ICM Controls ICM315 Installation guide

  • Hello! I've reviewed the specification for the ICM315 Defrost Control. This document details the device's input voltage options, defrost timing, and output ratings. It also outlines how to use the test mode and mentions available defrost intervals. I'm ready to answer any questions you may have about the device.
  • What are the available input voltages?
    What is the fixed defrost time?
    How can I test the operation?
    What are the selectable intervals between defrost?
ICM
315
DEFROST CONTROL
WIRING DIAGRAM
SPECIFICATIONS
Input
•Voltage: 24, 120 or 240 VAC
•Frequency: 50-60 Hz
•PowerConsumption: 1 watt maximum
Time Delays
•Defrost: Fixed at 10 minutes (+/- 10%)
•IntervalBetweenDefrost:
– Pin selectable (30/45/90 minutes)
•TestTime: Short across “DEF” terminals
before power up (10 minutes = 7 seconds)
Output
•Rating:
–N.O.: 20 amps @ 240 VAC
–N.C.: 10 amps @ 240 VAC
•Type: Relay
•Form: SPDT
Mechanical
•Dimensions: 4.2” x 4.2”
•Mounting:
Surface mount using (4) #6 or
#8 screws, or plastic stand offs
Notes:
1) Disconnect sensor
to test operation
with warm
condenser coil.
2) Use only one
input voltage.
7313 William Barry Blvd.
North Syracuse, NY 13212
ICM CONTROLS 800.365.5525
www.icmcontrols.com LII052-2
COVER TO
BE USED
FOR 24V
UNITS
230V
110V
230V
110V
110/230 COM
24/110/230 VAC
1
N/O
3
N/C
2
COM 24 VAC
DEF SENSOR
30
4590
W
Input19-240 VAC
1
N/O
3
N/C
2
COM 24 VAC
Condenser
Fan
Defrost
Relay
24/110/230 VAC
1
N/O
3
N/C
2
COM 24 VAC
24 VAC
1
N/O
3
N/C
2
COM 24 VAC
110 VAC
1
N/O
3
N/C
2
COM 24 VAC
230 VAC
24 VAC 110 VAC
230 VAC Typical Outputs
230V
110V
230V
110V
230V
110V
230V
110V
TEMPERATURE
SENSOR
/