When outdoor unit is connected to factory–approved indoor unit,
outdoor unit contains system refrigerant charge for operation with
AHRI rated indoor unit when connected by 15 ft. (4.57 m) of
field–supplied or factory accessory tubing. For proper unit
operation, check refrigerant charge using charging information
located on control box cover and/or in the Check Charge section of
this instruction.
IMPORTANT: Maximum liquid–line size is 3/8–in. OD for all
residential applications including long line.
IMPORTANT: Always install the factory–supplied liquid–line
filter drier. Obtain replacement filter driers from your distributor or
branch.
INSTALLATION
IMPORTANT: Effective January 1, 2015, all split system and
packaged air conditioners must be installed pursuant to applicable
regional efficiency standards issued by the Department of Energy.
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and
wear appropriate protective clothing and gloves when handling
parts.
CAUTION
!
Check Equipment and Job Site
Unpack Unit
Move to final location. Remove carton taking care not to damage
unit.
Inspect Equipment
File claim with shipping company prior to installation if shipment
is damaged or incomplete. Locate unit rating plate on unit corner
panel. It contains information needed to properly install unit.
Check rating plate to be sure unit matches job specifications.
Install on a Solid, Level Mounting Pad
If conditions or local codes require the unit be attached to pad, tie
down bolts should be used and fastened through knockouts
provided in unit base pan. Refer to unit mounting pattern in Fig. 2
to determine base pan size and knockout hole location.
For hurricane tie downs, contact distributor for details and PE
Certification (Professional Engineer), if required.
On rooftop applications, mount on level platform or frame. Place
unit above a load–bearing wall and isolate unit and tubing set from
structure. Arrange supporting members to adequately support unit
and minimize transmission of vibration to building. Consult local
codes governing rooftop applications.
Roof mounted units exposed to winds above 5 mph may require
wind baffles. Consult the Service Manual – Residential Split
System Air Conditioners and Heat Pumps for wind baffle
construction.
NOTE: Unit must be level to within ±2° (3/8 in/ft,9.5 mm/m)
per compressor manufacturer specifications.
Elevate Unit
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or
improper operation.
Unit must be kept free of an accumulation of water and/or ice in
the basepan.
CAUTION
!
Elevate unit per local climate and code requirements to provide
clearance above estimated snowfall level and ensure adequate
drainage of unit. If using accessory support feet, use installation
instructions from kit for installation.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or
improper operation.
To prevent damage to the unit, ensure that it is located with the
supports such that the unit is stable in all circumstances including
adverse conditions.
CAUTION
!
Clearance Requirements
When installing, allow sufficient space for airflow clearance,
wiring, refrigerant piping, and service. Allow 24 in. (609.6 mm)
clearance to service end of unit and 48 in. (1219.2 mm) (above
unit. For proper airflow, a 6–in. (152.4 mm) clearance on 1 side of
unit and 12–in. (304.8 mm) on all remaining sides must be
maintained. Maintain a distance of 24 in. (609.6 mm) between
units or 18 in. (457.2 mm) if no overhang within 12 ft. (3.66 m).
Position so water, snow, or ice from roof or eaves cannot fall
directly on unit.
NOTE: 18” (457.2 mm) clearance option described above is
approved for outdoor units with wire grille coil guard only .
Units with louver panels require 24” (609.6 mm) between units.
On rooftop applications, locate unit at least 6 in. above roof
surface.
3/8–in. (9.53 mm) Dia.
Tiedown Knockouts in
Basepan(2) Places
View From Top
UNIT BASE PAN
Dimension in. (mm)
TIEDOWN KNOCKOUT LOCATIONS in. (mm)
A B C
23 X 23
(585 X 585)
7–3/4 (196.8) 4–13/32 (111.9) 18–1/32 (457.9)
26 X 26
(660 X 660)
9–1/8 (231.8) 4–7/16 (112.7) 21–1/4 (539.8)
31–1/2 X 31–1/ 2
(800 X 800)
9–1/8 (231.8) 6–9/16 (166.7) 24–11/16 (627.1)
35 X 35
(889 X 889)
9–1/8 (231.8) 6–9/16 (166.7) 28–7/16 (722.3)
A05177
Fig. 2 – Tiedown Knockout Locations
Operating Ambient
The minimum outdoor operating ambient in cooling mode without
accessory is 55°F (12.78°C), and the maximum outdoor operating
ambient in cooling mode is 125°F (51.67°C). The maximum
outdoor operating ambient in heating mode is 66 °F (18.89°C).
Check Defr ost Thermostat
Check defrost thermostat to ensure it is properly located and
securely attached. There is a liquid header with a distributor and
feeder tube going into outdoor coil. At the end of the one of the
feeder tubes, there is a 3/8 in. O.D. stub tube approximately 2 in.
(50.8 mm) long (see Fig. 3). The defrost thermostat should be
located on stub tube. Note that there is only one stub tube used
with liquid header , and on most units it is the bottom circuit.