Buderus Logano G234X Operating Instructions Manual

Type
Operating Instructions Manual
Please read carefully before installing and servicing.
Operating Instructions
Gas boiler
Logano G234X
6 720 804 886-00.1T
Gas boiler
6 720 804 888 (2012/08) EN-US
UPON COMPLETION OF THE INSTALLATION THE INSTALLER MUST
INSTRUCT THE OWNER AND OPERATOR ON THE FUNCTIONALITY AND
THE PROPER OPERATION OF THE BOILER AND THE HEATING SYSTEM.
INSTALLER MUST REVIEW ALL SAFETY INSTRUCTIONS WITH THE
OWNER AND OPERATOR.
THIS MANUAL SHOULD BE HANDED TO THE QWNER AND OPERATOR OF
THE APPLIANCE.
DANGER!
The installation instructions included in this Manual are intended solely for
use by a trained and certified installer, service company or the gas supply
company. If the information in this manual is not followed, a fire or explosion
may result causing property damage, personal injury, or death.
Have installation and service performed by a trained and certified
installer or service company, or the gas supply company.
Buderus recommends signing a service and maintenance contract with
a trained and certified installer or service company that covers annual
servicing and condition-based maintenance. Proper maintenance is a
fundamental requirement for safe and efficient operation and long
service life.
The boiler must be serviced annually including the main burner, ignition
burner, the entire venting system, and the combustion air supply. All
parts that show any signs of damage or corrosion must be replaced
.

The owner and operator is responsible for the operational safety and
regulatory compliance of the heating system.
Improper installation, adjustment, alteration, service, or maintenance
can cause property damage, personal injury, or death. Refer to this
manual and consult a trained and certified installer or service company,
or the gas supply company before installation, service or maintenance.
Contents
Logano G234X – 6 720 804 888 (2012/08)2
Contents
1 Safety considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.1 Key to symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.2 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 Product information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1 Correct use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Certification and testing mark . . . . . . . . . . . . . . . . . . . . . 4
2.3 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.4 Product description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.1 Before operating the appliance . . . . . . . . . . . . . . . . . . . . 4
3.2 Checking the operating pressure, topping up
the boiler water, and purging air from the system . . . . . 4
3.2.1 Checking the operating pressure . . . . . . . . . . . . . . . . . . 4
3.2.2 Topping up the heating water and bleeding the system . 5
3.3 Start up instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.4 Shut down the heating system . . . . . . . . . . . . . . . . . . . . 7
3.4.1 Normal system shut-down . . . . . . . . . . . . . . . . . . . . . . . . 7
3.4.2 Emergency shut-down procedures . . . . . . . . . . . . . . . . . 7
3.5 Operating Tips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.6 Why is annual maintenance important? . . . . . . . . . . . . . 7
1 Safety considerations
1.1 Key to symbols
Warnings
The following keywords are defined and can be used in this document:
NOTICE indicates that property damage may occur.
CAUTION indicates that personal injury may occur.
WARNING indicates that severe personal injury may occur.
DANGER indicates that severe personal injury or death may occur.
Important Information
Additional symbols
1.2 Safety instructions
If you hear gas leaking
Leave the building immediately.
Prevent others from entering the building.
Notify the police and fire department from outside the building.
From outside the building, call the gas supply company and a trained
and certified installer or service company.
If you smell gas
Turn off the gas shut-off valve.
Open windows and doors.
Do not touch any electrical switch, telephone, and do not use outlets.
Extinguish all open flames.
▶Do not smoke.
Do not use lighters.
Warn all occupants of the building that they need to leave the building.
Do not ring doorbells.
Notify the police and fire department from outside the building.
From outside the building, call the gas supply company and a trained
and certified installer or service company.
Warnings in this document are identified by a warning
triangle printed against a grey background. Keywords at
the start of a warning indicate the type and seriousness
of the ensuing risk if measures to prevent the risk are not
taken.
Important information for the proper use of the boiler is
also provided in this manual. You will find the information
with a symbol shown on the left and bordered by
horizontal lines above and below the text.
Symbol Explanation
Sequence of steps
Cross-reference to other points in this document or to
other documents
Listing/list entry
Listing/list entry (2nd level)
Table 1
1
Safety considerations
Logano G234X – 6 720 804 888 (2012/08) 3
If you smell flue gas
Switch off the heating system by shutting off the emergency shut-off
switch.
Open windows and doors.
Call a trained and certified installer or service company
DANGER: Risk of fatal injury from failing to consider your own
safety
Never risk your own life. Your own safety must always take the highest
priority.
DANGER: Risk of fire when soldering and brazing
Take appropriate protective measures when soldering and brazing
around combustible and flammable material.
DANGER: Risk of personal injury or death from flue gas poisoning
Do not install a thermostatic flue gas damper downstream of the draft
hood.
Do not tamper with, remove, or attempt to repair the blocked vent
switch.
When replacing the blocked vent switch, install the new part in the
original location.
A blocked vent switch tripping more than once indicates a problem
with the venting system or chimney which must be repaired
immediately.
Ensure none of the vent pipes and chimneys are damaged or blocked.
Connect only one appliance to each venting system or chimney.
The venting system must not feed into or route through another air
extraction duct.
The venting system must be inspected annually. All parts that show
any signs of damage or corrosion must be replaced.
DANGER: Risk of personal injury or death from explosion
Work on gas components may only be carried out by a trained and
certified installer or service company.
Appliance installation, the connection of gas and vent piping, initial
commissioning, electrical connections, and service and maintenance
must only be carried out by a trained and certified installer or service
company.
DANGER: Risk of personal injury or death from flue gas poisoning
Never close off or reduce the size of the combustion air openings.
The boiler must not be operated until any obstructions have been
removed.
DANGER: Risk of personal injury or death from fire
Do nut use flammable or combustible material in the boiler room.
It is recommended not to store any items within 16 inches (415 mm)
of the appliance.
DANGER: Risk of personal injury or death from electric shock
Before removing the front panel, disconnect the heating system from
the electrical power supply by shutting off the emergency shutoff
switch or the heating system circuit breaker.
It is not enough to switch off the control panel. Power to the panel
must be disconnected.
Ensure that the power is not restored unintentionally by following
proper lock out/tag out procedures.
Only qualified electricians are permitted to carry out electrical work.
DANGER: Safety devices
Never shut off safety valves.
Hot water may escape from the safety valve at any time when the
appliance is running.
DANGER: Risk of personal injury or death after a flood
Do not attempt to operate an appliance if any part of it has been under
water.
An appliance that was subject to flooding must be replaced.
CAUTION: Appliance damage from contaminated combustion air
Keep the combustion air free of corrosive substances, e.g.
halogenated hydrocarbons from painting operations or beauty
salons.
Keep combustion air free from dust and lint, e.g. from laundry or
agricultural operations.
If clean room air is not available, fresh outdoor combustion air must be
provided.
NOTICE: Risk of appliance damage from improper operation of the
boiler
Only use the boiler for its intended purpose.
Only operate the boiler if it has been installed and maintained per the
instructions provided in the Installation Manual.
Do not attempt to operate an appliance if any part of it is not in
working order or is damaged.
Use only original spare parts. The use of parts not supplied by the
manufacturer may cause damage to the boiler, other property and
personal injury. Also, boiler damage caused by the use of
unauthorized parts is not covered by the warranty.
NOTICE:
The installation must comply with all applicable national, state, and
local codes, rules, and regulations.
The operator is responsible for the operational safety and regulatory
compliance of the heating system.
In the Commonwealth of Massachusetts, the appliance must be
installed by a licensed plumber or gas fitter.
NOTICE:
Upon completion of the installation, these instructions should be
handed to the owner and operator of the appliance.
The installer must instruct the owner and operator on the functionality
of the components and the proper operation of the boiler and the
heating system.
The boiler must be serviced annually including the main burner,
ignition burner, the entire venting system, and the combustion air
supply. All parts that show any signs of damage or corrosion must be
replaced.
2
Product information
Logano G234X – 6 720 804 888 (2012/08)4
2 Product information
To ensure safe, economical and environmentally friendly use of the
heating system, we recommend that you carefully read the safety
instructions and operating instructions.
These instructions provide the operator of the heating system with an
overview of the use and operation of the boiler.
2.1 Correct use
The boiler is designed for heating central heating system water and
indirect provision of domestic hot water (e.g. via a hot water storage
tank) in residential buildings or apartment buildings. Any other purpose
is considered improper use.
2.2 Certification and testing mark
This appliance has been tested and meets the basic standards for the US
and Canadian markets.
2.3 Disposal
Dispose of boiler packaging in an environmentally-responsible
manner.
All heating system components that have to be replaced should be
disposed of in environmentally-responsible manner at an authorized
disposal site.
2.4 Product description
The G234X model boiler is a low temperature atmospheric gas-fired
boiler.
The boiler consists of:
Ignition module and boiler temperature controller
Boiler jacket and front door
Boiler block with insulation
•Gas burner
The ignition module and boiler temperature controller monitor and
control all electrical components of the boiler.
The boiler jacket prevents energy loss and acts as soundproofing.
The boiler block transfers the heat generated by the burner to the boiler
water. The insulation prevents energy loss.
