14
into consideration.
In the outside suction version, the diameter of the fume discharge duct must be no smaller than
the cooker hood connection. We recommend using pipes with 150 mm diameter.
If using pipes with 120 mm diameter, install attached “reducer (150-120 mm)” to the discharge
hole of the cooker hood.
When screwing or installing the metallic duct to the wall which metal lath, wire lath or metal
plate is lined, do not let them come in contact with metal part. Otherwise, it may cause electric
leakages or fi res.
In the horizontal sections, the duct must slope slightly (around 10%) upwards, so at to better
convey the air outside of the room. The duct must be installed not to bend it in the immediate
vicinity of the discharge hole. Otherwise, the return valve will get stuck with the duct, and will
not work for the exhaust properly. Reduce curves to the bare minimum, and check that the
length of the ducts is also the bare minimum.
Comply with the current regulations on air discharge into the atmosphere.
If other appliances that use gas or other fuels are being used at the same time (boiler, stove,
fi replaces, etc.), make sure the room where the fumes are extracted is well ventilated, in com-
pliance with the current regulations.
Assembly instructions: see section “K” of the booklet.
ELECTRICAL CONNECTIONS
D
(Section reserved for qualified installers)
WARNING!
Before doing any work inside the cooker hood, disconnect the appliance from the mains
power supply.
Check that the wires inside the cooker hood are not disconnected or cut; if this is the case,
contact your nearest service centre. The electrical connections must be performed by quali-
fi ed personnel.
The connections must be performed in compliance with the legal standards in force. Check
that the relief valve and the electrical system are able to support the load of the appliance (see
the technical specifi cations in point B).
This appliance is supplied with a cable without plug. Standardized plugs must be used, keeping
in mind that:
- the yellow-green wire must be used for the earth,
- the blue wire must be used for the neutral,
- the brown wire must be used for the phase; the cable must not come into contact with hot
parts (over 70°C).
- fi t a plug that is suitable for the load to the power cable, and connect it to a suitable power
outlet.
Please refer to a qualifed person. (See technical specifi cations in point B).
WARNING!
The supply cord must be set properly not to be damaged. The manufacturer declines all li-
ability if the safety standards are not observed.
E
HOOD VERSION WITH EXTERNAL EXHAUST
In this version the kitchen fumes and vapours are conveyed outside through an exhaust pipe.
The exhaust conveyor that protrudes from the upper part of the hood must be connected with
the pipe that conducts the fumes and vapours in an external output.
In this version, charcoal fi lters supplied on the hoods must not be used.
When the kitchen hood is used simultaneously with other appliances that use gas or other
fuels, the room must have suffi cient ventilation according to the standards in force.