of the phase-locked loop is
k
2 Hz. The input signal
waveform must enter the limits of logical
"0" and logical
"1
"
(each for a duration of at least 50 ns) once per cycle.
As a check of proper phase-lock operation, follow
paragraph 6.8 of the Conformance Test Procedure.
Failure to lock could be due to an excessive difference
between the internal and external reference frequencies.
3.3.4 Phase-Locking Two or More Instruments
.
(51 00 and 51 10)
To phase-lock two or more instruments, use the 8 MHz
reference output from a master instrument as an exter-
nal 8 MHz clock input to the slave
instrument(s). All slave
instrument phase-locked loops are bypassed because
they are driven directly by the single crystal reference
of the master instrument, which itself may be phase-
locked to an external
1 MHz signal, or driven by an 8 MHz
input signal.
The
lnput Reference Selector Jumper located inside the
unit on the main board (assembly drawing
02-004-31 00)
must be in the INT position for the master unit, and EXT
for the slave
unit(s).
3.4 OUTPUT SIGNALS
Main output and reference signals are available from
Models
51 00 and 51 10. The main outputs are fixed and
variable (Model
51 00 only) amplitude sine waves, at the
programmed frequency. Reference frequency outputs
are
1 MHz square or
8
MHz pulse signals derived from
the system clock.
3.4.1
Model 51 00 Main Outputs
Main output signals available from the Model 51 00 are
fixed amplitude
(I Vp-p) and variable amplitude (1 OVp-p
maximum) sine waves, at the programmed frequency.
3.4.1
.I
Model 51 00 Fixed Amplitude Outputs
The Model 5100 front and rear panel jacks labeled
1 'VOLT
P-P
and FXD OUT, respectively, provide sine
wave signals (at the programmed frequency) which may
be used for scope synchronization or frequency monitor-
ing. The source impedance is 50R and the amplitude is
nominally
1 Vp-p with no load, or 0.5 Vp-p into 50R. The
LEVEL and ATTENUATION settings have no control of
the output amplitude.
3.4.1.2 Model 51 00 Variable Amplitude Outputs
The Model 51 00 front and rear panel jacks labeled OUT-
PUT and VAR OUT, respectively, provide the main sine
wave output signal (at the programmed frequency) from
the instrument. The source impedance is
509 and the
maximum amplitude is
10 Vp-p with no load, or 5 Vp-p
into
50R, as determined by the LEVEL and ATTENUA-
TION control settings.
3.4.2 Model 51 10 Main Outputs
Main output signals available from the Model 51 10 are
fixed amplitude
1 Vrms, (1 OVp-pfor units equipped with
Option 004) sine waves, at the programmed frequency.
3.4.2.1 Model 51 10 Fixed Amplitude Outputs
The Model 51 10 output signal (at the programmed fre-
quency) is available from the front panel BNC jack
labeled OUTPUT 50R and
from the rear panel jack
labeled FXD OUT. The source impedance is 50R and the
amplitude is nominally
1 Vrms with no load, or 0.5 Vrms
into 50R.
For units equipped with Option 004, the OUTPUT
509
and FXD OUTsignal amplitudes are increased to 10 Vp-p
(3.6 Vrms) with no load, or
5Wp-p into 509 (nominally).
Option 004 also increases harmonic components (see
paragraph
1.2.5).
3.4.3
Models 51 00 and 51 10 Reference Output
Signals
The rear panel
REF
OUT signal can be either a 1 MHz
square-wave or an 8 MHz pulse waveform, as deter-
mined by the Output Reference Selector Jumper shown
in drawing
02-004-31 00, Mainboard Assembly. For the
Model
51 00, the source can be an
8
MHz signal from
either the internal
8
MHz reference (Input Reference
Selector Jumper set to INT), or an external
8
MHz signal
(jumper set to EXT). The Model
51 10 works identically
to the
51 00, except that no 8 MHz REF OUT signal is
generated if the
8
MHz reference signal is from an
external source. The instrument is shipped with the Out-
put Reference Selector Jumper in the
1 MHz position.
The output is a buffered
TTL
signal capable of driving
30 standard loads.
3.5 REMOTE SWITCH AND INDICATOR (MODEL
51 00 ONLY)
The Model 51 00 is always operating in either the local
or remote mode, as indicated by the amber REMOTE
lamp on the front panel. The REMOTE switch must be
in the OUT position for local mode operation. Remote
mode operation may be effected in two ways:
1. By setting the REMOTE switch to the IN position.
2. By setting the programming line REMOTE to the
proper state. Thus, the unit may be called into the
remote mode by either front- or rear-panel control.
Local mode operation requires that neither
(1) or (2)
above be present.
3.6 LOCAL MODE OPERATION (MODEL 51 00 ONLY)
All local frequency and attenuation control is derived
from the front panel switches.