding
Potentialbondingshouldbecarriedoutaccording
to60364-4-41:2007andIEC60364-5-54:2011.
Bondingpointonthemountingplatebelowrightcornermarked
withearthsymbol.
Disconnection
Thesubstationmustbeelectricallyconnectedsothatitcanbe
disconnectedforrepairs.
Outdoortemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto
directsunlight.Theyshouldnotbeplacedclosetodoors,windows
orventilationoutlets.
Theoutdoorsensormustbeconnectedtothestationonthe
terminalblockundertheelectroniccontrol.
Authorizedelectrician
Electricalconnectionsmustbemadebyanauthorizedelectricianonly.
Localstandards
Electricalconnectionsmustbemadeinaccordancewithcurrent
regulationsandlocalstandards.
DanfossDistrictEnergy
VI.LZ.M1.02/LUK42363
DEN-GT
13
OperatingGuideTermixCompact28VX-FI
5.0Design
5.1Design
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
A
Heatexchanger,HE
10
Circulatorpump
26
Pressuregauge,HE
F
Electroniccontroller
14
Sensorpocket,energymeter
27AActuator,HE
4
Safetyvalve,HE
20
Filling/drainvalve
27E
Actuator,Tank
9
Strainer
25
Pressuregaugewithballvalve
48
Airvent,manual
14
DEN-GT
VI.LZ.M1.02/LUK42363
DanfossDistrictEnergy
OperatingGuideTermixCompact28VX-FI
5.2Schematicdiagram
5.2.1SchematicdiagramTermixCompact28VX-FI
DH
Supply
HE
Supply
DH
Return
HE
Return
TRL
TFL
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
A
Heatexchanger,HE
14
Sensorpocket,energymeter
25
Pressuregaugewithballvalve
F
Electroniccontroller
16
Outdoorsensor
26
Pressuregauge
1
Ballvalve
18
Thermometer
27
Actuator
4
Safetyvalve
19
Surfacesensor
30
Flowcontrollerwithintegratedcontrolvalve
9
Strainer
20
Filling/drainvalve
48
Airvent,manual
10
Circulatorpump
24
Deliveredloosewithunit
DanfossDistrictEnergy
VI.LZ.M1.02/LUK42363
DEN-GT
15
OperatingGuideTermixCompact28VX-FI
5.2.2SchematicdiagramTermixCompact28VX-FIwithtankregulationmounted
DH
Supply
HE
Supply
DH
Return
HE
Return
DHW
HWC
DCW
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
A
Heatexchanger,HE
11
Domestichotwaterpump
25
Pressuregaugewithballvalve
E
Hotwatertankwithcoil
14
Sensorpocket,energymeter
26
Pressuregauge
F
Electroniccontroller
16
Outdoorsensor
27
Actuator
L
Borderofdelivery
18
Thermometer
29
2-waymotorizedvalve
1
Ballvalve
19
Surfacesensor
30
Flowcontrollerwithintegratedcontrolvalve
2
Singlecheckvalve
20
Filling/drainvalve
31
Differentialpressurecontroller
4
Safetyvalve
23
Ballvalve
44
Immersionsensor
9
Strainer
24
Deliveredloosewithunit
48
Airvent,manual
10
Circulatorpump
DHSupply:DistrictHeatingSupply
DHReturn:DistrictHeatingReturn
HESupply:HeatingSupply
HEReturn:HeatingReturn
TFL:
Tankowline
TRL:
Tankreturnline
DHW:
Domestichotwater
HWC:
Hotwatercirculation
DCW:
Domesticcoldwater
5.2.3Technicalparameters
Nominalpressure:
PN16
Max.DHsupplytemperature:
110°C
Brazingmaterial(HEX):
Copper
Heatexchangerstestpressure:30bar
Soundlevel:55dB
16
DEN-GT
VI.LZ.M1.02/LUK42363
DanfossDistrictEnergy
OperatingGuideTermixCompact28VX-FI
6.0Controls
6.1Heatingcircuit
6.1.1Differentialpressurecontroller
Thedifferentialpressurecontrollersmoothsouttheuctuationsin
pressurearrivingfromthedistrictheatingnetwork.Theoperating
pressureinthesubstationisthusheldsteady.
6.1.2Flowcontrollerwithintegratedcontrolvalve
Thecontrollerisaself-actingowcontrollerwithintegratedcontrol
valve.Thecontrollercloseswhensetmax.owisexceededand
canbeusedincombinationwithDanfosselectricalactuatorswith
orwithoutsafetyfunction.Springreturnmotorcanbeusedas
safetyfunctionbypowerfailure.
DanfossDistrictEnergy
VI.LZ.M1.02/LUK42363
DEN-GT
17
OperatingGuideTermixCompact28VX-FI
6.1.3Electric2–waymotorizedvalve
Actuatorswithorwithoutsafetyfunctionareavailablefor3-point
controls.Spring-returnactuatorscanbeusedtoprovidesafety
shut-offintheeventofpowerfailure.
6.1.4Electroniccontrol
Substationswithelectroniccontrolmustbesetinaccordancewith
manufacturer´sinstructions.
Wheretheroomtemperatureiscontrolledbyradiatorthermostats,
itisrecommendedthatthermostatsbesetforminimum
temperatureineachroom.
6.1.5Outsidetemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto
directsunlight.Theyshouldnotbeplacedclosetodoors,windows
orventilationoutlets.
18
DEN-GT
VI.LZ.M1.02/LUK42363
DanfossDistrictEnergy
OperatingGuideTermixCompact28VX-FI
6.1.6Circulatorpump
TheUPML,UPMXLcirculatorpumpsaredesignedforcirculating
liquidsinheatingsystemswithvariableows,internallycontrolled
withthreeproportionalpressurecurvesandthreeconstant
pressure/powercurvestobeselectedviauserinterface.
EuP2015Ready.
TheMAGNA3circulatorpumpsaredesignedforcirculatingliquids
inheatingsystemswithvariableowswhereyouwanttooptimise
thesettingofthepumpdutypoint,thusreducingenergycosts.
EuP2015Ready.
6.1.7GrundfosUPML/UPMXLinstructions
PP=Proportionalpressure(fastash)
CP=Constantpressure(slowash)
DanfossDistrictEnergy
VI.LZ.M1.02/LUK42363
DEN-GT
19
OperatingGuideTermixCompact28VX-FI
6.1.8HEpressuregauge
TheHEpressuregaugeindicatesthepressureoftheHEsystem.
6.2Other
6.2.1Safetyvalve
Thepurposeofthesafetyvalveistoprotectthesubstationfrom
excessivepressure.
Theblow-offpipefromthesafetyvalvemustnotbeclosed.The
blow-offpipeoutletshouldbeplacedsothatitdischargesfreely
anditispossibletoobserveanydrippingfromthesafetyvalve.
Itisrecommendedtochecktheoperationofsafetyvalvesat
intervalsof6months.Thisisdonebyturningthevalveheadin
directionindicated.
6.2.2Strainer
Strainersshouldbecleanedregularlybyauthorizedpersonnel.The
frequencyofcleaningwoulddependonoperatingconditionsand
themanufacturer’sinstructions.
20
DEN-GT
VI.LZ.M1.02/LUK42363
DanfossDistrictEnergy
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28

Danfoss Termix Compact 28 VX-FI Operating instructions

Type
Operating instructions

Danfoss Termix Compact 28 VX-FI is a heat exchanger unit for the production of heating in large buildings. It can be used for connection to indirect district heating in places where the district heating plant requires a hydraulic break on the plant side. It is also suitable for conversion to district heating when the secondary heating system is suitable to being connected to direct district heating or when a particularly effective security against leakage in the heating system is required. It is possible to connect a hot-water tank.

The substation is fitted with an efficient plate heat exchanger, which ensures the most favorable heat extraction and achieves optimum comfort and operating economy.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI