Service Communicator
Subject: S Model Installation Use and Care Manual Corrections
S Model Ice Machine Installation, Use and Care
Manual part number 80-1478-3 has incorrect
information listed.
Page 2-4 - Heat of rejection is incorrectly listed
for the S850 and S1000 ice machines
• The correct heat of rejection for the S850 =
12,000 average Btu/hr 18,000 Peak Btu/hr
• The correct heat of rejection for the S1000 =
16,000 average Btu/hr 22,000 Peak Btu/hr
Page 2-11 - The incorrect Remote Single Circuit
Condenser is listed for the S1000 ice machine.
• The correct remote condenser is JC0895.
Page 2-16 - Heat of rejection, internal condenser
volume and refrigerant charge are incorrect for
the S850 and S1000.
• The correct heat of rejection for the S850 =
12,000 average Btu/hr 18,000 Peak Btu/hr
• The correct heat of rejection for the S1000 =
16,000 average Btu/hr 22,000 Peak Btu/hr
• The correct internal volume for the S850 =
0.045 minimum, 0.060 maximum.
• The correct internal volume for the S1000 =
0.045 minimum, 0.060 maximum.
S Model QuietQube Ice Machine Installation, Use
and Care Manual part number 80-1504-3 has
incorrect information listed.
Page 2-12 - The linesets for the S1070C ice
machine head section and CVD1085 condensing
unit are incorrect.
• The correct linesets are RC-21, RC-31 or
RC-51 (5/8” suction Line, 3/8” Liquid Line).
These two manuals along with all current Installation, Use and Care, Parts and Service Manuals are
available on our website at www.manitowocice.com
SC158-04
2/04