Fig. 1 G234X boiler
[1] AquaSmart
TM
[2] Burner control unit
[3] Boiler block with thermal insulation
[4] Boiler casing
[5] Burner
[6] Front panel of boiler
3 Operation
3.1 Before operating the appliance
Before starting up the appliance, make sure that
the operating pressure is sufficient
the fuel supply has been turned on at the main shut-off valve, and
the heating system emergency shutoff switch is in the ON position.
3.2 Checking the operating pressure, topping up
the boiler water, and purging air from the system
The water used for filling the heating system loses a substantial amount
of volume in the first few days due to the release of its gas content. This
causes air pockets to form and the heating water starts to make noises.
With new heating systems, check the operating pressure daily at first,
topping off the heating water and bleeding the radiators if needed.
Later on, check the operating pressure monthly, topping off heating
water and purging the boiler and radiators if needed.
3.2.1 Checking the operating pressure
Your heating contractor will have set the system to the required
operating pressure of at least 15 psi (1 bar) and entered the setting in
Tab. 2, page 5.
Read the current operating pressure and temperature from the
temperature/pressure gauge.
If the temperature/pressure gauge needle drops below the minimum
pressure marker of 15 psi (1 bar), the operating pressure is too low.
Add water to the system.
The boiler is fully functional with the factory-installed
AquaSmart
TM
.
If you are not comfortable performing the following
operations contact you trained and certified installer.
6 720 804 886-01.1T
3
Operation
Logano G234X – 6 720 804 888 (2012/08) 5
Fig. 2 Pressure/temperature gauge
3.2.2 Topping up the heating water and bleeding the system
Ask your heating contractor to show you where the boiler fill & drain
valve for topping off the heating system is located.
Slowly fill the heating system. Observe the temperature/pressure
gauge while filling.
3.3 Start up instructions
For your safety, read before start up.
WARNING: Health risk from contaminated drinking
water!
It is imperative that you observe all regulations and
standards applicable in your country regarding
prevention of drinking water contamination.
CAUTION: Risk of damage to system due to temperature
stress!
If you fill the heating system when it is hot, the resulting
temperature stress can cause stress cracks. The boiler
will then leak.
Only top off the heating system when it is below a
supply temperature of 100 °F (38 °C).
CAUTION: Risk of system damage due to frequent
topping off!
If you have to top off the boiler water once a month, the
heating system may suffer damage from corrosion or
scale buildup, depending on the water quality.
Ask your trained and certified installer if the local
water can be used untreated or whether it needs to be
treated.
Notify your heating contractor if you find you need to
top off your heating system once a month.
Operating pressure
Design operating pressure
(optimum setting) _____________ psi
Maximum heating system operating
pressure
(standard = 30 psi/2bar) _____________ psi
Table 2 Operating pressure (entered by system installer)
7 747 010 720-24.2RS
DANGER: Risk of fatal injury due to not observing the
start-up instructions and resulting incorrect operation!
If these instructions are not followed, a fire or
explosion may result.
DANGER: Risk of explosion!
If you smell gas there is a danger of explosio n.
Close the gas shut-off valve.
Open windows and doors.
Do not operate any electrical switches or equipment
such as telephones, power plugs and doorbells.
Extinguish all open flames. Do not smoke. Do not use
lighters.
Warn all occupants of the building, but do not ring
doorbells.
If you can actually hear gas escaping, leave the
building immediately. Prevent others from entering
and notify the police and fire department from
outside the building.
From outside the building, call the gas utility
company and approved heating contractor.
WARNING: Risk of system damage!
This unit is fitted with an ignition module that
automatically starts the pilot burner.
Do not attempt to ignite it manually.
WARNING: Risk of system damage!
This test must also be conducted at floor level, because
some types of gas are heavier than air and may
accumulate at floor level.
Check for an odor of gas around the heating system.
WARNING: Risk of system damage!
Any attempt to use force or to repair the valve may cause
a fire or explosion.
Switch on the ON/OFF switch on the gas valve by
hand only.
Never use a tool as assistance.
If you cannot actuate the ON/OFF switch on the gas
valve by hand, do not attempt to repair it.
Contact a trained and certified installer.
WARNING: Risk of system damage!
Do not operate the appliance if any part is under
water.
Contact a trained and certified installer immediately.
3
Operation
Logano G234X – 6 720 804 888 (2012/08)6
STOP! First read the safety instructions on page 5 of these instructions.
Set thermostat to the lowest value.
Shut off the heating system from the power supply.
Close main gas shut-off.
Unscrew left and right screws [1] in the side panels, lift front panel of
boiler [3] up, pull outward and remove to the front.
Fig. 3 Remove front panel of boiler
[1] Locking screws
[2] Boiler jacket
[3] Front panel of boiler
Turn the gas valve ON/OFF dial [1] clockwise to the OFF position. Do
not use force.
Wait five (5) minutes until all gas residues have dissipated. Finally
check whether there is any smell of gas, including at floor level. If you
smell gas, STOP! Follow instructions in section “B” of the safety
instructions ( page 5).
If you do not smell gas, go to the next step.
Turn gas valve ON/OFF dial[1] counterclockwise to ON position. Do
not use force.
Replace front panel of boiler ( Fig. 3).
Open main gas shut-off.
Switch on electric power to heating system.
Fig. 4 Gas valve
[1] ON/OFF dial (at OFF position)
Set thermostat to desired room temperature.
If the heating system does not start up, follow the instructions above
for turning off the gas supply. After that, inform a customer service
technician or the gas utility company.
Flame roll-out switch
The boiler is equipped with a flame roll-out switch. If the flue duct in the
boiler is blocked, the flame roll-out switch responds.
Do not try to light the boiler in this case. Inform a qualified service
company. The flue duct in the boiler must be checked for blockage and
the flame baffle replaced.
The flame roll-out switch is for one-time use only. Do not try to use it
again.
Flue gas monitoring switch
The boiler is equipped with a flue gas monitor. If the flue gas escape of
the boiler is blocked the flue gas monitoring switch reacts. The flue gas
monitoring switch is mounted directly on the draft hood.
Fig. 5 Gas valve
[1] ON/OFF button (at OFF position)
Do not try to light the boiler if the flue gas escape of the boiler is blocked.
Inform a qualified service company. The flue gas path must be searched
for blockages. In order to start the boiler up again, the flue gas
monitoring switch must first be reset.
WARNING: Risk of fatal injury due to not observing the
start-up instructions and resulting incorrect operation!
If these instructions are not followed, a fire or
explosion may result.
This unit is fitted with an ignition module that
automatically starts the pilot burner. Do not attempt to
ignite it manually.
3
Operation
Logano G234X – 6 720 804 888 (2012/08) 7
3.4 Shut down the heating system
3.4.1 Normal system shut-down
Switch off the on/off switch ("OFF" position). This switches off the
boiler and all its components (e.g. burner).
Further shut-down procedure refer to AquaSmart
TM
documentation.
Shut off fuel supply by closing main valve.
Fig. 6 Heating system shut-down
[1] ON/OFF switch (emergency shut off switch)
3.4.2 Emergency shut-down procedures
Action in an emergency
Never risk your own life. Your own safety must always take the highest
priority.
Shut off fuel supply by closing main valve.
Disconnect the heating system from the electrical power supply by
means of the emergency shutoff switch or the appropriate circuit
breaker.
3.5 Operating Tips
The right fuel
To ensure it operates properly, the heating system requires fuel of the
correct type and grade.
Consult your trained and certified installer if you want to convert your
heating system to a different fuel or run the boiler on fuel with different
specifications.
Notes about the boiler room
3.6 Why is annual maintenance important?
Heating systems should be maintained annually for the following
reasons:
to maintain high efficiency,
to operate the system economically (low fuel consumption),
to maintain the cleanest combustion.
CAUTION: Risk of system damage due to freezing!
If the heating system has been switched off, it may
freeze in cold weather conditions.
Protect your system from freezing by draining the
boiler, the heating system and hot water pipes at the
lowest point.
Use the heating system emergency shut-off switch
located outside the boiler room or the heating system
circuit breaker for emergency shutdown.
CAUTION: Risk of system damage from use of incorrect
fuel!
Only use the fuel specified. The correct fuel is entered
in Tab. 3 by the heating system installer.
Only use this fuel type
____________________________
____________________________________________ Stamp/Date/Signature
Table 3 Fuel to be used (entered by heating system installer)
CAUTION: Risk of boiler damage from contaminated
combustion air!
Keep the combustion air free of corrosive substances
(e. g. halogenated hydrocarbons that contain
chlorine or fluorine compounds). This will help
prevent corrosion.
Prevent heavy accumulation of dust.
CAUTION: Risk of system damage from water!
In the event of severe risk of flooding, disconnect the
boiler from its power supply and shut off the fuel
supply before water enters the boiler room.
All parts that have been in contact with water must be
replaced by a trained and certified installer.
CAUTION: Risk of damage to system due to lack of or
inadequate cleaning and maintenance!
Have your heating system inspected, cleaned and
maintained by a trained and certified installer once a
year.
We recommend you sign a contract covering an
annual inspection and maintenance.
United States and Canada
Bosch Thermotechnology Corp.
50 Wentworth Avenue
Londonderry, NH 03053
Tel. 603-552-1100
Fax 603-584-1681
www.buderus.us
U.S.A.
Products manufactured by
Bosch Thermotechnik GmbH
Sophienstrasse 30-32
D-35576 Wetzlar
www.buderus.com
Bosch Thermotechnology Corp. reserves the right
to make changes without notice due to continuing
engineering and technological advances.