Fantech PROPLUS-L Installation guide

Type
Installation guide

This manual is also suitable for

Installation Manual
Manuel d’opération
Manual de Instalación
Item #: 153509
Rev Date: 2019-07-11
ProPLUS(-L) Series
Bathroom Exhaust Fan with Motion and Humidity Sensors
Ventilateur de salle de bain avec capteurs de mouvement et d'humidité
Extractor de baño con sensores de movimiento y humeda
Package includes:
Fantech Exhaust Fan, 1 pc
EZ Mounting Bracket, 1 pc
Mounting screws, 7 pcs
L'ensemble comprend:
Ventilateur extracteur ou ventilateur à éclairage
Fantech, 1 pc
Supports de fixation, 1 pc
Vis de fixation, 7 pcs
El paquete incluye:
Extractor de aire o un extractor con luces
Fantech, 1 pc
Ménsulas de montaje, 1 pc
Tornillos de montaje, 7 pc
Technical / Customer Support:
United States Tel.: 800 747 1762
Canada Tel.: 1 800 565 3548
Mexico Tel.: +52 55 9126 3455
2
fantech
Note Warning /
Important
note
Information Technical
information
Practical tip
1. Use this unit in the manner intended by the
manufacturer. If you have any questions,
please contact the manufacturer.
2. Before servicing or cleaning unit, switch
power off at service panel and lock the
service disconnecting means to prevent
power from being switched on accidentally.
When the service disconnecting means
cannot be locked, securely fasten a
prominent warning device, such as a tag,
to the service panel.
3. Installation work and electrical wiring must
be done by qualified person(s) in
accordance with all applicable codes and
standards, including fire-rated
construction.
4. Sufficient air is needed for proper
combustion and exhausting of gases
through the flue (chimney) of fuel burning
equipment to prevent back drafting. Follow
the heating equipment manufacturer’s
guideline and safety standards such as
those published by the National Fire
Protection Association (NFPA), and the
American Society for Heating, Refrigeration
and Air Conditioning Engineers (ASHRAE),
and the local code authorities.
5. When cutting or drilling into wall or ceiling,
do not damage electrical wiring and other
hidden utilities.
6. Ducted fans must always be vented to the
outdoors.
7. If this unit is to be installed over a tub or
shower, it must be marked as appropriate
for the application and be connected to a
GFCI (Ground Fault Circuit Interrupter) –
protected branch circuit.
8. NEVER place a switch where it can be
reached from a tub or shower.
9. This fan must be properly grounded.
10. Do not use in the cooking area (Figure. 1).
11. Do not block the air intakes or exhaust.
12. Power supply wiring is to be No. 14 AWG
wire or larger (suitable for at least 90°C
(190°F) ).
13. Not for use outdoors.
14. The fan must not be installed in a ceiling
with an “R” rating greater than 40.
15. The fan is type IC (Inherently Protected).
16. To reduce the risk of injury, install the fan
at least 7 feet (2.1m) above the floor.
17. Acceptable for use over a shower or tub
when installed in a GFCI protected branch
circuit.
18. The fan should not be turned on or off
rapidly.
19. Do not clean the fan with corrosive
chemicals or water in excess of 60° C
(140° F).
20. If the fan is not operating properly, shut
the power off immediately, and have a
certified installer inspect it and have it
serviced as required.
21. Fan must be mounted to structural
members that are strong enough to
support the fan’s weight.
22. Do not allow foreign objects to enter the
fan; this could result in electric shock or
fan damage.
Caution:
1. For general ventilating use only. Do not use
to exhaust hazardous or explosive
materials and vapors.
2. This product is designed for installation in
flat ceilings only. Do not install it in a
sloping ceiling or in a wall.
3. To avoid motor bearing damage and noisy
unbalanced impellers keep construction
material / dust from entering the fan.
4. Please read specification label on the
product for further information and
requirements.
Figure 1
Cooking area
Do not install above or
inside this area
45°45°
Floor
Cooking
Equipment
Read and Save these instructions for future reference.
Before installation, to reduce the risk of fire, electric shock, or injury to persons, observe the following:
5
fantech
Dimensions • Dimensiones
Specifications
Fan Specifications
Model Power Consumption (W) Airflow (CFM)
Power Motor
ProPLUS 120V/60 Hz 25 80 / 90 / 110 / 140
ProPLUS -L 120V/60 Hz 30 80 / 90 / 110 / 140
Spécification du ventilateur
Modèle Consommation d'énergie (W) Débit d'air (pi
3
/min)
Puissance Moteur
ProPLUS 120V/60 Hz 25 80 / 90 / 110 / 140
ProPLUS -L 120V/60 Hz 30 80 / 90 / 110 / 140
Especificaciones del extractor
Modelo Consumo de energía (W) Flujo de aire (CFM)
Alimentación Motor
ProPLUS 120V/60 Hz 25 80 / 90 / 110 / 140
ProPLUS -L 120V/60 Hz 30 80 / 90 / 110 / 140
Spécifications
Especificaciones
7-5/8"
11-3/8"
10-1/2"
13"
13-3/4"
289 mm
267 mm
350 mm
330 mm
194 mm
11-3/8"
10-1/2"
7-5/8"
13"
13-3/4"
289 mm
267 mm
330 mm
350 mm
194 mm
6
fantech
Assembly
The ducting from this fan to the outside of the building has a strong effect on the air ow, noise and energy use of the fan. Use the
shortest, straightest duct routing possible for best performance, and avoid installing the fan with smaller ducts than recommended.
Insulation around the ducts can reduce energy loss and inhibit mold growth. Fans installed with existing ducts may not achieve their
rated air ow.
Please remove duct assembly and blower assembly before installation.
EZ mounting frame Housing Duct Assembly Blower Assembly
1. Install EZ Mounting Frame
2. Install Duct And Housing
Attach duct assembly to frame using provided (1) 1/4" screw. Before
inserting the housing, first pull the locking tab located opposite of the
duct collar and push housing into the frame. Release the locking tab
so that it temporarily holds the housing in place. To secure permanently
in place, use the remaining (2) 1-inch screws as shown in the illustration.
3. Install Blower Assembly (Only necessary if installing a contractor pack)
Install blower assembly in housing and secure with screws.
Tab
Tab Tab
slot
hole
hole hole
7
fantech
4. Install Junction Box And Ductwork
Remove junction box cover and connect electrical wiring (refer to wiring diagram. Note:
1/2" strain relief not provided). Finish by replacing the junction box cover. Connect the
round ductwork (not included) to the damper/duct connector, and run the ductwork to a
roof or wall cap (not included). Using tape (not included), secure all the ductwork
connections so that they are air tight.
The ducting from this fan to the outside of building has a strong effect on the air flow,
noise and energy use of the fan. Use the shortest, straightest duct routing possible for
best performance, and avoid installing the fan with smaller ducts than recommended.
Insulation around the ducts can reduce energy loss and inhibit mold growth. Fans
installed with existing ducts may not achieve their rated air flow.
Wiring diagram
Run 120 Vac house wiring to the location of the fan. Use only UL-approved connectors (not included) to attach the field wiring to the
wiring plate. Refer to the wiring diagram, and connect the wires as shown.
Install the Grille
To attach the grille assembly to the fan housing. Insert the sensor plug into the mating
receptacle on the power box. Pinch the grille springs on the sides of the grille assembly,
and position the grille into the housing with the grille springs in the appropriate slots.
Push the grille assembly towards the ceiling to secure.
FAN
LIGHT
SWITCH BOX
WHITE
Fan
N
Sensor
GREEN
UNIT
LIGHT
SWITCH
FAN
SWITCH
BLACK
RED
WHITE
WHITE
LINE
IN
CONTROL
CIRCUIT
Low CFM
switch
Humidity sensor
switch
S
BLACK
L1: light (Red)
L1: Mtr (Black)
N: Light & Mtr (White)
: Ground (Green)
2
8
fantech
Maintenance
For quiet and efficient operation, long life, and attractive appearance - lower or remove grille and vacuum interior of unit with the dusting brush
attachment.The motor is permanently lubricated and never needs oiling. If the motor bearings are making excessive or unusual noises, replace
the motor with the exact service motor. The impeller should also be replaced.
Keep all electrical components away from water. Do not use corrosive chemicals or water in excess of 60C (140°F) to clean plastic
parts.
Operation
See “Connect Wiring” for details.
The control box, located inside the fan housing, has three separate
adjustments:
(1) The low airflow knob(s) adjusts the lower airflow from 40CFM up to
the air flow rate of the high fan speed determined by the toggle switch
setting.
(2) The Humidity Sensor Knob set user adjustable setpoint (50%-100%
relative humidity).
(3) The toggle switch will adjust the upper fan speed setting from
80 to 140 CFM.
MOTION SENSOR
The fan will run continuously at the pre-set low speed. When motion is
detected, the fan speed increases to high speed. When the person exits the
area, the fan remains working at high speed until the delay time has passed
(20 minutes). After the time delay, the fan speed is reduced to the
continuous ventilation rate. Installation distance: 7 to 9 feet. Sensing range
is within the cone angle of 90°
HUMIDITY SENSOR OPERATION
The humidity-sensing fan uses a sophisticated humidity sensor that responds
to: (a) rapid to moderate (user-adjustable) increases in humidity or (b)
humidity above a user-adjustable set-point (50%-100% relative humidity).
The fan run continuously, at a preset lower level (set by the low speed
control Knob) and automatically boost up to high speed when environmental
conditions change. After delay timer (20 minutes), the fan returns to the
default low speed. If the fan continuously responds to changing environmental
conditions, “H” (means “humidity”) adjustment may be required. This figure is
factory-set for about 75% (Ambient temperature of 25°).
SENSITIVITY ADJUSTMENT
The “H” has been factory set for most shower applications. However, if the
fan is in a tub area or is being used for dampness control, the “H” may need
to be increased toward maximum “+”. If the control is responding too often
to changing environmental conditions, movement toward less “-” “H” may be
required. To adjust the “H”:
1. Disconnect power at service entrance.
2. Through the grille, locate the slot marked “H”.
3. Carefully rotate the “H” adjustment toward “+” or “-”.
4. Turn on power and check operation by turning on the shower or other
humidity source until the fan turns on.
5. Repeat above steps if necessary.
When the temperature changes, humidity sensor values will have deviation.
7 to 9 feet
Gesture area
sensor 90°
S H
~140
1 2 3
Switch
position
Airflow (CFM)
@0.1 INWC
~110
1 2 3
~90
1 2 3
~80
Hi Spd
Speed
setting
Med/HiMed/LoLo Spd
1 2
3
Speed control
for low speed
Humidity
HVI Certified performance based on HVI Procedures
915, 916, and 920.
15
fantech
Five (5) Year Warranty
This warranty supersedes all prior warranties
DURING ENTIRE WARRANTY PERIOD:
Fantech will repair or replace any part which has a factory defect in
workmanship or material. Product may need to be returned to the
Fantech factory, together with a copy of the bill of sale and identified
with RMA number.
FOR FACTORY RETURN YOU MUST:
Have a Return Materials Authorization (RMA) number. This may be
obtained by calling Fantech either in the USA at 1.800.747.1762 or
in CANADA at 1.800.565.3548. Please have bill of sale available.
The RMA number must be clearly written on the outside of the
carton, or the carton will be refused.
All parts and/or product will be repaired/replaced and shipped back to
buyer; no credit will be issued.
OR
The Distributor may place an order for the warranty part and/or product
and is invoiced. The Distributor will receive a credit equal to the invoice
only after product is returned prepaid and verified to be defective.
FANTECH WARRANTY TERMS DO NOT PROVIDE FOR REPLACEMENT
WITHOUT CHARGE PRIOR TO INSPECTION FOR A DEFECT.
REPLACEMENTS ISSUED IN ADVANCE OF DEFECT INSPECTION ARE
INVOICED, AND CREDIT IS PENDING INSPECTION OF RETURNED
MATERIAL. DEFECTIVE MATERIAL RETURNED BY END USERS SHOULD
NOT BE REPLACED BY THE DISTRIBUTOR WITHOUT CHARGE TO THE
END USER, AS CREDIT TO DISTRIBUTOR’S ACCOUNT WILL BE
PENDING INSPECTION AND VERIFICATION OF ACTUAL DEFECT BY
FANTECH.
THE FOLLOWING WARRANTIES DO NOT APPLY:
Damages from shipping, either concealed or visible. Claim must be
filed with freight company.
• Damages resulting from improper wiring or installation.
Damages or failure caused by acts of God, or resulting from improper
consumer procedures, such as:
1. Improper maintenance
2. Misuse, abuse, abnormal use, or accident, and
3. Incorrect electrical voltage or current.
Removal or any alteration made on the Fantech label control number
or date of manufacture.
Any other warranty, expressed, implied or written, and to any
consequential or incidental damages, loss or property, revenues, or
profit, or costs of removal, installation or reinstallation, for any breach
of warranty.
WARRANTY VALIDATION
• The user must keep a copy of the bill of sale to verify purchase date.
These warranties give you specific legal rights, and are subject to an
applicable consumer protection legislation. You may have additional
rights which vary from state to state.
This warranty does not apply to any Fantech product or part which has
failed as a result of faulty installation or abuse, incorrect electrical
connections or alterations made by others, or use under abnormal
operating conditions or misapplication of the product or parts. We will
not approve for payment any repair not made by us or our authorized
agent without prior written consent. The foregoing shall constitute our
sole and exclusive warranty and our sole exclusive liability, and is in lieu
of any other warranties, whether written, oral, implied or statutory.
There are no warranties which extend beyond the description on the
page hereof. In no event, whether as a result of breach of contract, or
warranty or alleged negligence, defect incorrect advice or other causes,
shall Fantech be liable for special or consequential damages, including,
but not limited to, loss of profits or revenue, loss of use of equipment or
any other associated equipment, cost of capital, cost of substitute
equipment, facilities or services, downtime costs, or claims of
customers of purchase for such damages. Fantech neither assumes or
authorizes any person to assume for it any other liability in connection
with the sale of product(s) or part(s). Some jurisdictions do not allow the
exclusion or limitation of incidental or consequential damages so the
above limitations and exclusions may not apply to you.
Limitation of Warranty and Liability Warning
Fantech products are designed and manufactured to provide reliable
performance, but they are not guaranteed to be 100% free from
defects. Even reliable products will experience occasional failures and
this possibility should be recognized by the user. If these products are
used in a life support ventilation system where failure could result in loss
or injury, the user should provide adequate backup ventilation,
supplementary natural ventilation, failure alarm system, or acknowledge
willingness to accept the risk of such loss or injury.
WARRANTY
Notes/Notas
Fantech reserves the right to make technical changes.
For updated documentation please refer to www.fantech.net
Fantech®
Fantech se réserve le droit de faire des changements
techniques. Pour de la documentation à jour, s'il vous plaît se
référer au www.fantech.net
Fantech se reserva el derecho de hacer modicaciones
técnicas en cualquier momento. Para obtener la documen-
tación actualizada, por favor consulte www.fantech.net
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Fantech PROPLUS-L Installation guide

Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI