Siemens US2:QA120AFCP User guide

Type
User guide

This manual is also suitable for

Siemens US2:QA120AFCP is a 2-Pole, 120 Amp AFCI Circuit Breaker that is designed to protect your home from electrical fires. This device is Underwriters Laboratories (UL) listed and complies with part 15 of Federal Communications Commission (FCC) regulations. It features a Push-to-Test (PTT) button that allows you to verify the functionality of the AFCI. The PTT button is the only method recommended to verify the functionality of the AFCIs by National Electrical Manufacturers Association (NEMA) and UL.

Siemens US2:QA120AFCP is a 2-Pole, 120 Amp AFCI Circuit Breaker that is designed to protect your home from electrical fires. This device is Underwriters Laboratories (UL) listed and complies with part 15 of Federal Communications Commission (FCC) regulations. It features a Push-to-Test (PTT) button that allows you to verify the functionality of the AFCI. The PTT button is the only method recommended to verify the functionality of the AFCIs by National Electrical Manufacturers Association (NEMA) and UL.

Answers for infrastructure.
AFCI troubleshooting checklist
www.usa.siemens.com/afci • 1-800-241-4453
For both 1- and 2-pole breakers, LED indications
will appear for 5 seconds each time the AFCI is
turned “ON” and will display each time the beaker
is reset for up to 30 days after the last trip. The
last known trip condition can cleared by the
following process:
1. Turn the AFCI to the “OFF” position.
2. Press and hold Push-to-Test (PTT) button(s).
3. Turn the AFCI to the “ON” position.
4. Release PTT button(s) within 3 seconds.
LED 1
LED 2
Test
button
LED 1
LED 2
LED 3
Test
buttons
Tips and Tricks
Route wires in strategic areas so homeowners and other trades are less likely
to pierce through a wire.
If possible, perform work after the other trades, i.e. HVAC and plumbing,
have completed.
Wire receptacles around the screw instead of backstabbing.
Use properly maintained tools, i.e. sharp blades.
Ensure a tight connection between light sockets and light bulb bases.
Do not overload circuit with excessive amounts of electronics.
Afrm furniture is not on or pushing against electrical wires.
Watch for blackened plugs, very damaged wires, or noisy electronics.
Electronics should be Underwriters Laboratories (UL) listed, or equivalent, and
comply with part 15 of Federal Communications Commission (FCC) regulations.
Protect electronics on surge protectors.
The PTT button is the only method recommended to verify the functionality of the
AFCIs by National Electrical Manufacturers Association (NEMA) and UL.
Test AFCIs once per month to ensure proper working conditions.
RPMR-COMBO-0812
1-Pole CAFCI circuit breaker
LED indicators
Last known
trip condition Troubleshooting1 2
Off Off Overcurrent
Ensure current on the circuits does not
exceed the current rating for the breaker.
On Off Arc fault
Check wiring for the parallel and series arc
faults. Check devices for series arc faults. Use
Intelli-Arc to assist and accelerate diagnosis.
On On Arc fault to ground
Check wiring, switches, and receptacles for
possible ground leakage. Use Intelli-Arc or
circuit tester to troubleshoot. Using safe
electrical practices, systematically identify
the source of the ground fault.
2-Pole CAFCI circuit breaker
LED indicators
Last known
trip condition Troubleshooting1 2 3
Off Off Off Overcurrent
Ensure current on the circuits does not
exceed the current rating for the breaker.
On Off Off Arc fault (leg A)
Check wiring for the parallel and series arc
faults. Check devices for series arc faults.
Use Intelli-Arc to assist and accelerate
diagnosis.
Off Off On Arc fault (leg B)
On On On Arc fault to ground
Check wiring, switches, and receptacles for
possible ground leakage. Use Intelli-Arc or
circuit tester to troubleshoot. Using safe
electrical practices, systematically identify
the source of the ground fault.
  • Page 1 1
  • Page 2 2

Siemens US2:QA120AFCP User guide

Type
User guide
This manual is also suitable for

Siemens US2:QA120AFCP is a 2-Pole, 120 Amp AFCI Circuit Breaker that is designed to protect your home from electrical fires. This device is Underwriters Laboratories (UL) listed and complies with part 15 of Federal Communications Commission (FCC) regulations. It features a Push-to-Test (PTT) button that allows you to verify the functionality of the AFCI. The PTT button is the only method recommended to verify the functionality of the AFCIs by National Electrical Manufacturers Association (NEMA) and UL.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI