Trane BAYSENS924 Quick Programming Manual

Type
Quick Programming Manual

Trane BAYSENS924 is a thermostat and remote sensor designed to work with the Trane Voyager EFlex unit. It allows for precise temperature control and scheduling, helping to optimize energy efficiency and comfort in commercial buildings. With its advanced features, the BAYSENS924 offers:

  • Customizable programming: Create detailed schedules to align with your business hours and occupancy patterns, ensuring the right temperature at the right time.

  • Remote monitoring: Access and adjust temperature settings remotely, providing flexibility and convenience for managing multiple zones or buildings.

Trane BAYSENS924 is a thermostat and remote sensor designed to work with the Trane Voyager EFlex unit. It allows for precise temperature control and scheduling, helping to optimize energy efficiency and comfort in commercial buildings. With its advanced features, the BAYSENS924 offers:

  • Customizable programming: Create detailed schedules to align with your business hours and occupancy patterns, ensuring the right temperature at the right time.

  • Remote monitoring: Access and adjust temperature settings remotely, providing flexibility and convenience for managing multiple zones or buildings.

RQC-2017-021 Version-1 1/9/18
1
of 8
Page



1. 
2. 
3. 
4. 
Operator Quesons:
1. 

2. 
3. 
4. 
Note: The thermostat accounts for the outside temperature and will adjust to hit the desired temperature at the
desiredme.
Energy Tip: Every temperature degree increases energy use by approximately 3% and impacts the electric and
naturalgasbills.Nightmetemperaturesetbacksarecricaltoreduceoperangcosts.
Typical Non-Breakfast Restaurant Schedule:



ItiscricaltohavetheHVACUnitrunninginOccupiedMode(FanON)duringmeswhentheKitchenExhaustFans
areoperang.
Trane
2018 BAYSENS924 Thermostat Programming - Quick Reference
Dining Room
Event Time
DR - Open
_________________________AM
DR - Closed
_________________________PM
DR - Clean up Complete
___________________AM/PM
Kitchen
Event Time
Prep Start
_________________________AM
Drive Thru Open
_________________________PM
Drive Thru Closed
___________________AM/PM
Clean Up Complete
___________________AM/PM
Dining Room
Status
Recommended
Set Point
Set Point
Unoccupied
Cooling 78
o
F
_________________________
Occupied
Cooling 72
o
F
_________________________
Occupied
Heating 72
o
F
_________________________
Unoccupied
Heating 60
o
F
_________________________
Kitchen
Status
Recommended
Set Point
Set Point
Unoccupied
Cooling 78
o
F
_________________________
Occupied
Cooling 72
o
F
_________________________
Occupied
Heating 72
o
F
_________________________
Unoccupied
Heating 60
o
F
_________________________
RQC-2017-021 Version-1 1/9/18
2
of 8
Page
Crical:FanAutoisonlyusedwhentherestaurantisclosedandthehoodsareturned OFF
Follow programming instrucons in the Installer Guide
Owner Project Requirements:
 

 

 

 
Installer: Aercompleteingtheprogrammingofthethermostat,lockthe
thermostatusingapassword.ProvidethepasswordandInstallaon,
OperaonandMaintenanceManualtotheFacilityManager
Trane EFLEX - Human Interface Display


Date & Time
 
 
 
 
Typical Schedule
Dining Room (Non-Breakfast Restrauant)
Event Start End Heating Cooling Thermostat Status
DR - Drive T Open
12:01am 1:00am 60 78
Occupied (Fan ON)
DR - Closed
1:00am 7:00am 60 78
Unccupied (Fan Auto)
DR - Pre-Open
7:00am 10:30am 68 72
Occupied (Fan ON)
DR - Open
10:31am 10:00pm 68 72
Occupied (Fan ON)
DR - Drive T Open
10:01pm 11:59pm 68 72
Occupied (Fan ON)
Typical Schedule
Kitchen (Non-Breakfast Restrauant)
Event Start End Heating Cooling Thermostat Status
KN - Open
12:01am 2:00am 68 72
Occupied (Fan ON)
KN - Closed
2:01am 7:00am 60 78
Unccupied (Fan Auto)
KN - Open
7:00am 11:59pm 68 72
Occupied (Fan ON)
Trane
2018 BAYSENS924 Thermostat Programming - Quick Reference
RQC-2017-021 Version-1 1/9/18
3
of 8
Page



Conguring Human Interface to READ ONLY MODE
 
 
 
 
 
ThescreenwillreadDISPLAYREADONLYMODE
Press and hold down a finger
where indicated.
1. Sensor Address: 002
2. Unit Address: 003
Note: Unit Address must match BCI board switches
BAYSENS
924
Programming Quick Reference
Refer to Interface Flowchart in the Installer Guide starting on Page 7
Access Programming Screens
1/2 - Network Settings Screen
Trane
2018 BAYSENS924 Thermostat Programming - Quick Reference
RQC-2017-021 Version-1 1/9/18
4
of 8
Page
1. Eco. Enable: ON
Opt. Strart/Stop ON
Shed Perm. OFF
Note: Critical to have schedule optimization so that
the space will reach occupied space temperature
at start of occupied period
2/4 - Configuration Screen
3/4 - Configuration
Trane
2018 BAYSENS924 Thermostat Programming - Quick Reference
Main Password: Set to desired
4
digit #
Hold down button to advance numbers
User Password: Set to desired
4
digit #
Hold down button to advance numbers
Schedule Menu: Disable
Cali. Temp: 0.0
o
F
Temp. occ time: 60 min
• Set temporary occupied time to 60 minutes to allow for a
1 hour override by the crew.
• Disable - Schedule is not accessible to crew. Clock is visible.
Main Password:___________________________________
User Password:___________________________________
1/4 - Configuration Screen
RQC-2017-021 Version-1 1/9/18
5
of 8
Page
Trane
2018 BAYSENS924 Thermostat Programming - Quick Reference
USER HMI: 1
Color: Blue
Units: F
1/2 - Display Screen
2/2 - Display
Unocc. Cool: 78
o
F
Occ. Cool: 72
oF
Occ. Heat: 68
oF
Unocc. Heat: 60
o
F
Note: Adjust set points to desired operator temperatures
Min. Dead Band: 2
oF
Max. Heating: 72
oF
Min. Cooling: 68
o
F
Note: Adjust maximum set points based on operator
desires. It is critical to restrict maximum heating
and cooling points
1/2 - Set Point Screen
2/2 - Set Point Screen
RQC-2017-021 Version-1 1/9/18
6
of 8
Page
Trane
2018 BAYSENS924 Thermostat Programming - Quick Reference
Time Format: AM/PM .
Time: Current Time
Year: Current Year
Month: Current Month
Day: Current Day
Weekday: Current Weekday
Clock: Schedule Menu: From 1/2 - Set Up Menu
Clock
Occupancy CM: Loc. Occ.
Where Occupancy is determined by the schedule
Schedule Type: 5 + 2 .
(Weekdays + Weekend)
Note: Adjust schedule type (7 day or 5+2) based on
restaurant schedule gathered earlier
Program the schedule for the Dining Room
and Kitchen thermostats
Note: Up to 3 occupied / unoccupied events are allowed
Options
Schedule
RQC-2017-021 Version-1 1/9/18
7
of 8
Page
Trane
2018 BAYSENS924 Thermostat Programming - Quick Reference
Kitchen - Weekdays
Event Schedule Time
Occupied 1 12:00 AM
Unoccupied 1 2:00 AM
Occupied 2 7:00 AM
Unoccupied 2 11:59 PM
Occupied 3 Not Used
Unoccupied 3 Not Used
Kitchen - Weekends
Event Schedule Time
Occupied 1 12:00 AM
Unoccupied 1 4:00 AM
Occupied 2 7:00 AM
Unoccupied 2 10:00 PM
Occupied 3 10:01 PM
Unoccupied 3 11:59 PM
Usearrowkeytoaccessweekendschedules
Note:TheFanmustbein“ON”Mode-“Occupied”ModeduringmeperiodswhentheExhaustFansareinoperaon.
Thisscheduleassumesdrivethroughclosingat1:00amandcleanupbeingcompleteat2:00am.
Therestaurantwouldbeunoccupiedat2:00amunl7:00am.
DriveThruisopenunl3:00amandcleanupis
competein1hour.Restaurantisunoccupiedat4:00am
Typical Schedule:
Installer to adjust based on operator schedule


Usearrowkeytoaccessweekendschedules
Dining Room - Weekdays
Event Schedule Time
Occupied 1 12:00 AM
Unoccupied 1 2:00 AM
Occupied 2 7:00 AM
Unoccupied 2 10:00 PM
Occupied 3 10:01 PM
Unoccupied 3 11:59 PM
Dining Room - Weekends
Event Schedule Time
Occupied 1 12:00 AM
Unoccupied 1 4:00 AM
Occupied 2 7:00 AM
Unoccupied 2 10:00 PM
Occupied 3 10:01 PM
Unoccupied 3 11:59 PM
RQC-2017-021 Version-1 1/9/18
8
of 8
Page
Troubleshoong:




Assistance:

Ruthann McCracken



Oce:
Email:
Trane
2018 BAYSENS924 Thermostat Programming - Quick Reference
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Trane BAYSENS924 Quick Programming Manual

Type
Quick Programming Manual

Trane BAYSENS924 is a thermostat and remote sensor designed to work with the Trane Voyager EFlex unit. It allows for precise temperature control and scheduling, helping to optimize energy efficiency and comfort in commercial buildings. With its advanced features, the BAYSENS924 offers:

  • Customizable programming: Create detailed schedules to align with your business hours and occupancy patterns, ensuring the right temperature at the right time.

  • Remote monitoring: Access and adjust temperature settings remotely, providing flexibility and convenience for managing multiple zones or buildings.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI